Files
templates-default/Morningstar_TriStar_PWM_by_SNMP.yaml

1169 lines
50 KiB
YAML

zabbix_export:
version: '7.0'
template_groups:
- uuid: 36bff6c29af64692839d077febfc7079
name: 'Templates/Network devices'
templates:
- uuid: 230fa9f7c1774821bbe6cdcbbba5cbc6
template: 'Morningstar TriStar PWM by SNMP'
name: 'Morningstar TriStar PWM by SNMP'
description: |
MIBs used:
TRISTAR
Generated by official Zabbix template tool "Templator"
vendor:
name: Zabbix
version: 7.0-2
groups:
- name: 'Templates/Network devices'
items:
- uuid: b76ef47ada0c43cfb50c6a80c8ca55e5
name: 'Battery: Battery Voltage discovery'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.8.30.0]'
key: 'battery.voltage.discovery[batteryVoltage.0]'
delay: 15m
history: '0'
value_type: FLOAT
units: V
description: |
MIB: TRISTAR
Description:Battery voltage
Scaling Factor:0.002950042724609375
Units:V
Range:[0.0, 80.0]
Modbus address:0x0008
preprocessing:
- type: MULTIPLIER
parameters:
- '0.002950042725'
tags:
- tag: component
value: battery
- tag: component
value: discovery
- tag: component
value: raw
- uuid: 0c57da022cf8497e88f788cee1b3a0a6
name: 'Status: Control Mode'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.8.45.0]'
key: 'control.mode[controlMode.0]'
value_type: FLOAT
description: |
MIB: TRISTAR
Description:Control Mode
Modbus address:0x001A
0: charge
1: loadControl
2: diversion
3: lighting
valuemap:
name: 'TriStar PWM control mode'
tags:
- tag: component
value: status
- uuid: 25a576060f6948e59a855462b04c7276
name: 'Counter: Amp-hours'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.8.39.0]'
key: 'counter.charge_amp_hours[ahResettable.0]'
value_type: FLOAT
units: Ah
description: |
MIB: TRISTAR
Description:Ah (Resettable)
Scaling Factor:0.1
Units:Ah
Range:[0.0, 50000.0]
Modbus addresses:H=0x0011 L=0x0012
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
tags:
- tag: component
value: counter
- uuid: d2351af0b6244044949eba67a7f7b39c
name: 'Counter: KW-hours'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.8.49.0]'
key: 'counter.charge_kw_hours[kilowattHours.0]'
value_type: FLOAT
units: '!kWh'
description: |
MIB: TRISTAR
Description:Kilowatt Hours
Scaling Factor:1.0
Units:kWh
Range:[0.0, 5000.0]
Modbus address:0x001E
preprocessing:
- type: MULTIPLIER
parameters:
- '0.001'
- type: REGEX
parameters:
- '^(\d+)(\.\d{1,2})?'
- \1\2
tags:
- tag: component
value: counter
- uuid: 03c3397ac32b47499002b13e0735ec9b
name: 'Status: Alarms'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.8.42.0]'
key: 'status.alarms[alarms.0]'
history: 1h
value_type: TEXT
trends: '0'
description: |
MIB: TRISTAR
Description:Alarms
Modbus addresses:H=0x001D L=0x0017
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
- type: JAVASCRIPT
parameters:
- |
var FIELDS = [
'rtsOpen',
'rtsShorted',
'rtsDisconnected',
'heatsinkTempSensorOpen',
'heatsinkTempSensorShorted',
'tristarHot',
'currentLimit',
'currentOffset',
'batterySense',
'batterySenseDisconnected',
'uncalibrated',
'rtsMiswire',
'highVoltageDisconnect',
'diversionLoadNearMax',
'systemMiswire',
'mosfetSOpen',
'p12VoltageReferenceOff',
'loadDisconnectState',
];
var flags = parseInt(value.replace(/\x20/g, ''), 16),
result = [];
for (var i = 0, f = 1 << 31 >>> 0, l = FIELDS.length; i < l; i++, f >>>= 1) {
if (flags & f) {
result.push(FIELDS[i]);
}
}
return result.length ? result.join('\n') : 'No alarms';
tags:
- tag: component
value: status
triggers:
- uuid: 121d47c6bbdd45bca261df2e01ea41c6
expression: 'count(/Morningstar TriStar PWM by SNMP/status.alarms[alarms.0],#3,"like","batterySense")=2'
name: 'Morningstar TriStar PWM: Status: Device has "batterySense" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: fd2d9290144143d39bb5a3cf0a2d261f
expression: 'count(/Morningstar TriStar PWM by SNMP/status.alarms[alarms.0],#3,"like","batterySenseDisconnected")=2'
name: 'Morningstar TriStar PWM: Status: Device has "batterySenseDisconnected" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 83d5b8d52acd4e21ac6d3a9cf05dcd04
expression: 'count(/Morningstar TriStar PWM by SNMP/status.alarms[alarms.0],#3,"like","currentLimit")=2'
name: 'Morningstar TriStar PWM: Status: Device has "currentLimit" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: d9529a4372d848038e6ee561d62e9f22
expression: 'count(/Morningstar TriStar PWM by SNMP/status.alarms[alarms.0],#3,"like","currentOffset")=2'
name: 'Morningstar TriStar PWM: Status: Device has "currentOffset" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 5f3983acc1cc417e860c1305b11c15ea
expression: 'count(/Morningstar TriStar PWM by SNMP/status.alarms[alarms.0],#3,"like","diversionLoadNearMax")=2'
name: 'Morningstar TriStar PWM: Status: Device has "diversionLoadNearMax" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 878e04df7e7b416bb0d2213b5dbb80e6
expression: 'count(/Morningstar TriStar PWM by SNMP/status.alarms[alarms.0],#3,"like","heatsinkTempSensorOpen")=2'
name: 'Morningstar TriStar PWM: Status: Device has "heatsinkTempSensorOpen" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: c642ed9496ce4322809c7142d32929a5
expression: 'count(/Morningstar TriStar PWM by SNMP/status.alarms[alarms.0],#3,"like","heatsinkTempSensorShorted")=2'
name: 'Morningstar TriStar PWM: Status: Device has "heatsinkTempSensorShorted" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 532421fe17bf4732a01a6990e34e649a
expression: 'count(/Morningstar TriStar PWM by SNMP/status.alarms[alarms.0],#3,"like","highVoltageDisconnect")=2'
name: 'Morningstar TriStar PWM: Status: Device has "highVoltageDisconnect" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: ae90e8034baf4b21906d56d18bfa4da8
expression: 'count(/Morningstar TriStar PWM by SNMP/status.alarms[alarms.0],#3,"like","loadDisconnectState")=2'
name: 'Morningstar TriStar PWM: Status: Device has "loadDisconnectState" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 8d8b721c6dee40499b29bee44b21589a
expression: 'count(/Morningstar TriStar PWM by SNMP/status.alarms[alarms.0],#3,"like","mosfetSOpen")=2'
name: 'Morningstar TriStar PWM: Status: Device has "mosfetSOpen" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 8cda8e5773de4583b9baa6a6e542e32c
expression: 'count(/Morningstar TriStar PWM by SNMP/status.alarms[alarms.0],#3,"like","p12VoltageReferenceOff")=2'
name: 'Morningstar TriStar PWM: Status: Device has "p12VoltageReferenceOff" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 1b6192b8ca364c229b35ba6de89ad56b
expression: 'count(/Morningstar TriStar PWM by SNMP/status.alarms[alarms.0],#3,"like","rtsDisconnected")=2'
name: 'Morningstar TriStar PWM: Status: Device has "rtsDisconnected" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 176de77a142d45a3ac39ea42989e209c
expression: 'count(/Morningstar TriStar PWM by SNMP/status.alarms[alarms.0],#3,"like","rtsMiswire")=2'
name: 'Morningstar TriStar PWM: Status: Device has "rtsMiswire" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: f63029eabc8e498ea7e6336d312ac169
expression: 'count(/Morningstar TriStar PWM by SNMP/status.alarms[alarms.0],#3,"like","rtsShorted")=2'
name: 'Morningstar TriStar PWM: Status: Device has "rtsShorted" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 480b69c1febf45a2971788c2f967c45d
expression: 'count(/Morningstar TriStar PWM by SNMP/status.alarms[alarms.0],#3,"like","systemMiswire")=2'
name: 'Morningstar TriStar PWM: Status: Device has "systemMiswire" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 4a287e4086c4458aaa3dc48bbb8ee219
expression: 'count(/Morningstar TriStar PWM by SNMP/status.alarms[alarms.0],#3,"like","tristarHot")=2'
name: 'Morningstar TriStar PWM: Status: Device has "tristarHot" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: de665482d2574730a3a839948dd730ea
expression: 'count(/Morningstar TriStar PWM by SNMP/status.alarms[alarms.0],#3,"like","uncalibrated")=2'
name: 'Morningstar TriStar PWM: Status: Device has "uncalibrated" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 9d0f4444f98c4ec082d35559e8fe9ac5
name: 'Status: Faults'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.8.43.0]'
key: 'status.faults[faults.0]'
history: 1h
value_type: TEXT
trends: '0'
description: |
MIB: TRISTAR
Description:Battery voltage
Scaling Factor:0.002950042724609375
Units:V
Range:[0.0, 80.0]
Modbus address:0x0008
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
- type: JAVASCRIPT
parameters:
- |
var FIELDS = [
'externalShort',
'overcurrent',
'mosfetSShorted',
'softwareFault',
'highVoltageDisconnect',
'tristarHot',
'dipSwitchChange',
'customSettingsEdit',
'reset',
'systemMiswire',
'rtsShorted',
'rtsDisconnected',
];
var flags = parseInt(value.replace(/\x20/g, ''), 16),
result = [];
for (var i = 0, f = 1 << 31 >>> 0, l = FIELDS.length; i < l; i++, f >>>= 1) {
if (flags & f) {
result.push(FIELDS[i]);
}
}
return result.length ? result.join('\n') : 'No faults';
tags:
- tag: component
value: status
triggers:
- uuid: 514b041aebdd4ddb8ab2d1222c0ef295
expression: 'count(/Morningstar TriStar PWM by SNMP/status.faults[faults.0],#3,"like","customSettingsEdit")=2'
name: 'Morningstar TriStar PWM: Status: Device has "customSettingsEdit" faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 1a40ce8b87f04ab1b4f30387e9ce2d9d
expression: 'count(/Morningstar TriStar PWM by SNMP/status.faults[faults.0],#3,"like","dipSwitchChange")=2'
name: 'Morningstar TriStar PWM: Status: Device has "dipSwitchChange" faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 49b120c3933c43b1b7f5c77f7b359997
expression: 'count(/Morningstar TriStar PWM by SNMP/status.faults[faults.0],#3,"like","externalShort")=2'
name: 'Morningstar TriStar PWM: Status: Device has "externalShort" faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: f063b9f717c44ab988db7ac95bfca68f
expression: 'count(/Morningstar TriStar PWM by SNMP/status.faults[faults.0],#3,"like","highVoltageDisconnect")=2'
name: 'Morningstar TriStar PWM: Status: Device has "highVoltageDisconnect" faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 468716d748f1470cb764ce1af922164d
expression: 'count(/Morningstar TriStar PWM by SNMP/status.faults[faults.0],#3,"like","mosfetSShorted")=2'
name: 'Morningstar TriStar PWM: Status: Device has "mosfetSShorted" faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: b6f65dfca421490eafff48991cdf1e3b
expression: 'count(/Morningstar TriStar PWM by SNMP/status.faults[faults.0],#3,"like","overcurrent")=2'
name: 'Morningstar TriStar PWM: Status: Device has "overcurrent" faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 73561a5765694633b1dc0ef1b1f60fd4
expression: 'count(/Morningstar TriStar PWM by SNMP/status.faults[faults.0],#3,"like","reset")=2'
name: 'Morningstar TriStar PWM: Status: Device has "reset" faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: d14c7d928f57448390c2b4c588a28c65
expression: 'count(/Morningstar TriStar PWM by SNMP/status.faults[faults.0],#3,"like","rtsDisconnected")=2'
name: 'Morningstar TriStar PWM: Status: Device has "rtsDisconnected" faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: d94067598c234968b4929404067eff86
expression: 'count(/Morningstar TriStar PWM by SNMP/status.faults[faults.0],#3,"like","rtsShorted")=2'
name: 'Morningstar TriStar PWM: Status: Device has "rtsShorted" faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 886b18bee7cd4f8eb454973e2d2ae59f
expression: 'count(/Morningstar TriStar PWM by SNMP/status.faults[faults.0],#3,"like","softwareFault")=2'
name: 'Morningstar TriStar PWM: Status: Device has "softwareFault" faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 2e520cdafaaa4eefad5ebea71819c3a6
expression: 'count(/Morningstar TriStar PWM by SNMP/status.faults[faults.0],#3,"like","systemMiswire")=2'
name: 'Morningstar TriStar PWM: Status: Device has "systemMiswire" faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 041be44e639d4d1eadb15230a678e278
expression: 'count(/Morningstar TriStar PWM by SNMP/status.faults[faults.0],#3,"like","tristarHot")=2'
name: 'Morningstar TriStar PWM: Status: Device has "tristarHot" faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 6903297e21e14aa8b5eed4eb0f7e1e01
name: 'Status: Uptime (hardware)'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.25.1.1.0]'
key: status.hw.uptime
units: uptime
description: 'The amount of time since this host was last initialized. Note that this is different from sysUpTime in the SNMPv2-MIB [RFC1907] because sysUpTime is the uptime of the network management portion of the system.'
preprocessing:
- type: CHECK_NOT_SUPPORTED
parameters:
- '-1'
error_handler: CUSTOM_VALUE
error_handler_params: '0'
- type: MULTIPLIER
parameters:
- '0.01'
tags:
- tag: component
value: status
- uuid: 642eec19ba5d450186590e9f5bba36db
name: 'Status: Uptime (network)'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.3.0]'
key: status.net.uptime
units: uptime
description: 'The time (in hundredths of a second) since the network management portion of the system was last re-initialized.'
preprocessing:
- type: MULTIPLIER
parameters:
- '0.01'
tags:
- tag: component
value: status
triggers:
- uuid: 64aa2a79fe854def8e179a4d27790417
expression: 'nodata(/Morningstar TriStar PWM by SNMP/status.net.uptime,5m)=1'
name: 'Morningstar TriStar PWM: Status: Failed to fetch data'
event_name: 'Morningstar TriStar PWM: Status: Failed to fetch data (or no data for 5m)'
priority: WARNING
description: 'Zabbix has not received data for items for the last 5 minutes.'
manual_close: 'YES'
tags:
- tag: scope
value: availability
- uuid: bc729e23973b4d9d97d694d884431e0b
name: 'Temperature: Battery'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.8.37.0]'
key: 'temp.battery[batteryTemperature.0]'
value_type: FLOAT
units: C
description: |
MIB: TRISTAR
Description:Battery Temperature
Scaling Factor:1.0
Units:deg C
Range:[-40, 120]
Modbus address:0x000F
tags:
- tag: component
value: temperature
triggers:
- uuid: e759b90e2bf44bbb8e5efe5b9e458e40
expression: 'min(/Morningstar TriStar PWM by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.CRIT}'
name: 'Morningstar TriStar PWM: Temperature: Critically high battery temperature'
event_name: 'Morningstar TriStar PWM: Temperature: Critically high battery temperature (over {$BATTERY.TEMP.MAX.CRIT}C for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: e57f335f657d45768509f139d31dcdae
expression: 'max(/Morningstar TriStar PWM by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.CRIT}'
name: 'Morningstar TriStar PWM: Temperature: Critically low battery temperature'
event_name: 'Morningstar TriStar PWM: Temperature: Critically low battery temperature (below {$BATTERY.TEMP.MIN.WARN}C for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 7d1444dba9334e91ad425a6f2ff9fef9
expression: 'min(/Morningstar TriStar PWM by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.WARN}'
name: 'Morningstar TriStar PWM: Temperature: High battery temperature'
event_name: 'Morningstar TriStar PWM: Temperature: High battery temperature (over {$BATTERY.TEMP.MAX.WARN}C for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar TriStar PWM: Temperature: Critically high battery temperature'
expression: 'min(/Morningstar TriStar PWM by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.CRIT}'
tags:
- tag: scope
value: notice
- uuid: 14fe4a22b28c4d08a24da51a54e36e81
expression: 'max(/Morningstar TriStar PWM by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.WARN}'
name: 'Morningstar TriStar PWM: Temperature: Low battery temperature'
event_name: 'Morningstar TriStar PWM: Temperature: Low battery temperature (below {$BATTERY.TEMP.MIN.WARN}C for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar TriStar PWM: Temperature: Critically low battery temperature'
expression: 'max(/Morningstar TriStar PWM by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.CRIT}'
tags:
- tag: scope
value: notice
- uuid: a9a009058e99419dbb6cbef5b7797388
name: 'Temperature: Heatsink'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.8.36.0]'
key: 'temp.heatsink[heatsinkTemperature.0]'
value_type: FLOAT
units: C
description: |
MIB: TRISTAR
Description:Heatsink Temperature
Scaling Factor:1.0
Units:deg C
Range:[-40, 120]
Modbus address:0x000E
tags:
- tag: component
value: temperature
discovery_rules:
- uuid: 0e06c296579f4b6aa40d69ebb62742b4
name: 'Battery voltage discovery'
type: DEPENDENT
key: battery.voltage.discovery
delay: '0'
description: 'Discovery for battery voltage triggers'
item_prototypes:
- uuid: e1960caed8c44606bb684e28cdfac3c7
name: 'Battery: Voltage{#SINGLETON}'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.8.30.0]'
key: 'battery.voltage[batteryVoltage.0{#SINGLETON}]'
value_type: FLOAT
units: V
description: |
MIB: TRISTAR
Description:Battery voltage
Scaling Factor:0.002950042724609375
Units:V
Range:[0.0, 80.0]
Modbus address:0x0008
preprocessing:
- type: MULTIPLIER
parameters:
- '0.002950042725'
- type: REGEX
parameters:
- '^(\d+)(\.\d{1,2})?'
- \1\2
tags:
- tag: component
value: battery
trigger_prototypes:
- uuid: 156ec13d673b4a8aa02a87b1794cb722
expression: 'min(/Morningstar TriStar PWM by SNMP/battery.voltage[batteryVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.CRIT}'
name: 'Morningstar TriStar PWM: Battery: Critically high battery voltage'
event_name: 'Morningstar TriStar PWM: Battery: Critically high battery voltage (over {#VOLTAGE.MAX.CRIT}V for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: capacity
- uuid: 5e4400321f4f45b39397c68a4ba54d8e
expression: 'max(/Morningstar TriStar PWM by SNMP/battery.voltage[batteryVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.CRIT}'
name: 'Morningstar TriStar PWM: Battery: Critically low battery voltage'
event_name: 'Morningstar TriStar PWM: Battery: Critically low battery voltage (below {#VOLTAGE.MIN.CRIT}V for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: capacity
- uuid: fa6502a4a0214f7f933e982182d21d6b
expression: 'min(/Morningstar TriStar PWM by SNMP/battery.voltage[batteryVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.WARN}'
name: 'Morningstar TriStar PWM: Battery: High battery voltage'
event_name: 'Morningstar TriStar PWM: Battery: High battery voltage (over {#VOLTAGE.MAX.WARN}V for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar TriStar PWM: Battery: Critically high battery voltage'
expression: 'min(/Morningstar TriStar PWM by SNMP/battery.voltage[batteryVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.CRIT}'
tags:
- tag: scope
value: capacity
- uuid: a5275748f4c742ea8ab9efd266901e95
expression: 'max(/Morningstar TriStar PWM by SNMP/battery.voltage[batteryVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.WARN}'
name: 'Morningstar TriStar PWM: Battery: Low battery voltage'
event_name: 'Morningstar TriStar PWM: Battery: Low battery voltage (below {#VOLTAGE.MIN.WARN}V for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar TriStar PWM: Battery: Critically low battery voltage'
expression: 'max(/Morningstar TriStar PWM by SNMP/battery.voltage[batteryVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.CRIT}'
tags:
- tag: scope
value: capacity
graph_prototypes:
- uuid: bbdea967f4f34a299dd8d9bee43f2841
name: 'Battery: Voltage{#SINGLETON}'
graph_items:
- drawtype: GRADIENT_LINE
color: 199C0D
item:
host: 'Morningstar TriStar PWM by SNMP'
key: 'battery.voltage[batteryVoltage.0{#SINGLETON}]'
master_item:
key: 'battery.voltage.discovery[batteryVoltage.0]'
preprocessing:
- type: JAVASCRIPT
parameters:
- |
var v_range = [
[[0, 18], [12, 15, 11.5, 15.5]],
[[18, 36], [24, 30, 23, 31]],
[[36, 99], [48, 60, 46, 62]],
],
result = [];
for (var idx in v_range) {
if (v_range[idx][0][0] < value && value <= v_range[idx][0][1]) {
result = [{
'{#VOLTAGE.MIN.WARN}': parseInt({$VOLTAGE.MIN.WARN}) || v_range[idx][1][0],
'{#VOLTAGE.MAX.WARN}': parseInt({$VOLTAGE.MAX.WARN}) || v_range[idx][1][1],
'{#VOLTAGE.MIN.CRIT}': parseInt({$VOLTAGE.MIN.CRIT}) || v_range[idx][1][2],
'{#VOLTAGE.MAX.CRIT}': parseInt({$VOLTAGE.MAX.CRIT}) || v_range[idx][1][3],
'{#SINGLETON}': ''
}];
break;
}
}
return JSON.stringify(result);
- uuid: 58a500192e61490f97f33d5b5f6e972f
name: 'Charge mode discovery'
type: DEPENDENT
key: controlmode.charge.discovery
delay: '0'
lifetime: 1h
description: 'Discovery for device in charge mode'
item_prototypes:
- uuid: f5d120bee1964f10853819d576ddb930
name: 'Array: Voltage{#SINGLETON}'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.8.32.0]'
key: 'array.voltage[arrayloadVoltage.0{#SINGLETON}]'
value_type: FLOAT
units: V
description: |
MIB: TRISTAR
Description:Array/Load Voltage
Scaling Factor:0.00424652099609375
Units:V
Range:[0, 80]
Modbus address:0x000A
preprocessing:
- type: MULTIPLIER
parameters:
- '0.004246520996'
- type: REGEX
parameters:
- '^(\d+)(\.\d{1,2})?'
- \1\2
tags:
- tag: component
value: array
- uuid: b5d74de2e96440a5a00a4a4dffffbb26
name: 'Battery: Charge Current{#SINGLETON}'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.8.33.0]'
key: 'charge.current[chargeCurrent.0{#SINGLETON}]'
value_type: FLOAT
units: A
description: |
MIB: TRISTAR
Description:Charge Current
Scaling Factor:0.002034515380859375
Units:A
Range:[0, 60]
Modbus address:0x000B
preprocessing:
- type: MULTIPLIER
parameters:
- '0.002034515381'
- type: REGEX
parameters:
- '^(\d+)(\.\d{1,2})?'
- \1\2
tags:
- tag: component
value: battery
graph_prototypes:
- uuid: 9886a05be4a74a82a208e3a5950f022d
name: 'Array: Voltage{#SINGLETON}'
graph_items:
- drawtype: GRADIENT_LINE
color: 199C0D
item:
host: 'Morningstar TriStar PWM by SNMP'
key: 'array.voltage[arrayloadVoltage.0{#SINGLETON}]'
- uuid: cd64c57669314d2e9526fbc580034c81
name: 'Battery: Charge Current{#SINGLETON}'
graph_items:
- drawtype: GRADIENT_LINE
color: 199C0D
item:
host: 'Morningstar TriStar PWM by SNMP'
key: 'charge.current[chargeCurrent.0{#SINGLETON}]'
master_item:
key: 'control.mode[controlMode.0]'
preprocessing:
- type: JAVASCRIPT
parameters:
- 'return JSON.stringify(parseInt(value) === 0 ? [{ ''{#SINGLETON}'': '''' }] : []);'
- uuid: 02fbfa1dd59a4b9c87bb81da81312f54
name: 'Charge + Diversion mode discovery'
type: DEPENDENT
key: controlmode.charge_diversion.discovery
delay: '0'
lifetime: 1h
description: 'Discovery for device in charge and diversion modes'
item_prototypes:
- uuid: e08b526bbb484753a11c99011d31d945
name: 'Battery: Charge State{#SINGLETON}'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.8.46.0]'
key: 'charge.state[controlState.0{#SINGLETON}]'
value_type: FLOAT
description: |
MIB: TRISTAR
Description:Control State
Modbus address:0x001B
valuemap:
name: 'TriStar PWM charge state'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
tags:
- tag: component
value: battery
trigger_prototypes:
- uuid: da21473ce79c42269cc24d3e470b7d07
expression: 'last(/Morningstar TriStar PWM by SNMP/charge.state[controlState.0{#SINGLETON}])={$CHARGE.STATE.CRIT}'
name: 'Morningstar TriStar PWM: Battery: Device charge in critical state'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 79a592050bc64c018cfa5c7b779fba02
expression: 'last(/Morningstar TriStar PWM by SNMP/charge.state[controlState.0{#SINGLETON}])={$CHARGE.STATE.WARN}'
name: 'Morningstar TriStar PWM: Battery: Device charge in warning state'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar TriStar PWM: Battery: Device charge in critical state'
expression: 'last(/Morningstar TriStar PWM by SNMP/charge.state[controlState.0{#SINGLETON}])={$CHARGE.STATE.CRIT}'
tags:
- tag: scope
value: notice
- uuid: edd7d01d2523481293f3ac9e8f3c0a00
name: 'Battery: Target Voltage{#SINGLETON}'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.8.38.0]'
key: 'target.voltage[targetVoltage.0{#SINGLETON}]'
value_type: FLOAT
units: V
description: |
MIB: TRISTAR
Description:Target Regulation Voltage
Scaling Factor:0.002950042724609375
Units:V
Range:[0.0, 80.0]
Modbus address:0x0010
preprocessing:
- type: MULTIPLIER
parameters:
- '0.002950042725'
- type: REGEX
parameters:
- '^(\d+)(\.\d{1,2})?'
- \1\2
tags:
- tag: component
value: battery
master_item:
key: 'control.mode[controlMode.0]'
preprocessing:
- type: JAVASCRIPT
parameters:
- |
var mode = parseInt(value);
return JSON.stringify((mode === 0 || mode === 2) ? [{ '{#SINGLETON}': '' }] : []);
- uuid: 8c345c0134fe4d90af83292e557d7309
name: 'Diversion mode discovery'
type: DEPENDENT
key: controlmode.diversion.discovery
delay: '0'
lifetime: 1h
description: 'Discovery for device in diversion mode'
item_prototypes:
- uuid: 33e6b5a75c1e454cb7b7bc0b1426d1b9
name: 'Load: PWM Duty Cycle{#SINGLETON}'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.8.48.0]'
key: 'diversion.pwm_duty_cycle[pwmDutyCycle.0{#SINGLETON}]'
value_type: FLOAT
description: |
MIB: TRISTAR
Description:PWM Duty Cycle
Scaling Factor:0.392156862745098
Units:%
Range:[0.0, 100.0]
Modbus address:0x001C
preprocessing:
- type: MULTIPLIER
parameters:
- '0.3921568627'
- type: REGEX
parameters:
- '^(\d+)(\.\d{1,2})?'
- \1\2
tags:
- tag: component
value: load
master_item:
key: 'control.mode[controlMode.0]'
preprocessing:
- type: JAVASCRIPT
parameters:
- 'return JSON.stringify(parseInt(value) === 2 ? [{ ''{#SINGLETON}'': '''' }] : []);'
- uuid: 54bfd7f730e64af89f937e9b1b6e4d79
name: 'Load mode discovery'
type: DEPENDENT
key: controlmode.load.discovery
delay: '0'
lifetime: 1h
description: 'Discovery for device in load mode'
item_prototypes:
- uuid: 6d42918b9c244f88a23ab1daf2a929ce
name: 'Load: State{#SINGLETON}'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.8.47.0]'
key: 'load.state[loadState.0{#SINGLETON}]'
value_type: FLOAT
description: |
MIB: TRISTAR
Description:Load State
Modbus address:0x001B
0: Start
1: Normal
2: LvdWarning
3: Lvd
4: Fault
5: Disconnect
6: LvdWarning1
7: OverrideLvd
8: Equalize
valuemap:
name: 'TriStar PWM load state'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
tags:
- tag: component
value: load
trigger_prototypes:
- uuid: 9035e0a92d384a3c844b8a4d4ebd1eb9
expression: 'last(/Morningstar TriStar PWM by SNMP/load.state[loadState.0{#SINGLETON}])={$LOAD.STATE.CRIT:"lvd"} or last(/Morningstar TriStar PWM by SNMP/load.state[loadState.0{#SINGLETON}])={$LOAD.STATE.CRIT:"fault"}'
name: 'Morningstar TriStar PWM: Load: Device load in critical state'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: a2d13f97c4bd46bfab8e74a2f2a7df2e
expression: 'last(/Morningstar TriStar PWM by SNMP/load.state[loadState.0{#SINGLETON}])={$LOAD.STATE.WARN:"lvdWarning"} or last(/Morningstar TriStar PWM by SNMP/load.state[loadState.0{#SINGLETON}])={$LOAD.STATE.WARN:"override"}'
name: 'Morningstar TriStar PWM: Load: Device load in warning state'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar TriStar PWM: Load: Device load in critical state'
expression: 'last(/Morningstar TriStar PWM by SNMP/load.state[loadState.0{#SINGLETON}])={$LOAD.STATE.CRIT:"lvd"} or last(/Morningstar TriStar PWM by SNMP/load.state[loadState.0{#SINGLETON}])={$LOAD.STATE.CRIT:"fault"}'
tags:
- tag: scope
value: notice
master_item:
key: 'control.mode[controlMode.0]'
preprocessing:
- type: JAVASCRIPT
parameters:
- 'return JSON.stringify(parseInt(value) === 1 ? [{ ''{#SINGLETON}'': '''' }] : []);'
- uuid: 2e2e01f5c1db4224a97162382c77832c
name: 'Load + Diversion mode discovery'
type: DEPENDENT
key: controlmode.load_diversion.discovery
delay: '0'
lifetime: 1h
description: 'Discovery for device in load and diversion modes'
item_prototypes:
- uuid: b6db019203cc41ca94dcbe54382fdaad
name: 'Load: Current{#SINGLETON}'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.8.34.0]'
key: 'load.current[loadCurrent.0{#SINGLETON}]'
value_type: FLOAT
units: A
description: |
MIB: TRISTAR
Description:Load Current
Scaling Factor:0.00966400146484375
Units:A
Range:[0, 60]
Modbus address:0x000C
preprocessing:
- type: MULTIPLIER
parameters:
- '0.009664001465'
- type: REGEX
parameters:
- '^(\d+)(\.\d{1,2})?'
- \1\2
tags:
- tag: component
value: load
- uuid: f87ddb7d31d748c8917030ede731f37a
name: 'Load: Voltage{#SINGLETON}'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.8.32.0]'
key: 'load.voltage[arrayloadVoltage.0{#SINGLETON}]'
value_type: FLOAT
units: V
description: |
MIB: TRISTAR
Description:Array/Load Voltage
Scaling Factor:0.00424652099609375
Units:V
Range:[0, 80]
Modbus address:0x000A
preprocessing:
- type: MULTIPLIER
parameters:
- '0.004246520996'
- type: REGEX
parameters:
- '^(\d+)(\.\d{1,2})?'
- \1\2
tags:
- tag: component
value: load
graph_prototypes:
- uuid: 91ee10b435144218ab3dfac8f6bf7bdd
name: 'Load: Current{#SINGLETON}'
graph_items:
- drawtype: GRADIENT_LINE
color: 199C0D
item:
host: 'Morningstar TriStar PWM by SNMP'
key: 'load.current[loadCurrent.0{#SINGLETON}]'
- uuid: b4b595193e0c40a2b390f7ce6eefba4a
name: 'Load: Voltage{#SINGLETON}'
graph_items:
- drawtype: GRADIENT_LINE
color: 199C0D
item:
host: 'Morningstar TriStar PWM by SNMP'
key: 'load.voltage[arrayloadVoltage.0{#SINGLETON}]'
master_item:
key: 'control.mode[controlMode.0]'
preprocessing:
- type: JAVASCRIPT
parameters:
- |
var mode = parseInt(value);
return JSON.stringify((mode === 1 || mode === 2) ? [{ '{#SINGLETON}': '' }] : []);
tags:
- tag: class
value: power
- tag: target
value: morningstar
macros:
- macro: '{$BATTERY.TEMP.MAX.CRIT}'
value: '60'
description: 'Battery high temperature critical value'
- macro: '{$BATTERY.TEMP.MAX.WARN}'
value: '45'
description: 'Battery high temperature warning value'
- macro: '{$BATTERY.TEMP.MIN.CRIT}'
value: '-20'
description: 'Battery low temperature critical value'
- macro: '{$BATTERY.TEMP.MIN.WARN}'
value: '0'
description: 'Battery low temperature warning value'
- macro: '{$CHARGE.STATE.CRIT}'
value: '4'
description: fault
- macro: '{$CHARGE.STATE.WARN}'
value: '2'
description: disconnect
- macro: '{$LOAD.STATE.CRIT:"fault"}'
value: '4'
description: fault
- macro: '{$LOAD.STATE.CRIT:"lvd"}'
value: '3'
description: lvd
- macro: '{$LOAD.STATE.WARN:"disconnect"}'
value: '5'
description: disconnect
- macro: '{$LOAD.STATE.WARN:"lvdWarning"}'
value: '2'
description: lvdWarning
- macro: '{$LOAD.STATE.WARN:"override"}'
value: '7'
description: override
- macro: '{$VOLTAGE.MAX.CRIT}'
- macro: '{$VOLTAGE.MAX.WARN}'
- macro: '{$VOLTAGE.MIN.CRIT}'
- macro: '{$VOLTAGE.MIN.WARN}'
dashboards:
- uuid: 7b5209a7cf3f407fb825712f3558bf03
name: 'Morningstar TriStar PWM: Overview'
pages:
- widgets:
- type: graph
width: '72'
height: '4'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'Morningstar TriStar PWM by SNMP'
name: 'Temperature: Battery/Heatsink'
- type: STRING
name: reference
value: AAAAA
valuemaps:
- uuid: 4985c4742d5844e7bc0aee5aeeacc436
name: 'TriStar PWM charge state'
mappings:
- value: '0'
newvalue: Start
- value: '1'
newvalue: NightCheck
- value: '2'
newvalue: Disconnect
- value: '3'
newvalue: Night
- value: '4'
newvalue: Fault
- value: '5'
newvalue: Bulk
- value: '6'
newvalue: Absorption
- value: '7'
newvalue: Float
- value: '8'
newvalue: Equalize
- uuid: 252c3fb63cc34bb1a36ae6e9cbe5880c
name: 'TriStar PWM control mode'
mappings:
- value: '0'
newvalue: Charge
- value: '1'
newvalue: LoadControl
- value: '2'
newvalue: Diversion
- value: '3'
newvalue: Lighting
- uuid: 735e1a0d990a4c449e59eeb402f3b40e
name: 'TriStar PWM load state'
mappings:
- value: '0'
newvalue: Start
- value: '1'
newvalue: Normal
- value: '2'
newvalue: LvdWarning
- value: '3'
newvalue: Lvd
- value: '4'
newvalue: Fault
- value: '5'
newvalue: Disconnect
- value: '6'
newvalue: LvdWarning1
- value: '7'
newvalue: OverrideLvd
- value: '8'
newvalue: Equalize
triggers:
- uuid: f0549419f015448497cd7d15a2bf96fa
expression: '(last(/Morningstar TriStar PWM by SNMP/status.hw.uptime)>0 and last(/Morningstar TriStar PWM by SNMP/status.hw.uptime)<10m) or (last(/Morningstar TriStar PWM by SNMP/status.hw.uptime)=0 and last(/Morningstar TriStar PWM by SNMP/status.net.uptime)<10m)'
name: 'Morningstar TriStar PWM: Status: Device has been restarted'
event_name: 'Morningstar TriStar PWM: Status: Device has been restarted (uptime < 10m)'
priority: INFO
description: 'Uptime is less than 10 minutes.'
manual_close: 'YES'
tags:
- tag: scope
value: notice
graphs:
- uuid: ce3aa40eac5f4ee199ed214752304e19
name: 'Temperature: Battery/Heatsink'
graph_items:
- drawtype: GRADIENT_LINE
color: 199C0D
item:
host: 'Morningstar TriStar PWM by SNMP'
key: 'temp.battery[batteryTemperature.0]'
- sortorder: '1'
drawtype: GRADIENT_LINE
color: F63100
item:
host: 'Morningstar TriStar PWM by SNMP'
key: 'temp.heatsink[heatsinkTemperature.0]'