Files
templates-default/Morningstar_ProStar_PWM_by_SNMP.yaml
T

1217 lines
52 KiB
YAML

zabbix_export:
version: '7.0'
template_groups:
- uuid: 36bff6c29af64692839d077febfc7079
name: 'Templates/Network devices'
templates:
- uuid: 24bed6339f0a492fab86fe757394b937
template: 'Morningstar ProStar PWM by SNMP'
name: 'Morningstar ProStar PWM by SNMP'
description: |
MIBs used:
PROSTAR-PWM
Generated by official Zabbix template tool "Templator"
vendor:
name: Zabbix
version: 7.0-2
groups:
- name: 'Templates/Network devices'
items:
- uuid: 953fb8b3c23f420bb6132874ce3e33e2
name: 'Array: Voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.6.31.0]'
key: 'array.voltage[arrayVoltage.0]'
value_type: FLOAT
units: V
description: |
MIB: PROSTAR-PWM
Description:Array Voltage
Scaling Factor:1.0
Units:V
Range:[0, 80]
Modbus address:0x0013
tags:
- tag: component
value: array
- uuid: a80ad3ace9b14446bc5fd5d6aaa5af87
name: 'Battery: Battery Voltage discovery'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.6.30.0]'
key: 'battery.voltage.discovery[batteryTerminalVoltage.0]'
delay: 15m
history: '0'
value_type: FLOAT
units: V
description: 'MIB: PROSTAR-PWM'
tags:
- tag: component
value: battery
- tag: component
value: discovery
- tag: component
value: raw
- uuid: 148008b117c94155ba81600e3050ab25
name: 'Battery: Charge Current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.6.33.0]'
key: 'charge.current[chargeCurrent.0]'
value_type: FLOAT
units: A
description: |
MIB: PROSTAR-PWM
Description:Charge Current
Scaling Factor:1.0
Units:A
Range:[0, 40]
Modbus address:0x0011
tags:
- tag: component
value: battery
- uuid: a7ae2d3b911e4bb5a7eeb770470245a5
name: 'Battery: Charge State'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.6.45.0]'
key: 'charge.state[chargeState.0]'
value_type: FLOAT
description: |
MIB: PROSTAR-PWM
Description:Control State
Modbus address:0x0021
0: Start
1: NightCheck
2: Disconnect
3: Night
4: Fault
5: Bulk
6: Pwm
7: Float
8: Equalize
valuemap:
name: 'ProStar PWM charge state'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
tags:
- tag: component
value: battery
triggers:
- uuid: f12fc2c1a7a142a287304c18bafa1181
expression: 'last(/Morningstar ProStar PWM by SNMP/charge.state[chargeState.0])={$CHARGE.STATE.CRIT}'
name: 'Morningstar ProStar PWM: Battery: Device charge in critical state'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: adf8cf02aa1e42fa84e1f11ddae4df01
expression: 'last(/Morningstar ProStar PWM by SNMP/charge.state[chargeState.0])={$CHARGE.STATE.WARN}'
name: 'Morningstar ProStar PWM: Battery: Device charge in warning state'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar ProStar PWM: Battery: Device charge in critical state'
expression: 'last(/Morningstar ProStar PWM by SNMP/charge.state[chargeState.0])={$CHARGE.STATE.CRIT}'
tags:
- tag: scope
value: notice
- uuid: 8acd2e7944694a828cf9b739b75513d9
name: 'Counter: Charge Amp-hours'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.6.49.0]'
key: 'counter.charge_amp_hours[ahChargeResettable.0]'
value_type: FLOAT
units: Ah
description: |
MIB: PROSTAR-PWM
Description:Ah Charge (Resettable)
Scaling Factor:0.1
Units:Ah
Range:[0.0, 4294967294]
Modbus addresses:H=0x0026 L=0x0027
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
tags:
- tag: component
value: counter
- uuid: 0e7124df3f2b4298b1a13576d0b2d5e7
name: 'Counter: Charge KW-hours'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.6.51.0]'
key: 'counter.charge_kw_hours[kwhChargeResettable.0]'
value_type: FLOAT
units: '!kWh'
description: |
MIB: PROSTAR-PWM
Description:Kilowatt Hours Charge (Resettable)
Scaling Factor:1.0
Units:kWh
Range:[0.0, 65535]
Modbus address:0x002A
tags:
- tag: component
value: counter
- uuid: 104a7db1c27d40b3bbee506f7f922393
name: 'Counter: Load Amp-hours'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.6.56.0]'
key: 'counter.load_amp_hours[ahLoadResettable.0]'
value_type: FLOAT
units: Ah
description: |
MIB: PROSTAR-PWM
Description:Ah Load (Resettable)
Scaling Factor:0.1
Units:Ah
Range:[0.0, 4294967294]
Modbus addresses:H=0x0032 L=0x0033
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
tags:
- tag: component
value: counter
- uuid: dcade8607cf142a2b88333f9880448fc
name: 'Load: Current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.6.34.0]'
key: 'load.current[loadCurrent.0]'
value_type: FLOAT
units: A
description: |
MIB: PROSTAR-PWM
Description:Load Current
Scaling Factor:1.0
Units:A
Range:[0, 60]
Modbus address:0x0016
tags:
- tag: component
value: load
- uuid: 14b3ca3869374f54a467e5e9017f918a
name: 'Load: State'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.6.53.0]'
key: 'load.state[loadState.0]'
value_type: FLOAT
description: |
MIB: PROSTAR-PWM
Description:Load State
Modbus address:0x002E
0: Start
1: Normal
2: LvdWarning
3: Lvd
4: Fault
5: Disconnect
6: NormalOff
7: Override
8: NotUsed
valuemap:
name: 'ProStar PWM load state'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
tags:
- tag: component
value: load
triggers:
- uuid: 7a8bf4420b6b48ab8a5bc999eecae760
expression: 'last(/Morningstar ProStar PWM by SNMP/load.state[loadState.0])={$LOAD.STATE.CRIT:"lvd"} or last(/Morningstar ProStar PWM by SNMP/load.state[loadState.0])={$LOAD.STATE.CRIT:"fault"}'
name: 'Morningstar ProStar PWM: Load: Device load in critical state'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 5152f9cd4ee34be485f3cb0a0f60afd5
expression: 'last(/Morningstar ProStar PWM by SNMP/load.state[loadState.0])={$LOAD.STATE.WARN:"lvdWarning"} or last(/Morningstar ProStar PWM by SNMP/load.state[loadState.0])={$LOAD.STATE.WARN:"override"}'
name: 'Morningstar ProStar PWM: Load: Device load in warning state'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar ProStar PWM: Load: Device load in critical state'
expression: 'last(/Morningstar ProStar PWM by SNMP/load.state[loadState.0])={$LOAD.STATE.CRIT:"lvd"} or last(/Morningstar ProStar PWM by SNMP/load.state[loadState.0])={$LOAD.STATE.CRIT:"fault"}'
tags:
- tag: scope
value: notice
- uuid: cccc0976a62b47b1a558d521704c125d
name: 'Load: Voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.6.32.0]'
key: 'load.voltage[loadVoltage.0]'
value_type: FLOAT
units: V
description: |
MIB: PROSTAR-PWM
Description:Load Voltage
Scaling Factor:1.0
Units:V
Range:[0, 80]
Modbus address:0x0014
tags:
- tag: component
value: load
- uuid: 7c1c1e03425c4b4bb176cf45458b916a
name: 'Status: Alarms'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.6.59.0]'
key: 'status.alarms[alarms.0]'
history: 1h
value_type: TEXT
trends: '0'
description: |
MIB: PROSTAR-PWM
Description:Alarms
Modbus addresses:H=0x0038 L=0x0039
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
- type: JAVASCRIPT
parameters:
- |
var FIELDS = [
'rtsOpen',
'rtsShorted',
'rtsDisconnected',
'heatsinkTempSensorOpen',
'heatsinkTempSensorShorted',
'heatsinkTempLimit',
'currentLimit',
'currentMeasurementError',
'batterySenseOutOfRange',
'batterySenseDisconnected',
'uncalibrated',
'batteryTempOutOfRange',
'fp10SupplyOutOfRange',
'mosfetOpen',
'arrayCurrentOffset',
'loadCurrentOffset',
'p33SupplyOutOfRange',
'p12SupplyOutOfRange',
'hightInputVoltageLimit',
'controllerReset',
'loadLvd',
'logTimeout',
'eepromAccessFailure'
];
var flags = parseInt(value.replace(/\x20/g, ''), 16),
result = [];
for (var i = 0, f = 1 << 31 >>> 0, l = FIELDS.length; i < l; i++, f >>>= 1) {
if (flags & f) {
result.push(FIELDS[i]);
}
}
return result.length ? result.join('\n') : 'No alarms';
tags:
- tag: component
value: status
triggers:
- uuid: 67fd46f034c3486e9af3cabfc5dc8056
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","arrayCurrentOffset")=2'
name: 'Morningstar ProStar PWM: Status: Device has "arrayCurrentOffset" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 31cc0b05b83045de80a7d07f26545010
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","batterySenseDisconnected")=2'
name: 'Morningstar ProStar PWM: Status: Device has "batterySenseDisconnected" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 9e498d21bc7f4ca1937f1628f4b1ea55
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","batterySenseOutOfRange")=2'
name: 'Morningstar ProStar PWM: Status: Device has "batterySenseOutOfRange" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 8a09c7609f9a45cea5b217757a7d2e5e
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","batteryTempOutOfRange")=2'
name: 'Morningstar ProStar PWM: Status: Device has "batteryTempOutOfRange" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: b173b8ca12f8464aae6476009b4c89e8
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","controllerReset")=2'
name: 'Morningstar ProStar PWM: Status: Device has "controllerReset" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: cdbac88810ff49caa35771e661d8b312
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","currentLimit")=2'
name: 'Morningstar ProStar PWM: Status: Device has "currentLimit" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 7758388df28d4540ba393f4423fef00a
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","currentMeasurementError")=2'
name: 'Morningstar ProStar PWM: Status: Device has "currentMeasurementError" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: a56fef1f61c44ba884ec448b0d306c1d
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","eepromAccessFailure")=2'
name: 'Morningstar ProStar PWM: Status: Device has "eepromAccessFailure" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: fefea5daa03d453c8c5148ddb39997f9
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","fp10SupplyOutOfRange")=2'
name: 'Morningstar ProStar PWM: Status: Device has "fp10SupplyOutOfRange" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: c252c82aff2a4ac680965115cb2fab64
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","heatsinkTempLimit")=2'
name: 'Morningstar ProStar PWM: Status: Device has "heatsinkTempLimit" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 5b93a0a09a62481d8096ec743c2ceaff
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","heatsinkTempSensorOpen")=2'
name: 'Morningstar ProStar PWM: Status: Device has "heatsinkTempSensorOpen" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: f28e5143a238470ba93c1345c814f87d
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","heatsinkTempSensorShorted")=2'
name: 'Morningstar ProStar PWM: Status: Device has "heatsinkTempSensorShorted" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 75c84ef378984fca854b34a8ef79668c
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","hightInputVoltageLimit")=2'
name: 'Morningstar ProStar PWM: Status: Device has "hightInputVoltageLimit" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 5c1551f7e2be40e0b8b50ed263f8e293
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","loadCurrentOffset")=2'
name: 'Morningstar ProStar PWM: Status: Device has "loadCurrentOffset" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 665117c5b9b64ea09a1d661e9c40fc43
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","loadLvd")=2'
name: 'Morningstar ProStar PWM: Status: Device has "loadLvd" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: b89c002c859c419ea748b43d575e9e27
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","logTimeout")=2'
name: 'Morningstar ProStar PWM: Status: Device has "logTimeout" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 17f51e7b248b4e63934e8b529b85b2ef
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","mosfetOpen")=2'
name: 'Morningstar ProStar PWM: Status: Device has "mosfetOpen" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 75e23772250741d0b1fc1ddff2a72ef6
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","p12SupplyOutOfRange")=2'
name: 'Morningstar ProStar PWM: Status: Device has "p12SupplyOutOfRange" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: fc374c9ac9fa4f979fbff9f7c7d83565
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","p33SupplyOutOfRange")=2'
name: 'Morningstar ProStar PWM: Status: Device has "p33SupplyOutOfRange" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: fbec2a1fdbe54d8da352471acf67bad1
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","rtsDisconnected")=2'
name: 'Morningstar ProStar PWM: Status: Device has "rtsDisconnected" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 915da6e7b1cd410da9a6c68e3b4abd85
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","rtsShorted")=2'
name: 'Morningstar ProStar PWM: Status: Device has "rtsShorted" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: e8bf2213a5444e2c9923b6f093d43f75
expression: 'count(/Morningstar ProStar PWM by SNMP/status.alarms[alarms.0],#3,"like","uncalibrated")=2'
name: 'Morningstar ProStar PWM: Status: Device has "uncalibrated" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 2517d96e51c14372a0336c9a6ed5d078
name: 'Status: Array Faults'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.6.46.0]'
key: 'status.array_faults[arrayFaults.0]'
history: 1h
value_type: TEXT
trends: '0'
description: |
MIB: PROSTAR-PWM
Description:Array Faults
Modbus address:0x0022
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
- type: JAVASCRIPT
parameters:
- |
var FIELDS = [
'overcurrent',
'mosfetSShorted',
'software',
'batteryHvd',
'arrayHvd',
'customSettingsEdit',
'rtsShorted',
'rtsNoLongerValid',
'localTempSensorDamaged',
'batteryLowVoltageDisconnect',
'slaveTimeout',
'dipSwitchChanged',
'p3Fault',
];
var flags = parseInt(value.replace(/\x20/g, ''), 16),
result = [];
for (var i = 0, f = 1 << 31 >>> 0, l = FIELDS.length; i < l; i++, f >>>= 1) {
if (flags & f) {
result.push(FIELDS[i]);
}
}
return result.length ? result.join('\n') : 'No faults';
tags:
- tag: component
value: status
triggers:
- uuid: b2ff69793e124031a79a668b03678fac
expression: 'count(/Morningstar ProStar PWM by SNMP/status.array_faults[arrayFaults.0],#3,"like","arrayHvd")=2'
name: 'Morningstar ProStar PWM: Status: Device has "arrayHvd" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: a4ca36ccaa9d45ceb79303afef1c49f0
expression: 'count(/Morningstar ProStar PWM by SNMP/status.array_faults[arrayFaults.0],#3,"like","batteryHvd")=2'
name: 'Morningstar ProStar PWM: Status: Device has "batteryHvd" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: f4d1120afb13456b9d45f8795dbc30b7
expression: 'count(/Morningstar ProStar PWM by SNMP/status.array_faults[arrayFaults.0],#3,"like","batteryLowVoltageDisconnect")=2'
name: 'Morningstar ProStar PWM: Status: Device has "batteryLowVoltageDisconnect" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 9e5f2c575945458ea8a39f33cb23b833
expression: 'count(/Morningstar ProStar PWM by SNMP/status.array_faults[arrayFaults.0],#3,"like","customSettingsEdit")=2'
name: 'Morningstar ProStar PWM: Status: Device has "customSettingsEdit" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: fd904f4469324784ac2c469e64069f94
expression: 'count(/Morningstar ProStar PWM by SNMP/status.array_faults[arrayFaults.0],#3,"like","dipSwitchChanged")=2'
name: 'Morningstar ProStar PWM: Status: Device has "dipSwitchChanged" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 62076ce0967049c8bde39f71afcb85d9
expression: 'count(/Morningstar ProStar PWM by SNMP/status.array_faults[arrayFaults.0],#3,"like","localTempSensorDamaged")=2'
name: 'Morningstar ProStar PWM: Status: Device has "localTempSensorDamaged" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: ea8487afe1c14bc08f3d9fd7f75d208f
expression: 'count(/Morningstar ProStar PWM by SNMP/status.array_faults[arrayFaults.0],#3,"like","mosfetSShorted")=2'
name: 'Morningstar ProStar PWM: Status: Device has "mosfetSShorted" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: b0bb139541ae493bafc40dac9074d898
expression: 'count(/Morningstar ProStar PWM by SNMP/status.array_faults[arrayFaults.0],#3,"like","overcurrent")=2'
name: 'Morningstar ProStar PWM: Status: Device has "overcurrent" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 8af94d7ff1a84e18b10122b0e3743d45
expression: 'count(/Morningstar ProStar PWM by SNMP/status.array_faults[arrayFaults.0],#3,"like","p3Fault")=2'
name: 'Morningstar ProStar PWM: Status: Device has "p3Fault" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: b41cb2e05acb40f59efa50a25f66cd62
expression: 'count(/Morningstar ProStar PWM by SNMP/status.array_faults[arrayFaults.0],#3,"like","rtsNoLongerValid")=2'
name: 'Morningstar ProStar PWM: Status: Device has "rtsNoLongerValid" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: d99c3f126c7e480cb4fcc705349eb61d
expression: 'count(/Morningstar ProStar PWM by SNMP/status.array_faults[arrayFaults.0],#3,"like","rtsShorted")=2'
name: 'Morningstar ProStar PWM: Status: Device has "rtsShorted" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 711b28f19cb74c0faeef73263ca1fb8f
expression: 'count(/Morningstar ProStar PWM by SNMP/status.array_faults[arrayFaults.0],#3,"like","slaveTimeout")=2'
name: 'Morningstar ProStar PWM: Status: Device has "slaveTimeout" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: e4a261d750d546c7b5d5067dd9a0ec25
expression: 'count(/Morningstar ProStar PWM by SNMP/status.array_faults[arrayFaults.0],#3,"like","software")=2'
name: 'Morningstar ProStar PWM: Status: Device has "software" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 2c9f864ac33b4c2d992459c6519d045a
name: 'Status: Uptime (hardware)'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.25.1.1.0]'
key: status.hw.uptime
units: uptime
description: 'The amount of time since this host was last initialized. Note that this is different from sysUpTime in the SNMPv2-MIB [RFC1907] because sysUpTime is the uptime of the network management portion of the system.'
preprocessing:
- type: CHECK_NOT_SUPPORTED
parameters:
- '-1'
error_handler: CUSTOM_VALUE
error_handler_params: '0'
- type: MULTIPLIER
parameters:
- '0.01'
tags:
- tag: component
value: status
- uuid: 1cd47d04af104cb9ab1cd7dc745a6aea
name: 'Status: Load Faults'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.6.54.0]'
key: 'status.load_faults[loadFaults.0]'
history: 1h
value_type: TEXT
trends: '0'
description: |
MIB: PROSTAR-PWM
Description:Load Faults
Modbus address:0x002F
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
- type: JAVASCRIPT
parameters:
- |
var FIELDS = [
'externalShortCircuit',
'overcurrent',
'mosfetShorted',
'software',
'loadHvd',
'highTempDisconnect',
'dipSwitchChanged',
'customSettingsEdit',
'p3Fault'
];
var flags = parseInt(value.replace(/\x20/g, ''), 16),
result = [];
for (var i = 0, f = 1 << 31 >>> 0, l = FIELDS.length; i < l; i++, f >>>= 1) {
if (flags & f) {
result.push(FIELDS[i]);
}
}
return result.length ? result.join('\n') : 'No faults';
tags:
- tag: component
value: status
triggers:
- uuid: 99ab5f0d3014459a8cd7d137d3a1f688
expression: 'count(/Morningstar ProStar PWM by SNMP/status.load_faults[loadFaults.0],#3,"like","customSettingsEdit")=2'
name: 'Morningstar ProStar PWM: Status: Device has "customSettingsEdit" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 77752192092f4f1caceef19c3c164b72
expression: 'count(/Morningstar ProStar PWM by SNMP/status.load_faults[loadFaults.0],#3,"like","dipSwitchChanged")=2'
name: 'Morningstar ProStar PWM: Status: Device has "dipSwitchChanged" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: d2e55501d89844aeb47f7887a11754a9
expression: 'count(/Morningstar ProStar PWM by SNMP/status.load_faults[loadFaults.0],#3,"like","externalShortCircuit")=2'
name: 'Morningstar ProStar PWM: Status: Device has "externalShortCircuit" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: a6548502cfc4406098ba3129af8efcb5
expression: 'count(/Morningstar ProStar PWM by SNMP/status.load_faults[loadFaults.0],#3,"like","highTempDisconnect")=2'
name: 'Morningstar ProStar PWM: Status: Device has "highTempDisconnect" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 6e8f0127bc7b42dea9d867ab174f458c
expression: 'count(/Morningstar ProStar PWM by SNMP/status.load_faults[loadFaults.0],#3,"like","loadHvd")=2'
name: 'Morningstar ProStar PWM: Status: Device has "loadHvd" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 2a303d4712e244a9b051fb1b0247fac5
expression: 'count(/Morningstar ProStar PWM by SNMP/status.load_faults[loadFaults.0],#3,"like","mosfetShorted")=2'
name: 'Morningstar ProStar PWM: Status: Device has "mosfetShorted" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 5720e2e15e5f42099fd7de361f62c99a
expression: 'count(/Morningstar ProStar PWM by SNMP/status.load_faults[loadFaults.0],#3,"like","overcurrent")=2'
name: 'Morningstar ProStar PWM: Status: Device has "overcurrent" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 2f522d50a8124ed2a8af4d7b6417c31c
expression: 'count(/Morningstar ProStar PWM by SNMP/status.load_faults[loadFaults.0],#3,"like","p3Fault")=2'
name: 'Morningstar ProStar PWM: Status: Device has "p3Fault" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: e75abe852b9c4e1d91a1f8f83622ef64
expression: 'count(/Morningstar ProStar PWM by SNMP/status.load_faults[loadFaults.0],#3,"like","software")=2'
name: 'Morningstar ProStar PWM: Status: Device has "software" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 42f6a75d923d4262b37d85c4f7d1d322
name: 'Status: Uptime (network)'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.3.0]'
key: status.net.uptime
units: uptime
description: 'The time (in hundredths of a second) since the network management portion of the system was last re-initialized.'
preprocessing:
- type: MULTIPLIER
parameters:
- '0.01'
tags:
- tag: component
value: status
triggers:
- uuid: 16c1444a745a47e59fd22bd1a64baef3
expression: 'nodata(/Morningstar ProStar PWM by SNMP/status.net.uptime,5m)=1'
name: 'Morningstar ProStar PWM: Status: Failed to fetch data'
event_name: 'Morningstar ProStar PWM: Status: Failed to fetch data (or no data for 5m)'
priority: WARNING
description: 'Zabbix has not received data for items for the last 5 minutes.'
manual_close: 'YES'
tags:
- tag: scope
value: availability
- uuid: f4b7bfb000754a17b4719863d3755519
name: 'Battery: Target Voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.6.48.0]'
key: 'target.voltage[targetVoltage.0]'
value_type: FLOAT
units: V
description: |
MIB: PROSTAR-PWM
Description:Target Regulation Voltage
Scaling Factor:1.0
Units:V
Range:[0.0, 80.0]
Modbus address:0x0024
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
tags:
- tag: component
value: battery
- uuid: 13d3479a7b5940b5a53d5f13bea9e2d1
name: 'Temperature: Ambient'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.6.40.0]'
key: 'temp.ambient[ambientTemperature.0]'
value_type: FLOAT
units: C
description: |
MIB: PROSTAR-PWM
Description:Ambient Temperature
Scaling Factor:1.0
Units:deg C
Range:[-128, 127]
Modbus address:0x001C
tags:
- tag: component
value: temperature
- uuid: 39763f7fccd94aefb720a34871c0962b
name: 'Temperature: Battery'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.6.39.0]'
key: 'temp.battery[batteryTemperature.0]'
value_type: FLOAT
units: C
description: |
MIB: PROSTAR-PWM
Description:Battery Temperature
Scaling Factor:1.0
Units:deg C
Range:[-128, 127]
Modbus address:0x001B
tags:
- tag: component
value: temperature
triggers:
- uuid: 46eb3a0e80294a4db8324d56337ed712
expression: 'min(/Morningstar ProStar PWM by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.CRIT}'
name: 'Morningstar ProStar PWM: Temperature: Critically high battery temperature'
event_name: 'Morningstar ProStar PWM: Temperature: Critically high battery temperature (over {$BATTERY.TEMP.MAX.CRIT}C for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: c3f3ba5b2cab4481bb62fa8527554e96
expression: 'max(/Morningstar ProStar PWM by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.CRIT}'
name: 'Morningstar ProStar PWM: Temperature: Critically low battery temperature'
event_name: 'Morningstar ProStar PWM: Temperature: Critically low battery temperature (below {$BATTERY.TEMP.MIN.WARN}C for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 80aaf1de029b4d6eadce9f2a946f6dde
expression: 'min(/Morningstar ProStar PWM by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.WARN}'
name: 'Morningstar ProStar PWM: Temperature: High battery temperature'
event_name: 'Morningstar ProStar PWM: Temperature: High battery temperature (over {$BATTERY.TEMP.MAX.WARN}C for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar ProStar PWM: Temperature: Critically high battery temperature'
expression: 'min(/Morningstar ProStar PWM by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.CRIT}'
tags:
- tag: scope
value: notice
- uuid: cf1db336ea124f9a9fd6eb367f93f0e8
expression: 'max(/Morningstar ProStar PWM by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.WARN}'
name: 'Morningstar ProStar PWM: Temperature: Low battery temperature'
event_name: 'Morningstar ProStar PWM: Temperature: Low battery temperature (below {$BATTERY.TEMP.MIN.WARN}C for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar ProStar PWM: Temperature: Critically low battery temperature'
expression: 'max(/Morningstar ProStar PWM by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.CRIT}'
tags:
- tag: scope
value: notice
- uuid: 1d13bd3ea24a4fcab3cd5b7586e6033a
name: 'Temperature: Heatsink'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.6.38.0]'
key: 'temp.heatsink[heatsinkTemperature.0]'
value_type: FLOAT
units: C
description: |
MIB: PROSTAR-PWM
Description:Heatsink Temperature
Scaling Factor:1.0
Units:deg C
Range:[-128, 127]
Modbus address:0x001A
tags:
- tag: component
value: temperature
discovery_rules:
- uuid: 17148797def9484ba26b0afdcc44bfd5
name: 'Battery voltage discovery'
type: DEPENDENT
key: battery.voltage.discovery
delay: '0'
description: 'Discovery for battery voltage triggers'
item_prototypes:
- uuid: 6e4ed5ae449c48eeb328d30b76d083a2
name: 'Battery: Voltage{#SINGLETON}'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.6.30.0]'
key: 'battery.voltage[batteryTerminalVoltage.0{#SINGLETON}]'
value_type: FLOAT
units: V
description: |
MIB: PROSTAR-PWM
Description:Control State
Modbus address:0x0021
tags:
- tag: component
value: battery
trigger_prototypes:
- uuid: e89cf2b8066840c2876642f0d8db1edd
expression: 'min(/Morningstar ProStar PWM by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.CRIT}'
name: 'Morningstar ProStar PWM: Battery: Critically high battery voltage'
event_name: 'Morningstar ProStar PWM: Battery: Critically high battery voltage (over {#VOLTAGE.MAX.CRIT}V for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: capacity
- uuid: 8356aba9afb242b09902873a5f0e1d47
expression: 'max(/Morningstar ProStar PWM by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.CRIT}'
name: 'Morningstar ProStar PWM: Battery: Critically low battery voltage'
event_name: 'Morningstar ProStar PWM: Battery: Critically low battery voltage (below {#VOLTAGE.MIN.CRIT}V for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: capacity
- uuid: 77f130af976c43edb8c823de5cbd57b2
expression: 'min(/Morningstar ProStar PWM by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.WARN}'
name: 'Morningstar ProStar PWM: Battery: High battery voltage'
event_name: 'Morningstar ProStar PWM: Battery: High battery voltage (over {#VOLTAGE.MAX.WARN}V for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar ProStar PWM: Battery: Critically high battery voltage'
expression: 'min(/Morningstar ProStar PWM by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.CRIT}'
tags:
- tag: scope
value: capacity
- uuid: 6c288c8b28db4f8e95c8ad2aa8b838ef
expression: 'max(/Morningstar ProStar PWM by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.WARN}'
name: 'Morningstar ProStar PWM: Battery: Low battery voltage'
event_name: 'Morningstar ProStar PWM: Battery: Low battery voltage (below {#VOLTAGE.MIN.WARN}V for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar ProStar PWM: Battery: Critically low battery voltage'
expression: 'max(/Morningstar ProStar PWM by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.CRIT}'
tags:
- tag: scope
value: capacity
graph_prototypes:
- uuid: 8ecd4f88627a4dadb132fdbb6d911b6b
name: 'Voltage: Battery/Load{#SINGLETON}'
graph_items:
- drawtype: GRADIENT_LINE
color: 199C0D
item:
host: 'Morningstar ProStar PWM by SNMP'
key: 'battery.voltage[batteryTerminalVoltage.0{#SINGLETON}]'
- sortorder: '1'
drawtype: GRADIENT_LINE
color: F63100
item:
host: 'Morningstar ProStar PWM by SNMP'
key: 'load.voltage[loadVoltage.0]'
master_item:
key: 'battery.voltage.discovery[batteryTerminalVoltage.0]'
preprocessing:
- type: JAVASCRIPT
parameters:
- |
var v_range = [
[[0, 18], [12, 15, 11.5, 15.5]],
[[18, 36], [24, 30, 23, 31]],
[[36, 99], [48, 60, 46, 62]],
],
result = [];
for (var idx in v_range) {
if (v_range[idx][0][0] < value && value <= v_range[idx][0][1]) {
result = [{
'{#VOLTAGE.MIN.WARN}': parseInt({$VOLTAGE.MIN.WARN}) || v_range[idx][1][0],
'{#VOLTAGE.MAX.WARN}': parseInt({$VOLTAGE.MAX.WARN}) || v_range[idx][1][1],
'{#VOLTAGE.MIN.CRIT}': parseInt({$VOLTAGE.MIN.CRIT}) || v_range[idx][1][2],
'{#VOLTAGE.MAX.CRIT}': parseInt({$VOLTAGE.MAX.CRIT}) || v_range[idx][1][3],
'{#SINGLETON}': ''
}];
break;
}
}
return JSON.stringify(result);
tags:
- tag: class
value: power
- tag: target
value: morningstar
macros:
- macro: '{$BATTERY.TEMP.MAX.CRIT}'
value: '60'
description: 'Battery high temperature critical value'
- macro: '{$BATTERY.TEMP.MAX.WARN}'
value: '45'
description: 'Battery high temperature warning value'
- macro: '{$BATTERY.TEMP.MIN.CRIT}'
value: '-20'
description: 'Battery low temperature critical value'
- macro: '{$BATTERY.TEMP.MIN.WARN}'
value: '0'
description: 'Battery low temperature warning value'
- macro: '{$CHARGE.STATE.CRIT}'
value: '4'
description: fault
- macro: '{$CHARGE.STATE.WARN}'
value: '2'
description: disconnect
- macro: '{$LOAD.STATE.CRIT:"fault"}'
value: '4'
description: fault
- macro: '{$LOAD.STATE.CRIT:"lvd"}'
value: '3'
description: lvd
- macro: '{$LOAD.STATE.WARN:"disconnect"}'
value: '5'
description: disconnect
- macro: '{$LOAD.STATE.WARN:"lvdWarning"}'
value: '2'
description: lvdWarning
- macro: '{$LOAD.STATE.WARN:"override"}'
value: '7'
description: override
- macro: '{$VOLTAGE.MAX.CRIT}'
- macro: '{$VOLTAGE.MAX.WARN}'
- macro: '{$VOLTAGE.MIN.CRIT}'
- macro: '{$VOLTAGE.MIN.WARN}'
dashboards:
- uuid: eb560f95bfa3418b8b614ef066b36dde
name: 'Morningstar ProStar PWM: Overview'
pages:
- widgets:
- type: graph
width: '72'
height: '4'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'Morningstar ProStar PWM by SNMP'
name: 'Array: Voltage'
- type: STRING
name: reference
value: AAAAA
- type: graph
'y': '4'
width: '72'
height: '4'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'Morningstar ProStar PWM by SNMP'
name: 'Current: Charge/Load'
- type: STRING
name: reference
value: AAAAB
- type: graph
'y': '8'
width: '72'
height: '4'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'Morningstar ProStar PWM by SNMP'
name: 'Temperature: Ambient/Battery/Heatsink'
- type: STRING
name: reference
value: AAAAC
valuemaps:
- uuid: f94eb6ad54c44281878c7c018c6209d1
name: 'ProStar PWM charge state'
mappings:
- value: '0'
newvalue: Start
- value: '1'
newvalue: NightCheck
- value: '2'
newvalue: Disconnect
- value: '3'
newvalue: Night
- value: '4'
newvalue: Fault
- value: '5'
newvalue: Bulk
- value: '6'
newvalue: Pwm
- value: '7'
newvalue: Float
- value: '8'
newvalue: Equalize
- uuid: f0be8765c74e4c4788d4ff99a6c5ccd4
name: 'ProStar PWM load state'
mappings:
- value: '0'
newvalue: Start
- value: '1'
newvalue: Normal
- value: '2'
newvalue: LvdWarning
- value: '3'
newvalue: Lvd
- value: '4'
newvalue: Fault
- value: '5'
newvalue: Disconnect
- value: '6'
newvalue: NormalOff
- value: '7'
newvalue: Override
- value: '8'
newvalue: NotUsed
triggers:
- uuid: dea364bf454746bca6be38d7e0759d06
expression: '(last(/Morningstar ProStar PWM by SNMP/status.hw.uptime)>0 and last(/Morningstar ProStar PWM by SNMP/status.hw.uptime)<10m) or (last(/Morningstar ProStar PWM by SNMP/status.hw.uptime)=0 and last(/Morningstar ProStar PWM by SNMP/status.net.uptime)<10m)'
name: 'Morningstar ProStar PWM: Status: Device has been restarted'
event_name: 'Morningstar ProStar PWM: Status: Device has been restarted (uptime < 10m)'
priority: INFO
description: 'Uptime is less than 10 minutes.'
manual_close: 'YES'
tags:
- tag: scope
value: notice
graphs:
- uuid: 730d1e1e43224d1ea7b08f53988a7a60
name: 'Array: Voltage'
graph_items:
- drawtype: GRADIENT_LINE
color: 199C0D
item:
host: 'Morningstar ProStar PWM by SNMP'
key: 'array.voltage[arrayVoltage.0]'
- uuid: 252a40cfba4242deac69f8ed77a04b84
name: 'Current: Charge/Load'
graph_items:
- drawtype: GRADIENT_LINE
color: 199C0D
item:
host: 'Morningstar ProStar PWM by SNMP'
key: 'charge.current[chargeCurrent.0]'
- sortorder: '1'
drawtype: GRADIENT_LINE
color: F63100
item:
host: 'Morningstar ProStar PWM by SNMP'
key: 'load.current[loadCurrent.0]'
- uuid: 94e4d2db752b4c54a8b497516b515fe0
name: 'Temperature: Ambient/Battery/Heatsink'
graph_items:
- drawtype: GRADIENT_LINE
color: 199C0D
item:
host: 'Morningstar ProStar PWM by SNMP'
key: 'temp.ambient[ambientTemperature.0]'
- sortorder: '1'
drawtype: GRADIENT_LINE
color: F63100
item:
host: 'Morningstar ProStar PWM by SNMP'
key: 'temp.battery[batteryTemperature.0]'
- sortorder: '2'
drawtype: GRADIENT_LINE
color: 00611C
item:
host: 'Morningstar ProStar PWM by SNMP'
key: 'temp.heatsink[heatsinkTemperature.0]'