zabbix_export:
|
|
version: '7.0'
|
|
template_groups:
|
|
- uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
|
|
name: Templates/Power
|
|
templates:
|
|
- uuid: 3ec55c9966624ef5bc1b50502812d581
|
|
template: 'APC UPS by SNMP'
|
|
name: 'APC UPS by SNMP'
|
|
description: |
|
|
Template Power APC UPS
|
|
|
|
MIBs used:
|
|
HOST-RESOURCES-MIB
|
|
PowerNet-MIB
|
|
SNMPv2-MIB
|
|
|
|
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
|
|
|
|
Generated by official Zabbix template tool "Templator"
|
|
vendor:
|
|
name: Zabbix
|
|
version: 7.0-4
|
|
groups:
|
|
- name: Templates/Power
|
|
items:
|
|
- uuid: 96898d48b27946bfa9a623d7d0b028be
|
|
name: 'Battery capacity'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.1.0]'
|
|
key: 'battery.capacity[upsHighPrecBatteryCapacity]'
|
|
value_type: FLOAT
|
|
units: '%'
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The remaining battery capacity expressed as
|
|
percentage of full capacity.
|
|
preprocessing:
|
|
- type: MULTIPLIER
|
|
parameters:
|
|
- '0.1'
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: power
|
|
triggers:
|
|
- uuid: aa0bbfb321d440438fb421825f23e140
|
|
expression: 'last(/APC UPS by SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}'
|
|
name: 'APC UPS: Battery has low capacity'
|
|
event_name: 'APC UPS: Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%)'
|
|
opdata: 'Current capacity: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: capacity
|
|
- uuid: 390e33a7623d41d2a8a67752c6d5c733
|
|
name: 'External battery packs count'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.5.0]'
|
|
key: 'battery.external_packs_count[upsAdvBatteryNumOfBattPacks]'
|
|
delay: 1h
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The number of external battery packs connected to the UPS. If
|
|
the UPS does not use smart cells then the agent reports
|
|
ERROR_NO_SUCH_NAME.
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: inventory
|
|
- uuid: 3d69adaa88e64b8084d38c1482815bf2
|
|
name: 'Battery last replace date'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.1.3.0]'
|
|
key: 'battery.last_replace_date[upsBasicBatteryLastReplaceDate]'
|
|
delay: 1h
|
|
value_type: CHAR
|
|
trends: '0'
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The date when the UPS system's batteries were last replaced
|
|
in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value
|
|
is originally set at the factory. When the UPS batteries
|
|
are replaced, this value should be reset by the administrator.
|
|
For Symmetra PX 250/500 this OID is read-only and is configurable in the local display only.
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: inventory
|
|
- uuid: eb74b3671b4d4335ad92bd3b027547b0
|
|
name: 'Battery replace indicator'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.4.0]'
|
|
key: 'battery.replace_indicator[upsAdvBatteryReplaceIndicator]'
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
Indicates whether the UPS batteries need replacement.
|
|
valuemap:
|
|
name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator'
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: power
|
|
triggers:
|
|
- uuid: 7e40918732e74b5e8bd854422989e77d
|
|
expression: 'last(/APC UPS by SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2'
|
|
name: 'APC UPS: Battery needs replacement'
|
|
priority: HIGH
|
|
description: 'A battery installed has an internal error condition.'
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: f52a3e2ae08c4b2996249c5601b4098d
|
|
name: 'Battery runtime remaining'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.3.0]'
|
|
key: 'battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]'
|
|
value_type: FLOAT
|
|
units: s
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The UPS battery run time remaining before battery
|
|
exhaustion.
|
|
preprocessing:
|
|
- type: MULTIPLIER
|
|
parameters:
|
|
- '0.01'
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: power
|
|
- uuid: f4106603e47e40548592d60a7b8b3148
|
|
name: 'Battery status'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.1.1.0]'
|
|
key: 'battery.status[upsBasicBatteryStatus]'
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The status of the UPS batteries. A batteryLow(3) value
|
|
indicates the UPS will be unable to sustain the current
|
|
load, and its services will be lost if power is not restored.
|
|
The amount of run time in reserve at the time of low battery
|
|
can be configured by the upsAdvConfigLowBatteryRunTime.
|
|
A batteryInFaultCondition(4)value indicates that a battery
|
|
installed has an internal error condition.
|
|
valuemap:
|
|
name: 'PowerNet-MIB::upsBasicBatteryStatus'
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: health
|
|
- tag: component
|
|
value: power
|
|
triggers:
|
|
- uuid: 7ae03f3f307b4f11ad2bc0548911cbd3
|
|
expression: 'last(/APC UPS by SNMP/battery.status[upsBasicBatteryStatus])=4'
|
|
name: 'APC UPS: Battery has an internal error condition'
|
|
priority: AVERAGE
|
|
description: 'A battery installed has an internal error condition.'
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 1282326bb61d45d88671bbbde3fab8ff
|
|
expression: 'last(/APC UPS by SNMP/battery.status[upsBasicBatteryStatus])=3'
|
|
name: 'APC UPS: Battery is Low'
|
|
priority: AVERAGE
|
|
description: 'The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.'
|
|
tags:
|
|
- tag: scope
|
|
value: capacity
|
|
- uuid: 7c35a9646eed4e4581edc51d42a9604c
|
|
name: 'Battery temperature'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.2.0]'
|
|
key: 'battery.temperature[upsHighPrecBatteryTemperature]'
|
|
value_type: FLOAT
|
|
units: ℃
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The current internal UPS temperature in Celsius.
|
|
Temperatures below zero read as 0.
|
|
preprocessing:
|
|
- type: MULTIPLIER
|
|
parameters:
|
|
- '0.1'
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: temperature
|
|
triggers:
|
|
- uuid: 36a14fe061d1433e9875373307a4e0f4
|
|
expression: 'min(/APC UPS by SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
|
|
name: 'APC UPS: Battery has high temperature'
|
|
event_name: 'APC UPS: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})'
|
|
opdata: 'Current temperature: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: b78d2e9160c74f328b8123ba2031d7bf
|
|
name: 'Battery voltage'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.4.0]'
|
|
key: 'battery.voltage[upsHighPrecBatteryActualVoltage]'
|
|
value_type: FLOAT
|
|
units: V
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The actual battery bus voltage in Volts.
|
|
preprocessing:
|
|
- type: MULTIPLIER
|
|
parameters:
|
|
- '0.1'
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: power
|
|
- uuid: 6ce40beab0b44248868652b0ed543afc
|
|
name: 'Input fail cause'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.3.2.5.0]'
|
|
key: 'input.fail[upsAdvInputLineFailCause]'
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The reason for the occurrence of the last transfer to UPS
|
|
battery power. The variable is set to:
|
|
- noTransfer(1) -- if there is no transfer yet.
|
|
- highLineVoltage(2) -- if the transfer to battery is caused
|
|
by an over voltage greater than the high transfer voltage.
|
|
- brownout(3) -- if the duration of the outage is greater than
|
|
five seconds and the line voltage is between 40% of the
|
|
rated output voltage and the low transfer voltage.
|
|
- blackout(4) -- if the duration of the outage is greater than five
|
|
seconds and the line voltage is between 40% of the rated
|
|
output voltage and ground.
|
|
- smallMomentarySag(5) -- if the duration of the outage is less
|
|
than five seconds and the line voltage is between 40% of the
|
|
rated output voltage and the low transfer voltage.
|
|
- deepMomentarySag(6) -- if the duration of the outage is less
|
|
than five seconds and the line voltage is between 40% of the
|
|
rated output voltage and ground. The variable is set to
|
|
- smallMomentarySpike(7) -- if the line failure is caused by a
|
|
rate of change of input voltage less than ten volts per cycle.
|
|
- largeMomentarySpike(8) -- if the line failure is caused by
|
|
a rate of change of input voltage greater than ten volts per cycle.
|
|
- selfTest(9) -- if the UPS was commanded to do a self test.
|
|
- rateOfVoltageChange(10) -- if the failure is due to the rate of change of
|
|
the line voltage.
|
|
valuemap:
|
|
name: 'PowerNet-MIB::upsAdvInputLineFailCause'
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: power
|
|
- uuid: 2c0b565f2b6a44a2a91cc61fd220f056
|
|
name: 'Input frequency'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.3.3.4.0]'
|
|
key: 'input.frequency[upsHighPrecInputFrequency]'
|
|
value_type: FLOAT
|
|
units: Hz
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The current input frequency to the UPS system in Hz.
|
|
preprocessing:
|
|
- type: MULTIPLIER
|
|
parameters:
|
|
- '0.1'
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: power
|
|
triggers:
|
|
- uuid: 1ddd2699b87f452a8893f75f805c0a81
|
|
expression: 'min(/APC UPS by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})'
|
|
name: 'APC UPS: Unacceptable input frequency'
|
|
event_name: 'APC UPS: Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD})'
|
|
opdata: 'Current frequency: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: de84a2fbbb464023a7b73e01895a9e9d
|
|
name: 'Input voltage'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.3.3.1.0]'
|
|
key: 'input.voltage[upsHighPrecInputLineVoltage]'
|
|
value_type: FLOAT
|
|
units: V
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The current utility line voltage in VAC.
|
|
preprocessing:
|
|
- type: MULTIPLIER
|
|
parameters:
|
|
- '0.1'
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: power
|
|
triggers:
|
|
- uuid: f6527c4fed3d41168be23f9367f18405
|
|
expression: 'min(/APC UPS by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})'
|
|
name: 'APC UPS: Unacceptable input voltage'
|
|
event_name: 'APC UPS: Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
|
|
opdata: 'Current voltage: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: a332c87a948045beae13f74984245b86
|
|
name: 'Output current'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.3.4.0]'
|
|
key: 'output.current[upsHighPrecOutputCurrent]'
|
|
value_type: FLOAT
|
|
units: A
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The current in amperes drawn by the load on the UPS.
|
|
preprocessing:
|
|
- type: MULTIPLIER
|
|
parameters:
|
|
- '0.1'
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: power
|
|
- uuid: c17c7fd7e6504592869dc14c4a002254
|
|
name: 'Output load'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.3.3.0]'
|
|
key: 'output.load[upsHighPrecOutputLoad]'
|
|
value_type: FLOAT
|
|
units: '%'
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The current UPS load expressed as percentage
|
|
of rated capacity.
|
|
preprocessing:
|
|
- type: MULTIPLIER
|
|
parameters:
|
|
- '0.1'
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: power
|
|
triggers:
|
|
- uuid: ebef08a42d1e47ffa82ea586c1a5b3d6
|
|
expression: 'min(/APC UPS by SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}'
|
|
name: 'APC UPS: Output load is high'
|
|
event_name: 'APC UPS: Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD})'
|
|
opdata: 'Current load: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
description: 'A battery installed has an internal error condition.'
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 0ae99a18a5c24fb0b812353d25459e1f
|
|
name: 'Output status'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.1.1.0]'
|
|
key: 'output.status[upsBasicOutputStatus]'
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The current state of the UPS. If the UPS is unable to
|
|
determine the state of the UPS this variable is set
|
|
to unknown(1).
|
|
During self-test most UPSes report onBattery(3) but
|
|
some that support it will report onBatteryTest(15).
|
|
To determine self-test status across all UPSes, refer
|
|
to the upsBasicStateOutputState OID.
|
|
valuemap:
|
|
name: 'PowerNet-MIB::upsBasicOutputStatus'
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: health
|
|
- tag: component
|
|
value: power
|
|
triggers:
|
|
- uuid: c0e0b1db9a1f41379c340c122426778d
|
|
expression: 'last(/APC UPS by SNMP/output.status[upsBasicOutputStatus])=16'
|
|
name: 'APC UPS: UPS is Emergency Static Bypass'
|
|
priority: AVERAGE
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 381a6a75d9084ff1bfcc30b6870a2682
|
|
expression: 'last(/APC UPS by SNMP/output.status[upsBasicOutputStatus])=10'
|
|
name: 'APC UPS: UPS is Hardware Failure Bypass'
|
|
priority: AVERAGE
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: da75b5277ceb423fac8d90b58d49c21f
|
|
expression: 'last(/APC UPS by SNMP/output.status[upsBasicOutputStatus])=7'
|
|
name: 'APC UPS: UPS is Off'
|
|
priority: AVERAGE
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: b0330f707fc64605934ed95233bd2246
|
|
expression: 'last(/APC UPS by SNMP/output.status[upsBasicOutputStatus])=3'
|
|
name: 'APC UPS: UPS is on battery'
|
|
priority: AVERAGE
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: f8d75a2fdb6942e6b63831d206c78e56
|
|
expression: 'last(/APC UPS by SNMP/output.status[upsBasicOutputStatus])=4'
|
|
name: 'APC UPS: UPS is on Smart Boost'
|
|
priority: AVERAGE
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 8eb59b4873e14acfa8e05791ed30c9d1
|
|
expression: 'last(/APC UPS by SNMP/output.status[upsBasicOutputStatus])=12'
|
|
name: 'APC UPS: UPS is On Smart Trim'
|
|
priority: AVERAGE
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: e06247b357b849d3ad1886f797705320
|
|
expression: 'last(/APC UPS by SNMP/output.status[upsBasicOutputStatus])=8'
|
|
name: 'APC UPS: UPS is Rebooting'
|
|
priority: AVERAGE
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 9b4424babc284dcabfb44dc725c03f40
|
|
expression: 'last(/APC UPS by SNMP/output.status[upsBasicOutputStatus])=11'
|
|
name: 'APC UPS: UPS is Sleeping Until Power Return'
|
|
priority: AVERAGE
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 9ac2faafee484894bb304da02d6ab0b2
|
|
expression: 'last(/APC UPS by SNMP/output.status[upsBasicOutputStatus])=6'
|
|
name: 'APC UPS: UPS is Software Bypass'
|
|
priority: AVERAGE
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: ce16d33b10e74b129d22378f96ede052
|
|
expression: 'last(/APC UPS by SNMP/output.status[upsBasicOutputStatus])=9'
|
|
name: 'APC UPS: UPS is Switched Bypass'
|
|
priority: AVERAGE
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: aa84fc5fd4434101a481481beb616a7c
|
|
expression: 'last(/APC UPS by SNMP/output.status[upsBasicOutputStatus])=5'
|
|
name: 'APC UPS: UPS is Timed Sleeping'
|
|
priority: AVERAGE
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 37d7eda5664c4ae2b4a126c60a8eb40b
|
|
name: 'Output voltage'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.3.1.0]'
|
|
key: 'output.voltage[upsHighPrecOutputVoltage]'
|
|
value_type: FLOAT
|
|
units: V
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The output voltage of the UPS system in VAC.
|
|
preprocessing:
|
|
- type: MULTIPLIER
|
|
parameters:
|
|
- '0.1'
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: power
|
|
- uuid: 2c52ba1a964a40e1b4a75582ee6ad43b
|
|
name: 'SNMP traps (fallback)'
|
|
type: SNMP_TRAP
|
|
key: snmptrap.fallback
|
|
delay: '0'
|
|
value_type: LOG
|
|
trends: '0'
|
|
description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items'
|
|
logtimefmt: 'hh:mm:sszyyyy/MM/dd'
|
|
tags:
|
|
- tag: component
|
|
value: network
|
|
- uuid: 299e4e11e0374888877e1dc386409726
|
|
name: 'System contact details'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.2.1.1.4.0]'
|
|
key: 'system.contact[sysContact.0]'
|
|
delay: 15m
|
|
value_type: CHAR
|
|
trends: '0'
|
|
description: |
|
|
MIB: SNMPv2-MIB
|
|
The textual identification of the contact person for this managed
|
|
node, together with information on how to contact this person. If no contact
|
|
information is known, the value is the zero-length string.
|
|
inventory_link: CONTACT
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 12h
|
|
tags:
|
|
- tag: component
|
|
value: system
|
|
- uuid: ed42f6f2d8c24176b53f38e0a857a129
|
|
name: 'System description'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.2.1.1.1.0]'
|
|
key: 'system.descr[sysDescr.0]'
|
|
delay: 15m
|
|
value_type: CHAR
|
|
trends: '0'
|
|
description: |
|
|
MIB: SNMPv2-MIB
|
|
A textual description of the entity. This value should
|
|
include the full name and version identification of the system's hardware type, software operating-system, and
|
|
networking software.
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 12h
|
|
tags:
|
|
- tag: component
|
|
value: system
|
|
- uuid: b3d5eea37f934efdac4885bcadc73b9b
|
|
name: 'Uptime (hardware)'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.2.1.25.1.1.0]'
|
|
key: 'system.hw.uptime[hrSystemUptime.0]'
|
|
delay: 30s
|
|
trends: '0'
|
|
units: uptime
|
|
description: |
|
|
MIB: HOST-RESOURCES-MIB
|
|
The amount of time since this host was last initialized. Note that this is different from sysUpTime in the SNMPv2-MIB [RFC1907] because sysUpTime is the uptime of the network management portion of the system.
|
|
preprocessing:
|
|
- type: CHECK_NOT_SUPPORTED
|
|
parameters:
|
|
- '-1'
|
|
error_handler: CUSTOM_VALUE
|
|
error_handler_params: '0'
|
|
- type: MULTIPLIER
|
|
parameters:
|
|
- '0.01'
|
|
tags:
|
|
- tag: component
|
|
value: system
|
|
- uuid: 445d7a843340424ab7c09ab001d5865c
|
|
name: 'System location'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.2.1.1.6.0]'
|
|
key: 'system.location[sysLocation.0]'
|
|
delay: 15m
|
|
value_type: CHAR
|
|
trends: '0'
|
|
description: |
|
|
MIB: SNMPv2-MIB
|
|
The physical location of this node (e.g., `telephone closet, 3rd floor'). If the location is unknown, the value is the zero-length string.
|
|
inventory_link: LOCATION
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: system
|
|
- uuid: 6030dbee3cc24dbeb15e4b802e89cbc8
|
|
name: Model
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.1.1.1.0]'
|
|
key: 'system.model[upsBasicIdentModel]'
|
|
delay: 15m
|
|
value_type: CHAR
|
|
trends: '0'
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The UPS model name (e.g. 'APC Smart-UPS 600').
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: inventory
|
|
- uuid: 45a80892f41b411e8457f99b069b59ee
|
|
name: 'System name'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.2.1.1.5.0]'
|
|
key: 'system.name[sysName.0]'
|
|
delay: 15m
|
|
value_type: CHAR
|
|
trends: '0'
|
|
description: |
|
|
MIB: SNMPv2-MIB
|
|
An administratively-assigned name for this managed node.By
|
|
convention, this is the node's fully-qualified domain name. If the name is unknown,
|
|
the value is the zero-length string.
|
|
inventory_link: NAME
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: system
|
|
triggers:
|
|
- uuid: facbfd1f8bb04401b563c162d7fe13a5
|
|
expression: 'last(/APC UPS by SNMP/system.name[sysName.0],#1)<>last(/APC UPS by SNMP/system.name[sysName.0],#2) and length(last(/APC UPS by SNMP/system.name[sysName.0]))>0'
|
|
name: 'APC UPS: System name has changed'
|
|
event_name: 'APC UPS: System name has changed (new name: {ITEM.VALUE})'
|
|
priority: INFO
|
|
description: 'The name of the system has changed. Acknowledge to close the problem manually.'
|
|
manual_close: 'YES'
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- tag: scope
|
|
value: security
|
|
- uuid: 701fa778bc03444aad94343d0dbe048e
|
|
name: 'Uptime (network)'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.2.1.1.3.0]'
|
|
key: 'system.net.uptime[sysUpTime.0]'
|
|
delay: 30s
|
|
trends: '0'
|
|
units: uptime
|
|
description: |
|
|
MIB: SNMPv2-MIB
|
|
The time (in hundredths of a second) since the network management portion of the system was last re-initialized.
|
|
preprocessing:
|
|
- type: MULTIPLIER
|
|
parameters:
|
|
- '0.01'
|
|
tags:
|
|
- tag: component
|
|
value: system
|
|
- uuid: 6780faad9fc9492f9f92915db5161e43
|
|
name: 'System object ID'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.2.1.1.2.0]'
|
|
key: 'system.objectid[sysObjectID.0]'
|
|
delay: 15m
|
|
value_type: CHAR
|
|
trends: '0'
|
|
description: |
|
|
MIB: SNMPv2-MIB
|
|
The vendor's authoritative identification of the network management
|
|
subsystem contained in the entity. This value is allocated within the SMI enterprises
|
|
subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what
|
|
kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was
|
|
assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1
|
|
to its `Fred Router'.
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: system
|
|
- uuid: 1df309508ac9433397f88120b2895451
|
|
name: 'Serial number'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.1.2.3.0]'
|
|
key: 'system.sn[upsAdvIdentSerialNumber]'
|
|
delay: 15m
|
|
value_type: CHAR
|
|
trends: '0'
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
An 8-character string identifying the serial number of
|
|
the UPS internal microprocessor. This number is set at
|
|
the factory. NOTE: This number does NOT correspond to
|
|
the serial number on the rear of the UPS.
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: inventory
|
|
- uuid: ca3275f69f3c4e7c9c71108451c0b64f
|
|
name: 'SNMP agent availability'
|
|
type: INTERNAL
|
|
key: 'zabbix[host,snmp,available]'
|
|
description: |
|
|
Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.
|
|
Possible values:
|
|
0 - not available
|
|
1 - available
|
|
2 - unknown
|
|
valuemap:
|
|
name: zabbix.host.available
|
|
tags:
|
|
- tag: component
|
|
value: health
|
|
- tag: component
|
|
value: network
|
|
triggers:
|
|
- uuid: 4572d871f1d944bb855b93fdc6de5e88
|
|
expression: 'max(/APC UPS by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
|
|
name: 'APC UPS: No SNMP data collection'
|
|
opdata: 'Current state: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
description: 'SNMP is not available for polling. Please check device connectivity and SNMP settings.'
|
|
tags:
|
|
- tag: scope
|
|
value: availability
|
|
discovery_rules:
|
|
- uuid: 52345d2975214002bdd05a24e43484a8
|
|
name: 'External bad battery packs discovery'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'discovery[{#EXTERNAL_PACKS},1.3.6.1.4.1.318.1.1.1.2.2.6]'
|
|
key: battery.packs.bad.discovery
|
|
delay: 1h
|
|
filter:
|
|
evaltype: AND
|
|
conditions:
|
|
- macro: '{#EXTERNAL_PACKS}'
|
|
value: '-1'
|
|
operator: NOT_MATCHES_REGEX
|
|
formulaid: A
|
|
description: 'Discovery of the number of external defective battery packs.'
|
|
item_prototypes:
|
|
- uuid: c4dccc96218448d696952f6ea5d1f24b
|
|
name: '{#SNMPINDEX}: External battery packs bad'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.6.0]'
|
|
key: 'battery.external_packs_bad[upsAdvBatteryNumOfBadBattPacks.{#SNMPINDEX}]'
|
|
delay: 15m
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The number of external battery packs connected to the UPS that
|
|
are defective. If the UPS does not use smart cells then the
|
|
agent reports ERROR_NO_SUCH_NAME.
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: inventory
|
|
- uuid: f7eb1c82c6694e72b7d28ba4d71d8741
|
|
name: 'External battery packs discovery'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'discovery[{#CARTRIDGE_STATUS},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7,{#BATTERY_PACK},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1,{#CARTRIDGE_INDEX},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2]'
|
|
key: battery.packs.discovery
|
|
delay: 1h
|
|
filter:
|
|
evaltype: AND
|
|
conditions:
|
|
- macro: '{#CARTRIDGE_STATUS}'
|
|
value: ^$
|
|
operator: NOT_MATCHES_REGEX
|
|
formulaid: A
|
|
item_prototypes:
|
|
- uuid: a168ef9da6504b31a8234b272f1a1a80
|
|
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery estimated replace date'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8.{#SNMPINDEX}]'
|
|
key: 'battery.estimated_replace_date[upsHighPrecBatteryPackCartridgeReplaceDate.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
|
|
delay: 1h
|
|
value_type: CHAR
|
|
trends: '0'
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The battery cartridge estimated battery replace date.
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: inventory
|
|
- tag: component
|
|
value: power
|
|
- uuid: fd71d1ceaf524aeaac38de5f63d101fd
|
|
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7.{#SNMPINDEX}]'
|
|
key: 'battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
|
|
value_type: CHAR
|
|
trends: '0'
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The battery cartridge health.
|
|
bit 0 Battery lifetime okay
|
|
bit 1 Battery lifetime near end, order replacement cartridge
|
|
bit 2 Battery lifetime exceeded, replace battery
|
|
bit 3 Battery lifetime near end acknowledged, order replacement cartridge
|
|
bit 4 Battery lifetime exceeded acknowledged, replace battery
|
|
bit 5 Battery measured lifetime near end, order replacement cartridge
|
|
bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: health
|
|
- tag: component
|
|
value: power
|
|
trigger_prototypes:
|
|
- uuid: a248194aa30645c5918278b83944b20e
|
|
expression: 'find(/APC UPS by SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1'
|
|
name: 'APC UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay'
|
|
opdata: 'Current bit set: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
description: |
|
|
The battery cartridge health.
|
|
bit 0 Battery lifetime okay
|
|
bit 1 Battery lifetime near end, order replacement cartridge
|
|
bit 2 Battery lifetime exceeded, replace battery
|
|
bit 3 Battery lifetime near end acknowledged, order replacement cartridge
|
|
bit 4 Battery lifetime exceeded acknowledged, replace battery
|
|
bit 5 Battery measured lifetime near end, order replacement cartridge
|
|
bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: fa05e062413a4c1fba4d35e3006b91f4
|
|
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10.{#SNMPINDEX}]'
|
|
key: 'battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
|
|
value_type: CHAR
|
|
trends: '0'
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The battery cartridge status.
|
|
bit 0 Disconnected
|
|
bit 1 Overvoltage
|
|
bit 2 NeedsReplacement
|
|
bit 3 OvertemperatureCritical
|
|
bit 4 Charger
|
|
bit 5 TemperatureSensor
|
|
bit 6 BusSoftStart
|
|
bit 7 OvertemperatureWarning
|
|
bit 8 GeneralError
|
|
bit 9 Communication
|
|
bit 10 DisconnectedFrame
|
|
bit 11 FirmwareMismatch
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: health
|
|
- tag: component
|
|
value: power
|
|
trigger_prototypes:
|
|
- uuid: 834b1a48cbab46a3bfb0209fb4302674
|
|
expression: 'find(/APC UPS by SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0'
|
|
name: 'APC UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay'
|
|
opdata: 'Current bit set: {ITEM.LASTVALUE1}'
|
|
priority: WARNING
|
|
description: |
|
|
The battery cartridge status:
|
|
bit 0 Disconnected
|
|
bit 1 Overvoltage
|
|
bit 2 NeedsReplacement
|
|
bit 3 OvertemperatureCritical
|
|
bit 4 Charger
|
|
bit 5 TemperatureSensor
|
|
bit 6 BusSoftStart
|
|
bit 7 OvertemperatureWarning
|
|
bit 8 GeneralError
|
|
bit 9 Communication
|
|
bit 10 DisconnectedFrame
|
|
bit 11 FirmwareMismatch
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 017347865030426e9dde74e9bcf38c76
|
|
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperature'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5.{#SNMPINDEX}]'
|
|
key: 'battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
|
|
value_type: FLOAT
|
|
units: ℃
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The current internal UPS temperature in Celsius.
|
|
Temperatures below zero read as 0.
|
|
preprocessing:
|
|
- type: MULTIPLIER
|
|
parameters:
|
|
- '0.1'
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: temperature
|
|
trigger_prototypes:
|
|
- uuid: 80f084121d56464f90e4a3ef9e198889
|
|
expression: 'min(/APC UPS by SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
|
|
name: 'APC UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature'
|
|
event_name: 'APC UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})'
|
|
opdata: 'Current temperature: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 354c1d6766d6453caeb382cf7ede7951
|
|
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4.{#SNMPINDEX}]'
|
|
key: 'system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
|
|
delay: 15m
|
|
value_type: CHAR
|
|
trends: '0'
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The battery pack serial number.
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: inventory
|
|
- uuid: 457169b3c43846739614a6ddc7155fda
|
|
name: 'External sensor port 1 discovery'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'discovery[{#EXTERNAL_SENSOR1_NAME},1.3.6.1.4.1.318.1.1.25.1.2.1.3]'
|
|
key: external.sensor1.discovery
|
|
delay: 1h
|
|
description: uioSensorStatusTable
|
|
item_prototypes:
|
|
- uuid: ee017a632ee944fe9122e21fa7e7531f
|
|
name: '{#EXTERNAL_SENSOR1_NAME}: Humidity sensor'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.1.7.{#SNMPINDEX}]'
|
|
key: 'external.sensor.humidity[uioSensorStatusHumidity.1.{#SNMPINDEX}]'
|
|
value_type: FLOAT
|
|
units: '%'
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The sensor's current humidity reading - a relative humidity
|
|
percentage. -1 indicates an invalid reading due to either a
|
|
sensor that doesn't read humidity or lost communications.
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: humidity
|
|
- tag: component
|
|
value: power
|
|
- uuid: 0431cf0a54b449c9b77623b69629920f
|
|
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.1.9.{#SNMPINDEX}]'
|
|
key: 'external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}]'
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The alarm status of the sensor. Possible values:
|
|
uioNormal (1),
|
|
uioWarning (2),
|
|
uioCritical (3),
|
|
sensorStatusNotApplicable (4)
|
|
valuemap:
|
|
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: health
|
|
- tag: component
|
|
value: power
|
|
trigger_prototypes:
|
|
- uuid: 3a40f3cb0a3b411697fe8d37f82404d4
|
|
expression: 'last(/APC UPS by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3'
|
|
name: 'APC UPS: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical'
|
|
priority: HIGH
|
|
description: 'The external sensor has returned a value greater than the critical threshold.'
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 63ba879a2a324ffc958b761f2010ac8e
|
|
expression: 'last(/APC UPS by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4'
|
|
name: 'APC UPS: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable'
|
|
priority: INFO
|
|
description: 'The external sensor does not work or is not connected.'
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: dc90cd795879495fa473b71a2ff57b49
|
|
expression: 'last(/APC UPS by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2'
|
|
name: 'APC UPS: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning'
|
|
priority: AVERAGE
|
|
description: 'The external sensor has returned a value greater than the warning threshold.'
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 6de4920e4e87418884a82ff8b40a46ab
|
|
name: '{#EXTERNAL_SENSOR1_NAME}: Temperature sensor'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.1.6.{#SNMPINDEX}]'
|
|
key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.1.{#SNMPINDEX}]'
|
|
value_type: FLOAT
|
|
units: ℃
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The sensor's current temperature reading in Celsius.
|
|
-1 indicates an invalid reading due to lost communications.
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: power
|
|
- tag: component
|
|
value: temperature
|
|
overrides:
|
|
- name: Temp
|
|
step: '1'
|
|
filter:
|
|
conditions:
|
|
- macro: '{#EXTERNAL_SENSOR1_NAME}'
|
|
value: Temp
|
|
formulaid: A
|
|
operations:
|
|
- operationobject: ITEM_PROTOTYPE
|
|
operator: LIKE
|
|
value: Humidity
|
|
discover: NO_DISCOVER
|
|
- uuid: 06a853147fe646659d066fff34f67faa
|
|
name: 'External sensor port 2 discovery'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'discovery[{#EXTERNAL_SENSOR2_NAME},1.3.6.1.4.1.318.1.1.25.1.2.2.3]'
|
|
key: external.sensor2.discovery
|
|
delay: 1h
|
|
description: uioSensorStatusTable
|
|
item_prototypes:
|
|
- uuid: 3417b035a4f14ce3992e10029674de8e
|
|
name: '{#EXTERNAL_SENSOR2_NAME}: Humidity sensor'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.2.7.{#SNMPINDEX}]'
|
|
key: 'external.sensor.humidity[uioSensorStatusHumidity.2.{#SNMPINDEX}]'
|
|
value_type: FLOAT
|
|
units: '%'
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The sensor's current humidity reading - a relative humidity
|
|
percentage. -1 indicates an invalid reading due to either a
|
|
sensor that doesn't read humidity or lost communications.
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: humidity
|
|
- tag: component
|
|
value: power
|
|
- uuid: d04af1687eb846d18b57af04ab1b594b
|
|
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.2.9.{#SNMPINDEX}]'
|
|
key: 'external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}]'
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The alarm status of the sensor. Possible values:
|
|
uioNormal (1),
|
|
uioWarning (2),
|
|
uioCritical (3),
|
|
sensorStatusNotApplicable (4)
|
|
valuemap:
|
|
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: health
|
|
- tag: component
|
|
value: power
|
|
trigger_prototypes:
|
|
- uuid: 8a62bc38e49e4779938c45839a190856
|
|
expression: 'last(/APC UPS by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3'
|
|
name: 'APC UPS: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical'
|
|
priority: HIGH
|
|
description: 'The external sensor has returned a value greater than the critical threshold.'
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: ca02e8f92e134dce9834bd1d6f3ab469
|
|
expression: 'last(/APC UPS by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4'
|
|
name: 'APC UPS: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable'
|
|
priority: INFO
|
|
description: 'The external sensor does not work or is not connected.'
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: 36ad29900db7410782daeddb9d7c648f
|
|
expression: 'last(/APC UPS by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2'
|
|
name: 'APC UPS: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning'
|
|
priority: AVERAGE
|
|
description: 'The external sensor has returned a value greater than the warning threshold.'
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: bbf611aad1454b38ad39fa258239394a
|
|
name: '{#EXTERNAL_SENSOR2_NAME}: Temperature sensor'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.2.6.{#SNMPINDEX}]'
|
|
key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.2.{#SNMPINDEX}]'
|
|
value_type: FLOAT
|
|
units: ℃
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The sensor's current temperature reading in Celsius.
|
|
-1 indicates an invalid reading due to lost communications.
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: power
|
|
- tag: component
|
|
value: temperature
|
|
overrides:
|
|
- name: Temp
|
|
step: '1'
|
|
filter:
|
|
conditions:
|
|
- macro: '{#EXTERNAL_SENSOR2_NAME}'
|
|
value: Temp
|
|
formulaid: A
|
|
operations:
|
|
- operationobject: ITEM_PROTOTYPE
|
|
operator: LIKE
|
|
value: Humidity
|
|
discover: NO_DISCOVER
|
|
- uuid: 16e8b3b4d38040a7961b1de4c18a4ea9
|
|
name: 'Input phases discovery'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.2.3.1.2.1.1]'
|
|
key: input.phases.discovery
|
|
delay: 1h
|
|
description: 'The input phase identifier. OID upsPhaseInputPhaseIndex.1.1'
|
|
item_prototypes:
|
|
- uuid: a1b8277cd1b248348263c233ab05fd4f
|
|
name: '{#PHASEINDEX}: Phase input current'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.2.3.1.6.1.1.{#PHASEINDEX}]'
|
|
key: 'phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]'
|
|
value_type: FLOAT
|
|
units: A
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The input current in 0.1 amperes, or -0.1 if it's
|
|
unsupported by this UPS.
|
|
preprocessing:
|
|
- type: MULTIPLIER
|
|
parameters:
|
|
- '0.1'
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: power
|
|
- uuid: 40c05eaf739540979d11787a694cb8c9
|
|
name: '{#PHASEINDEX}: Phase input voltage'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.2.3.1.3.1.1.{#PHASEINDEX}]'
|
|
key: 'phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]'
|
|
value_type: FLOAT
|
|
units: V
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The input voltage in VAC, or -1 if it's unsupported
|
|
by this UPS.
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: power
|
|
trigger_prototypes:
|
|
- uuid: 63c623a2a9af44f38388a17742c87486
|
|
expression: 'min(/APC UPS by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
|
|
name: 'APC UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage'
|
|
event_name: 'APC UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
|
|
opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
- uuid: ba649e1239384e3e8ebe6ae29394aecb
|
|
name: 'Output phases discovery'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.3.3.1.2.1.1]'
|
|
key: output.phases.discovery
|
|
delay: 1h
|
|
description: 'The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1'
|
|
item_prototypes:
|
|
- uuid: cfdded918e444958b5c592efae76b96e
|
|
name: '{#PHASEINDEX}: Phase output current'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.3.3.1.4.1.1.{#PHASEINDEX}]'
|
|
key: 'phase.output.current[upsPhaseOutputCurrent.1.1.{#PHASEINDEX}]'
|
|
value_type: FLOAT
|
|
units: A
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The output current in 0.1 amperes drawn
|
|
by the load on the UPS, or -1 if it's unsupported
|
|
by this UPS.
|
|
preprocessing:
|
|
- type: MULTIPLIER
|
|
parameters:
|
|
- '0.1'
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: power
|
|
- uuid: 262d5cf179e64a2596edd86adc5570e3
|
|
name: '{#PHASEINDEX}: Phase output load, %'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.3.3.1.10.1.1.{#PHASEINDEX}]'
|
|
key: 'phase.output.load.percent[upsPhaseOutputPercentLoad.1.1.{#PHASEINDEX}]'
|
|
value_type: FLOAT
|
|
units: '%'
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The percentage of the UPS load capacity in VA at
|
|
redundancy @ (n + x) presently being used on this
|
|
output phase, or -1 if it's unsupported by this UPS.
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: power
|
|
- uuid: ab38f845f0e448f0b3638f6728cbf5bf
|
|
name: '{#PHASEINDEX}: Phase output voltage'
|
|
type: SNMP_AGENT
|
|
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.3.3.1.3.1.1.{#PHASEINDEX}]'
|
|
key: 'phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]'
|
|
value_type: FLOAT
|
|
units: V
|
|
description: |
|
|
MIB: PowerNet-MIB
|
|
The output voltage in VAC, or -1 if it's unsupported
|
|
by this UPS.
|
|
preprocessing:
|
|
- type: DISCARD_UNCHANGED_HEARTBEAT
|
|
parameters:
|
|
- 6h
|
|
tags:
|
|
- tag: component
|
|
value: power
|
|
trigger_prototypes:
|
|
- uuid: feeb23a58ccb4ec1bed9d61f5d2ffc9e
|
|
expression: 'min(/APC UPS by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
|
|
name: 'APC UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage'
|
|
event_name: 'APC UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
|
|
opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}'
|
|
priority: HIGH
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
tags:
|
|
- tag: class
|
|
value: power
|
|
- tag: target
|
|
value: apc
|
|
macros:
|
|
- macro: '{$BATTERY.CAPACITY.MIN.WARN}'
|
|
value: '50'
|
|
description: 'Minimum battery capacity percentage for trigger expression.'
|
|
- macro: '{$BATTERY.TEMP.MAX.WARN}'
|
|
value: '55'
|
|
description: 'Maximum battery temperature for trigger expression.'
|
|
- macro: '{$SNMP.TIMEOUT}'
|
|
value: 5m
|
|
description: 'The time interval for SNMP agent availability trigger expression.'
|
|
- macro: '{$TIME.PERIOD}'
|
|
value: 15m
|
|
description: 'Time period for trigger expression.'
|
|
- macro: '{$UPS.INPUT_FREQ.MAX.WARN}'
|
|
value: '50.3'
|
|
description: 'Maximum input frequency for trigger expression.'
|
|
- macro: '{$UPS.INPUT_FREQ.MIN.WARN}'
|
|
value: '49.7'
|
|
description: 'Minimum input frequency for trigger expression.'
|
|
- macro: '{$UPS.INPUT_VOLT.MAX.WARN}'
|
|
value: '243'
|
|
description: 'Maximum input voltage for trigger expression.'
|
|
- macro: '{$UPS.INPUT_VOLT.MIN.WARN}'
|
|
value: '197'
|
|
description: 'Minimum input voltage for trigger expression.'
|
|
- macro: '{$UPS.OUTPUT.MAX.WARN}'
|
|
value: '80'
|
|
description: 'Maximum output load in % for trigger expression.'
|
|
dashboards:
|
|
- uuid: 1cd6a60d856944429e04ce20d5714e88
|
|
name: 'APC UPS: General'
|
|
pages:
|
|
- name: 'APC UPS: General'
|
|
widgets:
|
|
- type: graph
|
|
name: Voltage
|
|
width: '36'
|
|
height: '5'
|
|
fields:
|
|
- type: GRAPH
|
|
name: graphid.0
|
|
value:
|
|
host: 'APC UPS by SNMP'
|
|
name: 'APC UPS: Voltage'
|
|
- type: STRING
|
|
name: reference
|
|
value: AAAAA
|
|
- type: graph
|
|
name: 'Capacity of the UPS batteries'
|
|
'y': '5'
|
|
width: '36'
|
|
height: '5'
|
|
fields:
|
|
- type: GRAPH
|
|
name: graphid.0
|
|
value:
|
|
host: 'APC UPS by SNMP'
|
|
name: 'APC UPS: Capacity of the UPS batteries'
|
|
- type: STRING
|
|
name: reference
|
|
value: AAAAC
|
|
- type: graph
|
|
name: Output
|
|
x: '36'
|
|
width: '36'
|
|
height: '5'
|
|
fields:
|
|
- type: GRAPH
|
|
name: graphid.0
|
|
value:
|
|
host: 'APC UPS by SNMP'
|
|
name: 'APC UPS: Output'
|
|
- type: STRING
|
|
name: reference
|
|
value: AAAAB
|
|
valuemaps:
|
|
- uuid: a808aadebf964e0cb6b8724bf1165013
|
|
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
|
|
mappings:
|
|
- value: '1'
|
|
newvalue: Normal
|
|
- value: '2'
|
|
newvalue: Warning
|
|
- value: '3'
|
|
newvalue: Critical
|
|
- value: '4'
|
|
newvalue: 'Not applicable'
|
|
- uuid: 731b036e41d147ba81bfcfb7e99b561b
|
|
name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator'
|
|
mappings:
|
|
- value: '1'
|
|
newvalue: 'no Battery Needs Replacing'
|
|
- value: '2'
|
|
newvalue: 'battery Needs Replacing'
|
|
- uuid: f310a0bceb06404d9daee67ab578e4b8
|
|
name: 'PowerNet-MIB::upsAdvInputLineFailCause'
|
|
mappings:
|
|
- value: '1'
|
|
newvalue: 'no Transfer'
|
|
- value: '2'
|
|
newvalue: 'High Line Voltage'
|
|
- value: '3'
|
|
newvalue: Brownout
|
|
- value: '4'
|
|
newvalue: Blackout
|
|
- value: '5'
|
|
newvalue: 'Small Momentary Sag'
|
|
- value: '6'
|
|
newvalue: 'Deep Momentary Sag'
|
|
- value: '7'
|
|
newvalue: 'Small Momentary Spike'
|
|
- value: '8'
|
|
newvalue: 'Large Momentary Spike'
|
|
- value: '9'
|
|
newvalue: 'Self Test'
|
|
- value: '10'
|
|
newvalue: 'Rate of Voltage Change'
|
|
- uuid: 795c75c652124ad282bad3dfd50b8e39
|
|
name: 'PowerNet-MIB::upsBasicBatteryStatus'
|
|
mappings:
|
|
- value: '1'
|
|
newvalue: Unknown
|
|
- value: '2'
|
|
newvalue: Normal
|
|
- value: '3'
|
|
newvalue: Low
|
|
- value: '4'
|
|
newvalue: 'In Fault Condition'
|
|
- uuid: c536d9dc64724643a9291c9b601b1eac
|
|
name: 'PowerNet-MIB::upsBasicOutputStatus'
|
|
mappings:
|
|
- value: '1'
|
|
newvalue: Unknown
|
|
- value: '2'
|
|
newvalue: Online
|
|
- value: '3'
|
|
newvalue: 'On Battery'
|
|
- value: '4'
|
|
newvalue: 'On Smart Boost'
|
|
- value: '5'
|
|
newvalue: 'Timed Sleeping'
|
|
- value: '6'
|
|
newvalue: 'Software Bypass'
|
|
- value: '7'
|
|
newvalue: 'Off'
|
|
- value: '8'
|
|
newvalue: Rebooting
|
|
- value: '9'
|
|
newvalue: 'Switched Bypass'
|
|
- value: '10'
|
|
newvalue: 'Hardware Failure Bypass'
|
|
- value: '11'
|
|
newvalue: 'Sleeping Until Power Return'
|
|
- value: '12'
|
|
newvalue: 'On Smart Trim'
|
|
- value: '13'
|
|
newvalue: 'Eco Mode'
|
|
- value: '14'
|
|
newvalue: 'Hot Standby'
|
|
- value: '15'
|
|
newvalue: 'On Battery Test'
|
|
- value: '16'
|
|
newvalue: 'Emergency Static Bypass'
|
|
- value: '17'
|
|
newvalue: 'Static Bypass Standby'
|
|
- value: '18'
|
|
newvalue: 'Power Saving Mode'
|
|
- value: '19'
|
|
newvalue: 'Spot Mode'
|
|
- value: '20'
|
|
newvalue: E-Conversion
|
|
- value: '21'
|
|
newvalue: 'Charger Spotmode'
|
|
- value: '22'
|
|
newvalue: 'Inverter Spotmode'
|
|
- value: '23'
|
|
newvalue: 'Active Load'
|
|
- value: '24'
|
|
newvalue: 'Battery Discharge Spotmode'
|
|
- value: '25'
|
|
newvalue: 'Inverter Standby'
|
|
- value: '26'
|
|
newvalue: 'Charger Only'
|
|
- uuid: 781c568d935d40f2a43951488cf2e046
|
|
name: zabbix.host.available
|
|
mappings:
|
|
- value: '0'
|
|
newvalue: 'not available'
|
|
- value: '1'
|
|
newvalue: available
|
|
- value: '2'
|
|
newvalue: unknown
|
|
triggers:
|
|
- uuid: b0959bdb606542bcb2952e820ac972c9
|
|
expression: |
|
|
(last(/APC UPS by SNMP/system.hw.uptime[hrSystemUptime.0])>0 and last(/APC UPS by SNMP/system.hw.uptime[hrSystemUptime.0])<10m)
|
|
or (last(/APC UPS by SNMP/system.hw.uptime[hrSystemUptime.0])=0 and last(/APC UPS by SNMP/system.net.uptime[sysUpTime.0])<10m)
|
|
name: 'APC UPS: Host has been restarted'
|
|
event_name: 'APC UPS: {HOST.NAME} has been restarted (uptime < 10m)'
|
|
priority: WARNING
|
|
description: 'Uptime is less than 10 minutes.'
|
|
manual_close: 'YES'
|
|
dependencies:
|
|
- name: 'APC UPS: No SNMP data collection'
|
|
expression: 'max(/APC UPS by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
|
|
tags:
|
|
- tag: scope
|
|
value: notice
|
|
graphs:
|
|
- uuid: 2f54cf3da7be49108736e46afe0b5904
|
|
name: 'APC UPS: Capacity of the UPS batteries'
|
|
type: PIE
|
|
graph_items:
|
|
- color: 199C0D
|
|
item:
|
|
host: 'APC UPS by SNMP'
|
|
key: 'battery.capacity[upsHighPrecBatteryCapacity]'
|
|
- uuid: d4b2320e0515407cb32afa388f91cd29
|
|
name: 'APC UPS: Output'
|
|
graph_items:
|
|
- color: 199C0D
|
|
item:
|
|
host: 'APC UPS by SNMP'
|
|
key: 'output.current[upsHighPrecOutputCurrent]'
|
|
- sortorder: '1'
|
|
color: F63100
|
|
item:
|
|
host: 'APC UPS by SNMP'
|
|
key: 'output.load[upsHighPrecOutputLoad]'
|
|
- uuid: 4988c266dc15493592112371b061f9e2
|
|
name: 'APC UPS: Voltage'
|
|
graph_items:
|
|
- color: 199C0D
|
|
item:
|
|
host: 'APC UPS by SNMP'
|
|
key: 'input.voltage[upsHighPrecInputLineVoltage]'
|
|
- sortorder: '1'
|
|
color: F63100
|
|
item:
|
|
host: 'APC UPS by SNMP'
|
|
key: 'output.voltage[upsHighPrecOutputVoltage]'
|