1314 lines
56 KiB
YAML
1314 lines
56 KiB
YAML
zabbix_export:
|
|
version: '7.0'
|
|
template_groups:
|
|
- uuid: 36bff6c29af64692839d077febfc7079
|
|
name: 'Templates/Network devices'
|
|
templates:
|
|
- uuid: b84324c2a40a496dbbb379bbf5dde8d5
|
|
template: 'Morningstar ProStar MPPT by SNMP'
|
|
name: 'Morningstar ProStar MPPT by SNMP'
|
|
description: |
|
|
MIBs used:
|
|
PROSTAR-MPPT
|
|
|
|
Generated by official Zabbix template tool "Templator"
|
|
vendor:
|
|
name: Zabbix
|
|
version: 7.0-3
|
|
groups:
|
|
- name: 'Templates/Network devices'
|
|
items:
|
|
- uuid: a517a7aafbab426eb6ced8d5f57c1fa4
|
|
name: 'Array: Sweep Pmax'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.64.0]'
|
|
key: 'array.sweep_pmax[arrayMaxPowerSweep.0]'
|
|
value_type: FLOAT
|
|
units: W
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Array Max. Power (sweep)
|
|
Description:Array Max. Power (last sweep)
|
|
Scaling Factor:1.0
|
|
Units:W
|
|
Range:[0.0, 500]
|
|
Modbus address:0x003E
|
|
tags:
|
|
- tag: component
|
|
value: array
|
|
- uuid: 7714c76013e341f8b6753cc5a50a960f
|
|
name: 'Array: Sweep Vmp'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.63.0]'
|
|
key: 'array.sweep_vmp[arrayVmp.0]'
|
|
value_type: FLOAT
|
|
units: V
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Array Vmp
|
|
Description:Array Max. Power Point Voltage
|
|
Scaling Factor:1.0
|
|
Units:V
|
|
Range:[0.0, 5000.0]
|
|
Modbus address:0x003D
|
|
tags:
|
|
- tag: component
|
|
value: array
|
|
- uuid: 379ab969ad784968a1090ff98f5801ff
|
|
name: 'Array: Sweep Voc'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.65.0]'
|
|
key: 'array.sweep_voc[arrayVoc.0]'
|
|
value_type: FLOAT
|
|
units: V
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Array Voc
|
|
Description:Array Open Circuit Voltage
|
|
Scaling Factor:1.0
|
|
Units:V
|
|
Range:[0.0, 80.0]
|
|
Modbus address:0x003F
|
|
tags:
|
|
- tag: component
|
|
value: array
|
|
- uuid: 41a1118e1be3417daa79faace733d861
|
|
name: 'Array: Voltage'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.31.0]'
|
|
key: 'array.voltage[arrayVoltage.0]'
|
|
value_type: FLOAT
|
|
units: V
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Array Voltage
|
|
Description:Array Voltage
|
|
Scaling Factor:1.0
|
|
Units:V
|
|
Range:[0, 80]
|
|
Modbus address:0x0013
|
|
tags:
|
|
- tag: component
|
|
value: array
|
|
- uuid: fe5c3b724e894573acdaf522a2213adb
|
|
name: 'Battery: Battery Voltage discovery'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.30.0]'
|
|
key: 'battery.voltage.discovery[batteryTerminalVoltage.0]'
|
|
delay: 15m
|
|
history: '0'
|
|
value_type: FLOAT
|
|
units: V
|
|
description: 'MIB: PROSTAR-MPPT'
|
|
tags:
|
|
- tag: component
|
|
value: battery
|
|
- tag: component
|
|
value: discovery
|
|
- tag: component
|
|
value: raw
|
|
- uuid: ed1d54fce0904b7c9d0895a094f55108
|
|
name: 'Battery: Charge Current'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.33.0]'
|
|
key: 'charge.current[chargeCurrent.0]'
|
|
value_type: FLOAT
|
|
units: A
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Charge Current
|
|
Description:Charge Current
|
|
Scaling Factor:1.0
|
|
Units:A
|
|
Range:[0, 40]
|
|
Modbus address:0x0010
|
|
tags:
|
|
- tag: component
|
|
value: battery
|
|
- uuid: 1b1b61995c0d4d89a7f9ad4e14c3541f
|
|
name: 'Battery: Charge State'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.45.0]'
|
|
key: 'charge.state[chargeState.0]'
|
|
value_type: FLOAT
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Charge State
|
|
Description:Control State
|
|
Modbus address:0x0021
|
|
|
|
0: Start
|
|
1: NightCheck
|
|
2: Disconnect
|
|
3: Night
|
|
4: Fault
|
|
5: BulkMppt
|
|
6: Absorption
|
|
7: Float
|
|
8: Equalize
|
|
9: Slave
|
|
10: Fixed
|
|
valuemap:
|
|
name: 'ProStar MPPT charge state'
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 1h
|
|
tags:
|
|
- tag: component
|
|
value: battery
|
|
triggers:
|
|
- uuid: fe4863fdd4d64e1c977328bd3d0f687f
|
|
expression: 'last(/Morningstar ProStar MPPT by SNMP/charge.state[chargeState.0])={$CHARGE.STATE.CRIT}'
|
|
name: 'Morningstar ProStar MPPT: Battery: Device charge in critical state'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 4d064e4877474d72b85c9cdfb7b09dad
|
|
expression: 'last(/Morningstar ProStar MPPT by SNMP/charge.state[chargeState.0])={$CHARGE.STATE.WARN}'
|
|
name: 'Morningstar ProStar MPPT: Battery: Device charge in warning state'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
dependencies:
|
|
- name: 'Morningstar ProStar MPPT: Battery: Device charge in critical state'
|
|
expression: 'last(/Morningstar ProStar MPPT by SNMP/charge.state[chargeState.0])={$CHARGE.STATE.CRIT}'
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 009eb72ff6674da49d1dd85a6f9459cf
|
|
name: 'Counter: Charge Amp-hours'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.49.0]'
|
|
key: 'counter.charge_amp_hours[ahChargeResettable.0]'
|
|
value_type: FLOAT
|
|
units: Ah
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Ah Charge (Resettable)
|
|
Description:Ah Charge (Resettable)
|
|
Scaling Factor:0.1
|
|
Units:Ah
|
|
Range:[0.0, 4294967294]
|
|
Modbus addresses:H=0x0026 L=0x0027
|
|
preprocessing:
|
|
- type: MULTIPLIER
|
|
parameters:
|
|
- '0.1'
|
|
tags:
|
|
- tag: component
|
|
value: counter
|
|
- uuid: 4a53a2211a1249d59369ad65762ffe47
|
|
name: 'Counter: Charge KW-hours'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.51.0]'
|
|
key: 'counter.charge_kw_hours[kwhChargeResettable.0]'
|
|
value_type: FLOAT
|
|
units: '!kWh'
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
kWh Charge (Resettable)
|
|
Description:Kilowatt Hours Charge (Resettable)
|
|
Scaling Factor:1.0
|
|
Units:kWh
|
|
Range:[0.0, 65535]
|
|
Modbus address:0x002A
|
|
tags:
|
|
- tag: component
|
|
value: counter
|
|
- uuid: c72ef851c2d240c9835c1703cec49fd6
|
|
name: 'Counter: Load Amp-hours'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.56.0]'
|
|
key: 'counter.load_amp_hours[ahLoadResettable.0]'
|
|
value_type: FLOAT
|
|
units: Ah
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Description:Ah Load (Resettable)
|
|
Scaling Factor:0.1
|
|
Units:Ah
|
|
Range:[0.0, 4294967294]
|
|
Modbus addresses:H=0x0032 L=0x0033
|
|
preprocessing:
|
|
- type: MULTIPLIER
|
|
parameters:
|
|
- '0.1'
|
|
tags:
|
|
- tag: component
|
|
value: counter
|
|
- uuid: 29a7d76472fb4025bc78fbeab273e955
|
|
name: 'Load: Current'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.34.0]'
|
|
key: 'load.current[loadCurrent.0]'
|
|
value_type: FLOAT
|
|
units: A
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Load Current
|
|
Description:Load Current
|
|
Scaling Factor:1.0
|
|
Units:A
|
|
Range:[0, 60]
|
|
Modbus address:0x0016
|
|
tags:
|
|
- tag: component
|
|
value: load
|
|
- uuid: ae927b5cba5b43f5a2136fd3ee71b63d
|
|
name: 'Load: State'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.53.0]'
|
|
key: 'load.state[loadState.0]'
|
|
value_type: FLOAT
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Load State
|
|
Description:Load State
|
|
Modbus address:0x002E
|
|
|
|
0: Start
|
|
1: Normal
|
|
2: LvdWarning
|
|
3: Lvd
|
|
4: Fault
|
|
5: Disconnect
|
|
6: NormalOff
|
|
7: Override
|
|
8: NotUsed
|
|
valuemap:
|
|
name: 'ProStar MPPT load state'
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 1h
|
|
tags:
|
|
- tag: component
|
|
value: load
|
|
triggers:
|
|
- uuid: a88025c5e5a748e3a6dfa01685ba075b
|
|
expression: 'last(/Morningstar ProStar MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.CRIT:"lvd"} or last(/Morningstar ProStar MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.CRIT:"fault"}'
|
|
name: 'Morningstar ProStar MPPT: Load: Device load in critical state'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 9ab107b39b874fed83d09e7c1964a699
|
|
expression: 'last(/Morningstar ProStar MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.WARN:"lvdWarning"} or last(/Morningstar ProStar MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.WARN:"override"}'
|
|
name: 'Morningstar ProStar MPPT: Load: Device load in warning state'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
dependencies:
|
|
- name: 'Morningstar ProStar MPPT: Load: Device load in critical state'
|
|
expression: 'last(/Morningstar ProStar MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.CRIT:"lvd"} or last(/Morningstar ProStar MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.CRIT:"fault"}'
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 47894752dd1d41f1aa882387acf6dc3a
|
|
name: 'Load: Voltage'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.32.0]'
|
|
key: 'load.voltage[loadVoltage.0]'
|
|
value_type: FLOAT
|
|
units: V
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Load Voltage
|
|
Description:Load Voltage
|
|
Scaling Factor:1.0
|
|
Units:V
|
|
Range:[0, 80]
|
|
Modbus address:0x0014
|
|
tags:
|
|
- tag: component
|
|
value: load
|
|
- uuid: d44cb5d7db31402dae79275a9148817d
|
|
name: 'Status: Alarms'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.59.0]'
|
|
key: 'status.alarms[alarms.0]'
|
|
history: 1h
|
|
value_type: TEXT
|
|
trends: '0'
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Description:Alarms
|
|
Modbus addresses:H=0x0038 L=0x0039
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 1h
|
|
- type: JAVASCRIPT
|
|
parameters:
|
|
- |
|
|
var FIELDS = [
|
|
'rtsOpen',
|
|
'rtsShorted',
|
|
'rtsDisconnected',
|
|
'heatsinkTempSensorOpen',
|
|
'heatsinkTempSensorShorted',
|
|
'heatsinkTempLimit',
|
|
'inductorTempSensorOpen',
|
|
'inductorTempSensorShorted',
|
|
'inductorTempLimit',
|
|
'currentLimit',
|
|
'currentMeasurementError',
|
|
'batterySenseOutOfRange',
|
|
'batterySenseDisconnected',
|
|
'uncalibrated',
|
|
'tb5v',
|
|
'fp10SupplyOutOfRange',
|
|
'unused',
|
|
'mosfetOpen',
|
|
'arrayCurrentOffset',
|
|
'loadCurrentOffset',
|
|
'p33SupplyOutOfRange',
|
|
'p12SupplyOutOfRange',
|
|
'hightInputVoltageLimit',
|
|
'controllerReset',
|
|
'loadLvd',
|
|
'logTimeout',
|
|
'eepromAccessFailure'
|
|
];
|
|
|
|
var flags = parseInt(value.replace(/\x20/g, ''), 16),
|
|
result = [];
|
|
|
|
for (var i = 0, f = 1 << 31 >>> 0, l = FIELDS.length; i < l; i++, f >>>= 1) {
|
|
if (flags & f) {
|
|
result.push(FIELDS[i]);
|
|
}
|
|
}
|
|
|
|
return result.length ? result.join('\n') : 'No alarms';
|
|
tags:
|
|
- tag: component
|
|
value: status
|
|
triggers:
|
|
- uuid: a2d0ab5150dd4bad8b5ec4f2c6aa13f8
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","arrayCurrentOffset")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "arrayCurrentOffset" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: cc6a15f16fd8470a9dcd9a9e01cba61c
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","batterySenseDisconnected")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "batterySenseDisconnected" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 55d4726d9b9047c79cf690353d950797
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","batterySenseOutOfRange")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "batterySenseOutOfRange" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 7f015198395042219666cde4458d407c
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","controllerReset")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "controllerReset" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 48339339e5a7465fbc67266998c9a8fe
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","currentLimit")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "currentLimit" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: c88074037099498c896bb4793e04fea3
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","currentMeasurementError")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "currentMeasurementError" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: cecd8ee17e5143ffb46495e927750c82
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","eepromAccessFailure")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "eepromAccessFailure" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 4affa15e1c1c42459ea8dd6820d1c008
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","fp10SupplyOutOfRange")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "fp10SupplyOutOfRange" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 41e4225072a3468696cfb534c65b9736
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","heatsinkTempLimit")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "heatsinkTempLimit" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 5d269997a57d44ceb545e751e8e2d919
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","heatsinkTempSensorOpen")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "heatsinkTempSensorOpen" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: a8342a4e2fff40a7b830086dec303fd9
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","heatsinkTempSensorShorted")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "heatsinkTempSensorShorted" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 32e5b7ae81ce4ebea9b05ff7ab411e5a
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","hightInputVoltageLimit")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "hightInputVoltageLimit" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: c10d27c1d9d54b8981a639e7bf0dfc02
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","inductorTempLimit")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "inductorTempLimit" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 9f80959684b34b6498a1634097cd0d22
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","inductorTempSensorOpen")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "inductorTempSensorOpen" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: cc735ddcc98e4c099bb770e2b2a171b5
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","inductorTempSensorShorted")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "inductorTempSensorShorted" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 217935cd6c7547bc95f5af51b3e643d4
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","loadCurrentOffset")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "loadCurrentOffset" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: cb05261f120240bf944b304ffc4979e6
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","loadLvd")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "loadLvd" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 1ed1de932e084ce5ba03747bdd8ca4e5
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","logTimeout")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "logTimeout" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 8824f80f1ef245508d6d0d660e3cabf1
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","mosfetOpen")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "mosfetOpen" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 59569aaebf32403c9fd310f6b26845b0
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","p12SupplyOutOfRange")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "p12SupplyOutOfRange" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 4775d3a7b843455eb404661c070be092
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","p33SupplyOutOfRange")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "p33SupplyOutOfRange" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 2015d2b876564ad79699a23fc6b60f07
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","rtsDisconnected")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "rtsDisconnected" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: cce1eb2bee094a3b9a993ec2d60d182b
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","rtsShorted")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "rtsShorted" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 7a07b757660a4c9a879ac03a94832720
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","tb5v")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "tb5v" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 39205fc6d2cd4888994cccb016b4b2f8
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","uncalibrated")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "uncalibrated" alarm flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 8fbb5c650fa040c892a1d10a17fbbf14
|
|
name: 'Status: Array Faults'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.46.0]'
|
|
key: 'status.array_faults[arrayFaults.0]'
|
|
history: 1h
|
|
value_type: TEXT
|
|
trends: '0'
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Description:Array Faults
|
|
Modbus address:0x0022
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 1h
|
|
- type: JAVASCRIPT
|
|
parameters:
|
|
- |
|
|
var FIELDS = [
|
|
'overcurrent',
|
|
'mosfetSShorted',
|
|
'software',
|
|
'batteryHvd',
|
|
'arrayHvd',
|
|
'customSettingsEdit',
|
|
'rtsShorted',
|
|
'rtsNoLongerValid',
|
|
'localTempSensorDamaged',
|
|
'batteryLowVoltageDisconnect',
|
|
'slaveTimeout',
|
|
'dipSwitchChanged',
|
|
];
|
|
|
|
var flags = parseInt(value.replace(/\x20/g, ''), 16),
|
|
result = [];
|
|
|
|
for (var i = 0, f = 1 << 31 >>> 0, l = FIELDS.length; i < l; i++, f >>>= 1) {
|
|
if (flags & f) {
|
|
result.push(FIELDS[i]);
|
|
}
|
|
}
|
|
|
|
return result.length ? result.join('\n') : 'No faults';
|
|
tags:
|
|
- tag: component
|
|
value: status
|
|
triggers:
|
|
- uuid: 8322f8ca8e2e462a8799dc399f17ba27
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","arrayHvd")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "arrayHvd" array faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 6a138cd2af754bb3a22173e8da28b254
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","batteryHvd")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "batteryHvd" array faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 8e42cf21ec10409da840021bfd26f74c
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","batteryLowVoltageDisconnect")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "batteryLowVoltageDisconnect" array faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: d1112d9828064a879d56626ac6339dbf
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","customSettingsEdit")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "customSettingsEdit" array faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 75a67f17a33e41eea34585fade6319ef
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","dipSwitchChanged")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "dipSwitchChanged" array faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 4502112383524f0499ea13e6f83ce789
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","localTempSensorDamaged")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "localTempSensorDamaged" array faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: f1489dc1f8574895bd233b14ce080748
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","mosfetSShorted")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "mosfetSShorted" array faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 4ea903d3e8644ddaa5309eaa9715b894
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","overcurrent")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "overcurrent" array faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: e12a29ec16ea423cb69ca4ce460f201b
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","rtsNoLongerValid")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "rtsNoLongerValid" array faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 3ec4307bb2c444fc8eca27f9b7a136e2
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","rtsShorted")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "rtsShorted" array faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 915c00d98e144ee7a9a2d50d0bd474c0
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","slaveTimeout")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "slaveTimeout" array faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 9aac314eef594a8d86fd4b88308428e5
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","software")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "software" array faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 712a9b442bec4e89acf4ee5d5bf26fb8
|
|
name: 'Status: Uptime (hardware)'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.2.1.25.1.1.0]'
|
|
key: status.hw.uptime
|
|
units: uptime
|
|
description: 'The amount of time since this host was last initialized. Note that this is different from sysUpTime in the SNMPv2-MIB [RFC1907] because sysUpTime is the uptime of the network management portion of the system.'
|
|
preprocessing:
|
|
- type: CHECK_NOT_SUPPORTED
|
|
parameters:
|
|
- '-1'
|
|
error_handler: CUSTOM_VALUE
|
|
error_handler_params: '0'
|
|
- type: MULTIPLIER
|
|
parameters:
|
|
- '0.01'
|
|
tags:
|
|
- tag: component
|
|
value: status
|
|
- uuid: fb4d2147a8224b599ad908eca1b019e4
|
|
name: 'Status: Load Faults'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.54.0]'
|
|
key: 'status.load_faults[loadFaults.0]'
|
|
history: 1h
|
|
value_type: TEXT
|
|
trends: '0'
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Description:Array Faults
|
|
Modbus address:0x0022
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 1h
|
|
- type: JAVASCRIPT
|
|
parameters:
|
|
- |
|
|
var FIELDS = [
|
|
'externalShortCircuit',
|
|
'overcurrent',
|
|
'mosfetShorted',
|
|
'software',
|
|
'loadHvd',
|
|
'highTempDisconnect',
|
|
'dipSwitchChanged',
|
|
'customSettingsEdit'
|
|
];
|
|
|
|
var flags = parseInt(value.replace(/\x20/g, ''), 16),
|
|
result = [];
|
|
|
|
for (var i = 0, f = 1 << 31 >>> 0, l = FIELDS.length; i < l; i++, f >>>= 1) {
|
|
if (flags & f) {
|
|
result.push(FIELDS[i]);
|
|
}
|
|
}
|
|
|
|
return result.length ? result.join('\n') : 'No faults';
|
|
tags:
|
|
- tag: component
|
|
value: status
|
|
triggers:
|
|
- uuid: 93750f768ba94f1bb9302fc17c76faeb
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","customSettingsEdit")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "customSettingsEdit" load faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 456e2c36369f4519b2c80bcfe1acb4b0
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","dipSwitchChanged")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "dipSwitchChanged" load faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 359df17c40684187b7ae92c8aa0c9624
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","externalShortCircuit")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "externalShortCircuit" load faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 6dadf09064304f4381ad9ed0436e562a
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","highTempDisconnect")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "highTempDisconnect" load faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: bc41145ae8074290913a47cc3fd11e1e
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","loadHvd")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "loadHvd" load faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 8c8a7021928e4bf78b6309574e298876
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","mosfetShorted")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "mosfetShorted" load faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: b7d3f05837bd4d788d14f1aaf18b0482
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","overcurrent")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "overcurrent" load faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 801728740c1948b1a751469e6443daab
|
|
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","software")=2'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has "software" load faults flag'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 526ee94df484462a9264e57d92954e64
|
|
name: 'Status: Uptime (network)'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.2.1.1.3.0]'
|
|
key: status.net.uptime
|
|
units: uptime
|
|
description: 'The time (in hundredths of a second) since the network management portion of the system was last re-initialized.'
|
|
preprocessing:
|
|
- type: MULTIPLIER
|
|
parameters:
|
|
- '0.01'
|
|
tags:
|
|
- tag: component
|
|
value: status
|
|
triggers:
|
|
- uuid: 59cbcaaee8304b38a1144b3abf40bd9d
|
|
expression: 'nodata(/Morningstar ProStar MPPT by SNMP/status.net.uptime,5m)=1'
|
|
name: 'Morningstar ProStar MPPT: Status: Failed to fetch data'
|
|
event_name: 'Morningstar ProStar MPPT: Status: Failed to fetch data (or no data for 5m)'
|
|
priority: WARNING
|
|
description: 'Zabbix has not received data for items for the last 5 minutes.'
|
|
manual_close: 'YES'
|
|
tags:
|
|
- tag: scope
|
|
value: availability
|
|
- uuid: 20ce95acdff6486684461f10579a73b4
|
|
name: 'Battery: Target Voltage'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.48.0]'
|
|
key: 'target.voltage[targetVoltage.0]'
|
|
value_type: FLOAT
|
|
units: V
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Target Voltage
|
|
Description:Target Regulation Voltage
|
|
Scaling Factor:1.0
|
|
Units:V
|
|
Range:[0.0, 80.0]
|
|
Modbus address:0x0024
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 1h
|
|
tags:
|
|
- tag: component
|
|
value: battery
|
|
- uuid: 9a87cdcf65184059be334e986bcf801d
|
|
name: 'Temperature: Ambient'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.40.0]'
|
|
key: 'temp.ambient[ambientTemperature.0]'
|
|
value_type: FLOAT
|
|
units: C
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Ambient Temperature
|
|
Description:Ambient Temperature
|
|
Scaling Factor:1.0
|
|
Units:deg C
|
|
Range:[-128, 127]
|
|
Modbus address:0x001C
|
|
tags:
|
|
- tag: component
|
|
value: temperature
|
|
- uuid: 1a8e79f49e86429abc80dd29598299ee
|
|
name: 'Temperature: Battery'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.39.0]'
|
|
key: 'temp.battery[batteryTemperature.0]'
|
|
value_type: FLOAT
|
|
units: C
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Battery Temperature
|
|
Description:Battery Temperature
|
|
Scaling Factor:1.0
|
|
Units:deg C
|
|
Range:[-128, 127]
|
|
Modbus address:0x001B
|
|
tags:
|
|
- tag: component
|
|
value: temperature
|
|
triggers:
|
|
- uuid: c74e1d3be1c24bde986bbce068db4bb8
|
|
expression: 'min(/Morningstar ProStar MPPT by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.CRIT}'
|
|
name: 'Morningstar ProStar MPPT: Temperature: Critically high battery temperature'
|
|
event_name: 'Morningstar ProStar MPPT: Temperature: Critically high battery temperature (over {$BATTERY.TEMP.MAX.CRIT}C for 5m)'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 0c2180ae5deb41adb503e37bf91c34e2
|
|
expression: 'max(/Morningstar ProStar MPPT by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.CRIT}'
|
|
name: 'Morningstar ProStar MPPT: Temperature: Critically low battery temperature'
|
|
event_name: 'Morningstar ProStar MPPT: Temperature: Critically low battery temperature (below {$BATTERY.TEMP.MIN.WARN}C for 5m)'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 1ab91d781c734f1eb2b9552f6dee9370
|
|
expression: 'min(/Morningstar ProStar MPPT by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.WARN}'
|
|
name: 'Morningstar ProStar MPPT: Temperature: High battery temperature'
|
|
event_name: 'Morningstar ProStar MPPT: Temperature: High battery temperature (over {$BATTERY.TEMP.MAX.WARN}C for 5m)'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
dependencies:
|
|
- name: 'Morningstar ProStar MPPT: Temperature: Critically high battery temperature'
|
|
expression: 'min(/Morningstar ProStar MPPT by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.CRIT}'
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 6ec855dc6a5c42a79f1f40e14655418a
|
|
expression: 'max(/Morningstar ProStar MPPT by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.WARN}'
|
|
name: 'Morningstar ProStar MPPT: Temperature: Low battery temperature'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
dependencies:
|
|
- name: 'Morningstar ProStar MPPT: Temperature: Critically low battery temperature'
|
|
expression: 'max(/Morningstar ProStar MPPT by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.CRIT}'
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 7d0cf28c0d334154971738df11775d1f
|
|
name: 'Temperature: Heatsink'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.38.0]'
|
|
key: 'temp.heatsink[heatsinkTemperature.0]'
|
|
value_type: FLOAT
|
|
units: C
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Heatsink Temperature
|
|
Description:Heatsink Temperature
|
|
Scaling Factor:1.0
|
|
Units:deg C
|
|
Range:[-128, 127]
|
|
Modbus address:0x001A
|
|
tags:
|
|
- tag: component
|
|
value: temperature
|
|
discovery_rules:
|
|
- uuid: 1a21c30663c74c23b60e6ad72e228681
|
|
name: 'Battery voltage discovery'
|
|
type: DEPENDENT
|
|
key: battery.voltage.discovery
|
|
delay: '0'
|
|
description: 'Discovery for battery voltage triggers'
|
|
item_prototypes:
|
|
- uuid: c02c73a349ec4a6b8557e142c4866148
|
|
name: 'Battery: Voltage{#SINGLETON}'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.33333.5.30.0]'
|
|
key: 'battery.voltage[batteryTerminalVoltage.0{#SINGLETON}]'
|
|
value_type: FLOAT
|
|
units: V
|
|
description: |
|
|
MIB: PROSTAR-MPPT
|
|
Battery Terminal Voltage
|
|
Description:Battery Terminal Voltage
|
|
Scaling Factor:1.0
|
|
Units:V
|
|
Range:[0.0, 80.0]
|
|
Modbus address:0x0012
|
|
tags:
|
|
- tag: component
|
|
value: battery
|
|
trigger_prototypes:
|
|
- uuid: 402f73ca5b8d412689a7e715223e890d
|
|
expression: 'min(/Morningstar ProStar MPPT by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.CRIT}'
|
|
name: 'Morningstar ProStar MPPT: Battery: Critically high battery voltage'
|
|
event_name: 'Morningstar ProStar MPPT: Battery: Critically high battery voltage (over {#VOLTAGE.MAX.CRIT}V for 5m)'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: capacity
|
|
- uuid: 753a0d25832d434186f586f895124f31
|
|
expression: 'max(/Morningstar ProStar MPPT by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.CRIT}'
|
|
name: 'Morningstar ProStar MPPT: Battery: Critically low battery voltage'
|
|
event_name: 'Morningstar ProStar MPPT: Battery: Critically low battery voltage (below {#VOLTAGE.MIN.CRIT}V for 5m)'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: capacity
|
|
- uuid: 66e1fdfbfa5740dfa8945626f7f8be78
|
|
expression: 'min(/Morningstar ProStar MPPT by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.WARN}'
|
|
name: 'Morningstar ProStar MPPT: Battery: High battery voltage'
|
|
event_name: 'Morningstar ProStar MPPT: Battery: High battery voltage (over {#VOLTAGE.MAX.WARN}V for 5m)'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
dependencies:
|
|
- name: 'Morningstar ProStar MPPT: Battery: Critically high battery voltage'
|
|
expression: 'min(/Morningstar ProStar MPPT by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.CRIT}'
|
|
tags:
|
|
- tag: scope
|
|
value: capacity
|
|
- uuid: c9f3d03ce06641eb9b184f511a3a0341
|
|
expression: 'max(/Morningstar ProStar MPPT by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.WARN}'
|
|
name: 'Morningstar ProStar MPPT: Battery: Low battery voltage'
|
|
event_name: 'Morningstar ProStar MPPT: Battery: Low battery voltage (below {#VOLTAGE.MIN.WARN}V for 5m)'
|
|
opdata: 'Current value: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
dependencies:
|
|
- name: 'Morningstar ProStar MPPT: Battery: Critically low battery voltage'
|
|
expression: 'max(/Morningstar ProStar MPPT by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.CRIT}'
|
|
tags:
|
|
- tag: scope
|
|
value: capacity
|
|
graph_prototypes:
|
|
- uuid: 480e4c11060a4e34851b48bf7b9c5bb1
|
|
name: 'Voltage: Battery/Load{#SINGLETON}'
|
|
graph_items:
|
|
- drawtype: GRADIENT_LINE
|
|
color: 199C0D
|
|
item:
|
|
host: 'Morningstar ProStar MPPT by SNMP'
|
|
key: 'battery.voltage[batteryTerminalVoltage.0{#SINGLETON}]'
|
|
- sortorder: '1'
|
|
drawtype: GRADIENT_LINE
|
|
color: F63100
|
|
item:
|
|
host: 'Morningstar ProStar MPPT by SNMP'
|
|
key: 'load.voltage[loadVoltage.0]'
|
|
master_item:
|
|
key: 'battery.voltage.discovery[batteryTerminalVoltage.0]'
|
|
preprocessing:
|
|
- type: JAVASCRIPT
|
|
parameters:
|
|
- |
|
|
var v_range = [
|
|
[[0, 18], [12, 15, 11.5, 15.5]],
|
|
[[18, 36], [24, 30, 23, 31]],
|
|
[[36, 99], [48, 60, 46, 62]],
|
|
],
|
|
result = [];
|
|
|
|
for (var idx in v_range) {
|
|
if (v_range[idx][0][0] < value && value <= v_range[idx][0][1]) {
|
|
result = [{
|
|
'{#VOLTAGE.MIN.WARN}': parseInt({$VOLTAGE.MIN.WARN}) || v_range[idx][1][0],
|
|
'{#VOLTAGE.MAX.WARN}': parseInt({$VOLTAGE.MAX.WARN}) || v_range[idx][1][1],
|
|
'{#VOLTAGE.MIN.CRIT}': parseInt({$VOLTAGE.MIN.CRIT}) || v_range[idx][1][2],
|
|
'{#VOLTAGE.MAX.CRIT}': parseInt({$VOLTAGE.MAX.CRIT}) || v_range[idx][1][3],
|
|
'{#SINGLETON}': ''
|
|
}];
|
|
break;
|
|
}
|
|
}
|
|
|
|
return JSON.stringify(result);
|
|
tags:
|
|
- tag: class
|
|
value: power
|
|
- tag: target
|
|
value: morningstar
|
|
macros:
|
|
- macro: '{$BATTERY.TEMP.MAX.CRIT}'
|
|
value: '60'
|
|
description: 'Battery high temperature critical value'
|
|
- macro: '{$BATTERY.TEMP.MAX.WARN}'
|
|
value: '45'
|
|
description: 'Battery high temperature warning value'
|
|
- macro: '{$BATTERY.TEMP.MIN.CRIT}'
|
|
value: '-20'
|
|
description: 'Battery low temperature critical value'
|
|
- macro: '{$BATTERY.TEMP.MIN.WARN}'
|
|
value: '0'
|
|
description: 'Battery low temperature warning value'
|
|
- macro: '{$CHARGE.STATE.CRIT}'
|
|
value: '4'
|
|
description: fault
|
|
- macro: '{$CHARGE.STATE.WARN}'
|
|
value: '2'
|
|
description: disconnect
|
|
- macro: '{$LOAD.STATE.CRIT:"fault"}'
|
|
value: '4'
|
|
description: fault
|
|
- macro: '{$LOAD.STATE.CRIT:"lvd"}'
|
|
value: '3'
|
|
description: lvd
|
|
- macro: '{$LOAD.STATE.WARN:"disconnect"}'
|
|
value: '5'
|
|
description: disconnect
|
|
- macro: '{$LOAD.STATE.WARN:"lvdWarning"}'
|
|
value: '2'
|
|
description: lvdWarning
|
|
- macro: '{$LOAD.STATE.WARN:"override"}'
|
|
value: '7'
|
|
description: override
|
|
- macro: '{$VOLTAGE.MAX.CRIT}'
|
|
- macro: '{$VOLTAGE.MAX.WARN}'
|
|
- macro: '{$VOLTAGE.MIN.CRIT}'
|
|
- macro: '{$VOLTAGE.MIN.WARN}'
|
|
dashboards:
|
|
- uuid: 3765513f1a4945c0801639e4c689f99f
|
|
name: 'Morningstar ProStar MPPT: Overview'
|
|
pages:
|
|
- widgets:
|
|
- type: graph
|
|
width: '72'
|
|
height: '4'
|
|
fields:
|
|
- type: GRAPH
|
|
name: graphid.0
|
|
value:
|
|
host: 'Morningstar ProStar MPPT by SNMP'
|
|
name: 'Array: Voltage'
|
|
- type: STRING
|
|
name: reference
|
|
value: AAAAA
|
|
- type: graph
|
|
'y': '4'
|
|
width: '72'
|
|
height: '4'
|
|
fields:
|
|
- type: GRAPH
|
|
name: graphid.0
|
|
value:
|
|
host: 'Morningstar ProStar MPPT by SNMP'
|
|
name: 'Current: Charge/Load'
|
|
- type: STRING
|
|
name: reference
|
|
value: AAAAB
|
|
- type: graph
|
|
'y': '8'
|
|
width: '72'
|
|
height: '4'
|
|
fields:
|
|
- type: GRAPH
|
|
name: graphid.0
|
|
value:
|
|
host: 'Morningstar ProStar MPPT by SNMP'
|
|
name: 'Temperature: Ambient/Battery/Heatsink'
|
|
- type: STRING
|
|
name: reference
|
|
value: AAAAC
|
|
valuemaps:
|
|
- uuid: 1703c3aeb1b24641821e1c6d2cb4c8b7
|
|
name: 'ProStar MPPT charge state'
|
|
mappings:
|
|
- value: '0'
|
|
newvalue: Start
|
|
- value: '1'
|
|
newvalue: NightCheck
|
|
- value: '2'
|
|
newvalue: Disconnect
|
|
- value: '3'
|
|
newvalue: Night
|
|
- value: '4'
|
|
newvalue: Fault
|
|
- value: '5'
|
|
newvalue: BulkMppt
|
|
- value: '6'
|
|
newvalue: Absorption
|
|
- value: '7'
|
|
newvalue: Float
|
|
- value: '8'
|
|
newvalue: Equalize
|
|
- value: '9'
|
|
newvalue: Slave
|
|
- value: '10'
|
|
newvalue: Fixed
|
|
- uuid: b5403a0805a54b9294f69a1e11a438b1
|
|
name: 'ProStar MPPT load state'
|
|
mappings:
|
|
- value: '0'
|
|
newvalue: Start
|
|
- value: '1'
|
|
newvalue: Normal
|
|
- value: '2'
|
|
newvalue: LvdWarning
|
|
- value: '3'
|
|
newvalue: Lvd
|
|
- value: '4'
|
|
newvalue: Fault
|
|
- value: '5'
|
|
newvalue: Disconnect
|
|
- value: '6'
|
|
newvalue: NormalOff
|
|
- value: '7'
|
|
newvalue: Override
|
|
- value: '8'
|
|
newvalue: NotUsed
|
|
triggers:
|
|
- uuid: ca65a39c019046c29a522a6ca93ceb75
|
|
expression: '(last(/Morningstar ProStar MPPT by SNMP/status.hw.uptime)>0 and last(/Morningstar ProStar MPPT by SNMP/status.hw.uptime)<10m) or (last(/Morningstar ProStar MPPT by SNMP/status.hw.uptime)=0 and last(/Morningstar ProStar MPPT by SNMP/status.net.uptime)<10m)'
|
|
name: 'Morningstar ProStar MPPT: Status: Device has been restarted'
|
|
event_name: 'Morningstar ProStar MPPT: Status: Device has been restarted (uptime < 10m)'
|
|
priority: INFO
|
|
description: 'Uptime is less than 10 minutes.'
|
|
manual_close: 'YES'
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
graphs:
|
|
- uuid: 0662dc480c2b487e9f9afc389166a15b
|
|
name: 'Array: Voltage'
|
|
graph_items:
|
|
- drawtype: GRADIENT_LINE
|
|
color: 199C0D
|
|
item:
|
|
host: 'Morningstar ProStar MPPT by SNMP'
|
|
key: 'array.sweep_vmp[arrayVmp.0]'
|
|
- sortorder: '1'
|
|
drawtype: GRADIENT_LINE
|
|
color: F63100
|
|
item:
|
|
host: 'Morningstar ProStar MPPT by SNMP'
|
|
key: 'array.sweep_voc[arrayVoc.0]'
|
|
- sortorder: '2'
|
|
drawtype: GRADIENT_LINE
|
|
color: 00611C
|
|
item:
|
|
host: 'Morningstar ProStar MPPT by SNMP'
|
|
key: 'array.voltage[arrayVoltage.0]'
|
|
- uuid: 94bbfd8a60a8412998ff617011db9372
|
|
name: 'Current: Charge/Load'
|
|
graph_items:
|
|
- drawtype: GRADIENT_LINE
|
|
color: 199C0D
|
|
item:
|
|
host: 'Morningstar ProStar MPPT by SNMP'
|
|
key: 'charge.current[chargeCurrent.0]'
|
|
- sortorder: '1'
|
|
drawtype: GRADIENT_LINE
|
|
color: F63100
|
|
item:
|
|
host: 'Morningstar ProStar MPPT by SNMP'
|
|
key: 'load.current[loadCurrent.0]'
|
|
- uuid: 02652b1251244702bf28f691e72ba27e
|
|
name: 'Temperature: Ambient/Battery/Heatsink'
|
|
graph_items:
|
|
- drawtype: GRADIENT_LINE
|
|
color: 199C0D
|
|
item:
|
|
host: 'Morningstar ProStar MPPT by SNMP'
|
|
key: 'temp.ambient[ambientTemperature.0]'
|
|
- sortorder: '1'
|
|
drawtype: GRADIENT_LINE
|
|
color: F63100
|
|
item:
|
|
host: 'Morningstar ProStar MPPT by SNMP'
|
|
key: 'temp.battery[batteryTemperature.0]'
|
|
- sortorder: '2'
|
|
drawtype: GRADIENT_LINE
|
|
color: 00611C
|
|
item:
|
|
host: 'Morningstar ProStar MPPT by SNMP'
|
|
key: 'temp.heatsink[heatsinkTemperature.0]'
|