Files
templates-default/Morningstar_ProStar_MPPT_by_SNMP.yaml

1314 lines
56 KiB
YAML

zabbix_export:
version: '7.0'
template_groups:
- uuid: 36bff6c29af64692839d077febfc7079
name: 'Templates/Network devices'
templates:
- uuid: b84324c2a40a496dbbb379bbf5dde8d5
template: 'Morningstar ProStar MPPT by SNMP'
name: 'Morningstar ProStar MPPT by SNMP'
description: |
MIBs used:
PROSTAR-MPPT
Generated by official Zabbix template tool "Templator"
vendor:
name: Zabbix
version: 7.0-3
groups:
- name: 'Templates/Network devices'
items:
- uuid: a517a7aafbab426eb6ced8d5f57c1fa4
name: 'Array: Sweep Pmax'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.64.0]'
key: 'array.sweep_pmax[arrayMaxPowerSweep.0]'
value_type: FLOAT
units: W
description: |
MIB: PROSTAR-MPPT
Array Max. Power (sweep)
Description:Array Max. Power (last sweep)
Scaling Factor:1.0
Units:W
Range:[0.0, 500]
Modbus address:0x003E
tags:
- tag: component
value: array
- uuid: 7714c76013e341f8b6753cc5a50a960f
name: 'Array: Sweep Vmp'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.63.0]'
key: 'array.sweep_vmp[arrayVmp.0]'
value_type: FLOAT
units: V
description: |
MIB: PROSTAR-MPPT
Array Vmp
Description:Array Max. Power Point Voltage
Scaling Factor:1.0
Units:V
Range:[0.0, 5000.0]
Modbus address:0x003D
tags:
- tag: component
value: array
- uuid: 379ab969ad784968a1090ff98f5801ff
name: 'Array: Sweep Voc'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.65.0]'
key: 'array.sweep_voc[arrayVoc.0]'
value_type: FLOAT
units: V
description: |
MIB: PROSTAR-MPPT
Array Voc
Description:Array Open Circuit Voltage
Scaling Factor:1.0
Units:V
Range:[0.0, 80.0]
Modbus address:0x003F
tags:
- tag: component
value: array
- uuid: 41a1118e1be3417daa79faace733d861
name: 'Array: Voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.31.0]'
key: 'array.voltage[arrayVoltage.0]'
value_type: FLOAT
units: V
description: |
MIB: PROSTAR-MPPT
Array Voltage
Description:Array Voltage
Scaling Factor:1.0
Units:V
Range:[0, 80]
Modbus address:0x0013
tags:
- tag: component
value: array
- uuid: fe5c3b724e894573acdaf522a2213adb
name: 'Battery: Battery Voltage discovery'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.30.0]'
key: 'battery.voltage.discovery[batteryTerminalVoltage.0]'
delay: 15m
history: '0'
value_type: FLOAT
units: V
description: 'MIB: PROSTAR-MPPT'
tags:
- tag: component
value: battery
- tag: component
value: discovery
- tag: component
value: raw
- uuid: ed1d54fce0904b7c9d0895a094f55108
name: 'Battery: Charge Current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.33.0]'
key: 'charge.current[chargeCurrent.0]'
value_type: FLOAT
units: A
description: |
MIB: PROSTAR-MPPT
Charge Current
Description:Charge Current
Scaling Factor:1.0
Units:A
Range:[0, 40]
Modbus address:0x0010
tags:
- tag: component
value: battery
- uuid: 1b1b61995c0d4d89a7f9ad4e14c3541f
name: 'Battery: Charge State'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.45.0]'
key: 'charge.state[chargeState.0]'
value_type: FLOAT
description: |
MIB: PROSTAR-MPPT
Charge State
Description:Control State
Modbus address:0x0021
0: Start
1: NightCheck
2: Disconnect
3: Night
4: Fault
5: BulkMppt
6: Absorption
7: Float
8: Equalize
9: Slave
10: Fixed
valuemap:
name: 'ProStar MPPT charge state'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
tags:
- tag: component
value: battery
triggers:
- uuid: fe4863fdd4d64e1c977328bd3d0f687f
expression: 'last(/Morningstar ProStar MPPT by SNMP/charge.state[chargeState.0])={$CHARGE.STATE.CRIT}'
name: 'Morningstar ProStar MPPT: Battery: Device charge in critical state'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 4d064e4877474d72b85c9cdfb7b09dad
expression: 'last(/Morningstar ProStar MPPT by SNMP/charge.state[chargeState.0])={$CHARGE.STATE.WARN}'
name: 'Morningstar ProStar MPPT: Battery: Device charge in warning state'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar ProStar MPPT: Battery: Device charge in critical state'
expression: 'last(/Morningstar ProStar MPPT by SNMP/charge.state[chargeState.0])={$CHARGE.STATE.CRIT}'
tags:
- tag: scope
value: notice
- uuid: 009eb72ff6674da49d1dd85a6f9459cf
name: 'Counter: Charge Amp-hours'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.49.0]'
key: 'counter.charge_amp_hours[ahChargeResettable.0]'
value_type: FLOAT
units: Ah
description: |
MIB: PROSTAR-MPPT
Ah Charge (Resettable)
Description:Ah Charge (Resettable)
Scaling Factor:0.1
Units:Ah
Range:[0.0, 4294967294]
Modbus addresses:H=0x0026 L=0x0027
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
tags:
- tag: component
value: counter
- uuid: 4a53a2211a1249d59369ad65762ffe47
name: 'Counter: Charge KW-hours'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.51.0]'
key: 'counter.charge_kw_hours[kwhChargeResettable.0]'
value_type: FLOAT
units: '!kWh'
description: |
MIB: PROSTAR-MPPT
kWh Charge (Resettable)
Description:Kilowatt Hours Charge (Resettable)
Scaling Factor:1.0
Units:kWh
Range:[0.0, 65535]
Modbus address:0x002A
tags:
- tag: component
value: counter
- uuid: c72ef851c2d240c9835c1703cec49fd6
name: 'Counter: Load Amp-hours'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.56.0]'
key: 'counter.load_amp_hours[ahLoadResettable.0]'
value_type: FLOAT
units: Ah
description: |
MIB: PROSTAR-MPPT
Description:Ah Load (Resettable)
Scaling Factor:0.1
Units:Ah
Range:[0.0, 4294967294]
Modbus addresses:H=0x0032 L=0x0033
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
tags:
- tag: component
value: counter
- uuid: 29a7d76472fb4025bc78fbeab273e955
name: 'Load: Current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.34.0]'
key: 'load.current[loadCurrent.0]'
value_type: FLOAT
units: A
description: |
MIB: PROSTAR-MPPT
Load Current
Description:Load Current
Scaling Factor:1.0
Units:A
Range:[0, 60]
Modbus address:0x0016
tags:
- tag: component
value: load
- uuid: ae927b5cba5b43f5a2136fd3ee71b63d
name: 'Load: State'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.53.0]'
key: 'load.state[loadState.0]'
value_type: FLOAT
description: |
MIB: PROSTAR-MPPT
Load State
Description:Load State
Modbus address:0x002E
0: Start
1: Normal
2: LvdWarning
3: Lvd
4: Fault
5: Disconnect
6: NormalOff
7: Override
8: NotUsed
valuemap:
name: 'ProStar MPPT load state'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
tags:
- tag: component
value: load
triggers:
- uuid: a88025c5e5a748e3a6dfa01685ba075b
expression: 'last(/Morningstar ProStar MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.CRIT:"lvd"} or last(/Morningstar ProStar MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.CRIT:"fault"}'
name: 'Morningstar ProStar MPPT: Load: Device load in critical state'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 9ab107b39b874fed83d09e7c1964a699
expression: 'last(/Morningstar ProStar MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.WARN:"lvdWarning"} or last(/Morningstar ProStar MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.WARN:"override"}'
name: 'Morningstar ProStar MPPT: Load: Device load in warning state'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar ProStar MPPT: Load: Device load in critical state'
expression: 'last(/Morningstar ProStar MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.CRIT:"lvd"} or last(/Morningstar ProStar MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.CRIT:"fault"}'
tags:
- tag: scope
value: notice
- uuid: 47894752dd1d41f1aa882387acf6dc3a
name: 'Load: Voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.32.0]'
key: 'load.voltage[loadVoltage.0]'
value_type: FLOAT
units: V
description: |
MIB: PROSTAR-MPPT
Load Voltage
Description:Load Voltage
Scaling Factor:1.0
Units:V
Range:[0, 80]
Modbus address:0x0014
tags:
- tag: component
value: load
- uuid: d44cb5d7db31402dae79275a9148817d
name: 'Status: Alarms'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.59.0]'
key: 'status.alarms[alarms.0]'
history: 1h
value_type: TEXT
trends: '0'
description: |
MIB: PROSTAR-MPPT
Description:Alarms
Modbus addresses:H=0x0038 L=0x0039
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
- type: JAVASCRIPT
parameters:
- |
var FIELDS = [
'rtsOpen',
'rtsShorted',
'rtsDisconnected',
'heatsinkTempSensorOpen',
'heatsinkTempSensorShorted',
'heatsinkTempLimit',
'inductorTempSensorOpen',
'inductorTempSensorShorted',
'inductorTempLimit',
'currentLimit',
'currentMeasurementError',
'batterySenseOutOfRange',
'batterySenseDisconnected',
'uncalibrated',
'tb5v',
'fp10SupplyOutOfRange',
'unused',
'mosfetOpen',
'arrayCurrentOffset',
'loadCurrentOffset',
'p33SupplyOutOfRange',
'p12SupplyOutOfRange',
'hightInputVoltageLimit',
'controllerReset',
'loadLvd',
'logTimeout',
'eepromAccessFailure'
];
var flags = parseInt(value.replace(/\x20/g, ''), 16),
result = [];
for (var i = 0, f = 1 << 31 >>> 0, l = FIELDS.length; i < l; i++, f >>>= 1) {
if (flags & f) {
result.push(FIELDS[i]);
}
}
return result.length ? result.join('\n') : 'No alarms';
tags:
- tag: component
value: status
triggers:
- uuid: a2d0ab5150dd4bad8b5ec4f2c6aa13f8
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","arrayCurrentOffset")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "arrayCurrentOffset" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: cc6a15f16fd8470a9dcd9a9e01cba61c
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","batterySenseDisconnected")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "batterySenseDisconnected" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 55d4726d9b9047c79cf690353d950797
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","batterySenseOutOfRange")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "batterySenseOutOfRange" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 7f015198395042219666cde4458d407c
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","controllerReset")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "controllerReset" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 48339339e5a7465fbc67266998c9a8fe
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","currentLimit")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "currentLimit" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: c88074037099498c896bb4793e04fea3
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","currentMeasurementError")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "currentMeasurementError" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: cecd8ee17e5143ffb46495e927750c82
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","eepromAccessFailure")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "eepromAccessFailure" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 4affa15e1c1c42459ea8dd6820d1c008
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","fp10SupplyOutOfRange")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "fp10SupplyOutOfRange" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 41e4225072a3468696cfb534c65b9736
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","heatsinkTempLimit")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "heatsinkTempLimit" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 5d269997a57d44ceb545e751e8e2d919
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","heatsinkTempSensorOpen")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "heatsinkTempSensorOpen" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: a8342a4e2fff40a7b830086dec303fd9
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","heatsinkTempSensorShorted")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "heatsinkTempSensorShorted" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 32e5b7ae81ce4ebea9b05ff7ab411e5a
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","hightInputVoltageLimit")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "hightInputVoltageLimit" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: c10d27c1d9d54b8981a639e7bf0dfc02
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","inductorTempLimit")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "inductorTempLimit" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 9f80959684b34b6498a1634097cd0d22
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","inductorTempSensorOpen")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "inductorTempSensorOpen" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: cc735ddcc98e4c099bb770e2b2a171b5
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","inductorTempSensorShorted")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "inductorTempSensorShorted" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 217935cd6c7547bc95f5af51b3e643d4
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","loadCurrentOffset")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "loadCurrentOffset" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: cb05261f120240bf944b304ffc4979e6
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","loadLvd")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "loadLvd" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 1ed1de932e084ce5ba03747bdd8ca4e5
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","logTimeout")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "logTimeout" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 8824f80f1ef245508d6d0d660e3cabf1
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","mosfetOpen")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "mosfetOpen" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 59569aaebf32403c9fd310f6b26845b0
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","p12SupplyOutOfRange")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "p12SupplyOutOfRange" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 4775d3a7b843455eb404661c070be092
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","p33SupplyOutOfRange")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "p33SupplyOutOfRange" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 2015d2b876564ad79699a23fc6b60f07
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","rtsDisconnected")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "rtsDisconnected" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: cce1eb2bee094a3b9a993ec2d60d182b
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","rtsShorted")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "rtsShorted" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 7a07b757660a4c9a879ac03a94832720
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","tb5v")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "tb5v" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 39205fc6d2cd4888994cccb016b4b2f8
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","uncalibrated")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "uncalibrated" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 8fbb5c650fa040c892a1d10a17fbbf14
name: 'Status: Array Faults'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.46.0]'
key: 'status.array_faults[arrayFaults.0]'
history: 1h
value_type: TEXT
trends: '0'
description: |
MIB: PROSTAR-MPPT
Description:Array Faults
Modbus address:0x0022
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
- type: JAVASCRIPT
parameters:
- |
var FIELDS = [
'overcurrent',
'mosfetSShorted',
'software',
'batteryHvd',
'arrayHvd',
'customSettingsEdit',
'rtsShorted',
'rtsNoLongerValid',
'localTempSensorDamaged',
'batteryLowVoltageDisconnect',
'slaveTimeout',
'dipSwitchChanged',
];
var flags = parseInt(value.replace(/\x20/g, ''), 16),
result = [];
for (var i = 0, f = 1 << 31 >>> 0, l = FIELDS.length; i < l; i++, f >>>= 1) {
if (flags & f) {
result.push(FIELDS[i]);
}
}
return result.length ? result.join('\n') : 'No faults';
tags:
- tag: component
value: status
triggers:
- uuid: 8322f8ca8e2e462a8799dc399f17ba27
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","arrayHvd")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "arrayHvd" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 6a138cd2af754bb3a22173e8da28b254
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","batteryHvd")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "batteryHvd" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 8e42cf21ec10409da840021bfd26f74c
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","batteryLowVoltageDisconnect")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "batteryLowVoltageDisconnect" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: d1112d9828064a879d56626ac6339dbf
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","customSettingsEdit")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "customSettingsEdit" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 75a67f17a33e41eea34585fade6319ef
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","dipSwitchChanged")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "dipSwitchChanged" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 4502112383524f0499ea13e6f83ce789
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","localTempSensorDamaged")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "localTempSensorDamaged" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: f1489dc1f8574895bd233b14ce080748
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","mosfetSShorted")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "mosfetSShorted" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 4ea903d3e8644ddaa5309eaa9715b894
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","overcurrent")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "overcurrent" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: e12a29ec16ea423cb69ca4ce460f201b
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","rtsNoLongerValid")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "rtsNoLongerValid" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 3ec4307bb2c444fc8eca27f9b7a136e2
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","rtsShorted")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "rtsShorted" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 915c00d98e144ee7a9a2d50d0bd474c0
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","slaveTimeout")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "slaveTimeout" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 9aac314eef594a8d86fd4b88308428e5
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","software")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "software" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 712a9b442bec4e89acf4ee5d5bf26fb8
name: 'Status: Uptime (hardware)'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.25.1.1.0]'
key: status.hw.uptime
units: uptime
description: 'The amount of time since this host was last initialized. Note that this is different from sysUpTime in the SNMPv2-MIB [RFC1907] because sysUpTime is the uptime of the network management portion of the system.'
preprocessing:
- type: CHECK_NOT_SUPPORTED
parameters:
- '-1'
error_handler: CUSTOM_VALUE
error_handler_params: '0'
- type: MULTIPLIER
parameters:
- '0.01'
tags:
- tag: component
value: status
- uuid: fb4d2147a8224b599ad908eca1b019e4
name: 'Status: Load Faults'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.54.0]'
key: 'status.load_faults[loadFaults.0]'
history: 1h
value_type: TEXT
trends: '0'
description: |
MIB: PROSTAR-MPPT
Description:Array Faults
Modbus address:0x0022
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
- type: JAVASCRIPT
parameters:
- |
var FIELDS = [
'externalShortCircuit',
'overcurrent',
'mosfetShorted',
'software',
'loadHvd',
'highTempDisconnect',
'dipSwitchChanged',
'customSettingsEdit'
];
var flags = parseInt(value.replace(/\x20/g, ''), 16),
result = [];
for (var i = 0, f = 1 << 31 >>> 0, l = FIELDS.length; i < l; i++, f >>>= 1) {
if (flags & f) {
result.push(FIELDS[i]);
}
}
return result.length ? result.join('\n') : 'No faults';
tags:
- tag: component
value: status
triggers:
- uuid: 93750f768ba94f1bb9302fc17c76faeb
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","customSettingsEdit")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "customSettingsEdit" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 456e2c36369f4519b2c80bcfe1acb4b0
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","dipSwitchChanged")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "dipSwitchChanged" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 359df17c40684187b7ae92c8aa0c9624
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","externalShortCircuit")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "externalShortCircuit" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 6dadf09064304f4381ad9ed0436e562a
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","highTempDisconnect")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "highTempDisconnect" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: bc41145ae8074290913a47cc3fd11e1e
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","loadHvd")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "loadHvd" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 8c8a7021928e4bf78b6309574e298876
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","mosfetShorted")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "mosfetShorted" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: b7d3f05837bd4d788d14f1aaf18b0482
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","overcurrent")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "overcurrent" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 801728740c1948b1a751469e6443daab
expression: 'count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","software")=2'
name: 'Morningstar ProStar MPPT: Status: Device has "software" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 526ee94df484462a9264e57d92954e64
name: 'Status: Uptime (network)'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.3.0]'
key: status.net.uptime
units: uptime
description: 'The time (in hundredths of a second) since the network management portion of the system was last re-initialized.'
preprocessing:
- type: MULTIPLIER
parameters:
- '0.01'
tags:
- tag: component
value: status
triggers:
- uuid: 59cbcaaee8304b38a1144b3abf40bd9d
expression: 'nodata(/Morningstar ProStar MPPT by SNMP/status.net.uptime,5m)=1'
name: 'Morningstar ProStar MPPT: Status: Failed to fetch data'
event_name: 'Morningstar ProStar MPPT: Status: Failed to fetch data (or no data for 5m)'
priority: WARNING
description: 'Zabbix has not received data for items for the last 5 minutes.'
manual_close: 'YES'
tags:
- tag: scope
value: availability
- uuid: 20ce95acdff6486684461f10579a73b4
name: 'Battery: Target Voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.48.0]'
key: 'target.voltage[targetVoltage.0]'
value_type: FLOAT
units: V
description: |
MIB: PROSTAR-MPPT
Target Voltage
Description:Target Regulation Voltage
Scaling Factor:1.0
Units:V
Range:[0.0, 80.0]
Modbus address:0x0024
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
tags:
- tag: component
value: battery
- uuid: 9a87cdcf65184059be334e986bcf801d
name: 'Temperature: Ambient'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.40.0]'
key: 'temp.ambient[ambientTemperature.0]'
value_type: FLOAT
units: C
description: |
MIB: PROSTAR-MPPT
Ambient Temperature
Description:Ambient Temperature
Scaling Factor:1.0
Units:deg C
Range:[-128, 127]
Modbus address:0x001C
tags:
- tag: component
value: temperature
- uuid: 1a8e79f49e86429abc80dd29598299ee
name: 'Temperature: Battery'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.39.0]'
key: 'temp.battery[batteryTemperature.0]'
value_type: FLOAT
units: C
description: |
MIB: PROSTAR-MPPT
Battery Temperature
Description:Battery Temperature
Scaling Factor:1.0
Units:deg C
Range:[-128, 127]
Modbus address:0x001B
tags:
- tag: component
value: temperature
triggers:
- uuid: c74e1d3be1c24bde986bbce068db4bb8
expression: 'min(/Morningstar ProStar MPPT by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.CRIT}'
name: 'Morningstar ProStar MPPT: Temperature: Critically high battery temperature'
event_name: 'Morningstar ProStar MPPT: Temperature: Critically high battery temperature (over {$BATTERY.TEMP.MAX.CRIT}C for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 0c2180ae5deb41adb503e37bf91c34e2
expression: 'max(/Morningstar ProStar MPPT by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.CRIT}'
name: 'Morningstar ProStar MPPT: Temperature: Critically low battery temperature'
event_name: 'Morningstar ProStar MPPT: Temperature: Critically low battery temperature (below {$BATTERY.TEMP.MIN.WARN}C for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 1ab91d781c734f1eb2b9552f6dee9370
expression: 'min(/Morningstar ProStar MPPT by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.WARN}'
name: 'Morningstar ProStar MPPT: Temperature: High battery temperature'
event_name: 'Morningstar ProStar MPPT: Temperature: High battery temperature (over {$BATTERY.TEMP.MAX.WARN}C for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar ProStar MPPT: Temperature: Critically high battery temperature'
expression: 'min(/Morningstar ProStar MPPT by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.CRIT}'
tags:
- tag: scope
value: notice
- uuid: 6ec855dc6a5c42a79f1f40e14655418a
expression: 'max(/Morningstar ProStar MPPT by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.WARN}'
name: 'Morningstar ProStar MPPT: Temperature: Low battery temperature'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar ProStar MPPT: Temperature: Critically low battery temperature'
expression: 'max(/Morningstar ProStar MPPT by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.CRIT}'
tags:
- tag: scope
value: notice
- uuid: 7d0cf28c0d334154971738df11775d1f
name: 'Temperature: Heatsink'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.38.0]'
key: 'temp.heatsink[heatsinkTemperature.0]'
value_type: FLOAT
units: C
description: |
MIB: PROSTAR-MPPT
Heatsink Temperature
Description:Heatsink Temperature
Scaling Factor:1.0
Units:deg C
Range:[-128, 127]
Modbus address:0x001A
tags:
- tag: component
value: temperature
discovery_rules:
- uuid: 1a21c30663c74c23b60e6ad72e228681
name: 'Battery voltage discovery'
type: DEPENDENT
key: battery.voltage.discovery
delay: '0'
description: 'Discovery for battery voltage triggers'
item_prototypes:
- uuid: c02c73a349ec4a6b8557e142c4866148
name: 'Battery: Voltage{#SINGLETON}'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.5.30.0]'
key: 'battery.voltage[batteryTerminalVoltage.0{#SINGLETON}]'
value_type: FLOAT
units: V
description: |
MIB: PROSTAR-MPPT
Battery Terminal Voltage
Description:Battery Terminal Voltage
Scaling Factor:1.0
Units:V
Range:[0.0, 80.0]
Modbus address:0x0012
tags:
- tag: component
value: battery
trigger_prototypes:
- uuid: 402f73ca5b8d412689a7e715223e890d
expression: 'min(/Morningstar ProStar MPPT by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.CRIT}'
name: 'Morningstar ProStar MPPT: Battery: Critically high battery voltage'
event_name: 'Morningstar ProStar MPPT: Battery: Critically high battery voltage (over {#VOLTAGE.MAX.CRIT}V for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: capacity
- uuid: 753a0d25832d434186f586f895124f31
expression: 'max(/Morningstar ProStar MPPT by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.CRIT}'
name: 'Morningstar ProStar MPPT: Battery: Critically low battery voltage'
event_name: 'Morningstar ProStar MPPT: Battery: Critically low battery voltage (below {#VOLTAGE.MIN.CRIT}V for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: capacity
- uuid: 66e1fdfbfa5740dfa8945626f7f8be78
expression: 'min(/Morningstar ProStar MPPT by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.WARN}'
name: 'Morningstar ProStar MPPT: Battery: High battery voltage'
event_name: 'Morningstar ProStar MPPT: Battery: High battery voltage (over {#VOLTAGE.MAX.WARN}V for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar ProStar MPPT: Battery: Critically high battery voltage'
expression: 'min(/Morningstar ProStar MPPT by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.CRIT}'
tags:
- tag: scope
value: capacity
- uuid: c9f3d03ce06641eb9b184f511a3a0341
expression: 'max(/Morningstar ProStar MPPT by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.WARN}'
name: 'Morningstar ProStar MPPT: Battery: Low battery voltage'
event_name: 'Morningstar ProStar MPPT: Battery: Low battery voltage (below {#VOLTAGE.MIN.WARN}V for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar ProStar MPPT: Battery: Critically low battery voltage'
expression: 'max(/Morningstar ProStar MPPT by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.CRIT}'
tags:
- tag: scope
value: capacity
graph_prototypes:
- uuid: 480e4c11060a4e34851b48bf7b9c5bb1
name: 'Voltage: Battery/Load{#SINGLETON}'
graph_items:
- drawtype: GRADIENT_LINE
color: 199C0D
item:
host: 'Morningstar ProStar MPPT by SNMP'
key: 'battery.voltage[batteryTerminalVoltage.0{#SINGLETON}]'
- sortorder: '1'
drawtype: GRADIENT_LINE
color: F63100
item:
host: 'Morningstar ProStar MPPT by SNMP'
key: 'load.voltage[loadVoltage.0]'
master_item:
key: 'battery.voltage.discovery[batteryTerminalVoltage.0]'
preprocessing:
- type: JAVASCRIPT
parameters:
- |
var v_range = [
[[0, 18], [12, 15, 11.5, 15.5]],
[[18, 36], [24, 30, 23, 31]],
[[36, 99], [48, 60, 46, 62]],
],
result = [];
for (var idx in v_range) {
if (v_range[idx][0][0] < value && value <= v_range[idx][0][1]) {
result = [{
'{#VOLTAGE.MIN.WARN}': parseInt({$VOLTAGE.MIN.WARN}) || v_range[idx][1][0],
'{#VOLTAGE.MAX.WARN}': parseInt({$VOLTAGE.MAX.WARN}) || v_range[idx][1][1],
'{#VOLTAGE.MIN.CRIT}': parseInt({$VOLTAGE.MIN.CRIT}) || v_range[idx][1][2],
'{#VOLTAGE.MAX.CRIT}': parseInt({$VOLTAGE.MAX.CRIT}) || v_range[idx][1][3],
'{#SINGLETON}': ''
}];
break;
}
}
return JSON.stringify(result);
tags:
- tag: class
value: power
- tag: target
value: morningstar
macros:
- macro: '{$BATTERY.TEMP.MAX.CRIT}'
value: '60'
description: 'Battery high temperature critical value'
- macro: '{$BATTERY.TEMP.MAX.WARN}'
value: '45'
description: 'Battery high temperature warning value'
- macro: '{$BATTERY.TEMP.MIN.CRIT}'
value: '-20'
description: 'Battery low temperature critical value'
- macro: '{$BATTERY.TEMP.MIN.WARN}'
value: '0'
description: 'Battery low temperature warning value'
- macro: '{$CHARGE.STATE.CRIT}'
value: '4'
description: fault
- macro: '{$CHARGE.STATE.WARN}'
value: '2'
description: disconnect
- macro: '{$LOAD.STATE.CRIT:"fault"}'
value: '4'
description: fault
- macro: '{$LOAD.STATE.CRIT:"lvd"}'
value: '3'
description: lvd
- macro: '{$LOAD.STATE.WARN:"disconnect"}'
value: '5'
description: disconnect
- macro: '{$LOAD.STATE.WARN:"lvdWarning"}'
value: '2'
description: lvdWarning
- macro: '{$LOAD.STATE.WARN:"override"}'
value: '7'
description: override
- macro: '{$VOLTAGE.MAX.CRIT}'
- macro: '{$VOLTAGE.MAX.WARN}'
- macro: '{$VOLTAGE.MIN.CRIT}'
- macro: '{$VOLTAGE.MIN.WARN}'
dashboards:
- uuid: 3765513f1a4945c0801639e4c689f99f
name: 'Morningstar ProStar MPPT: Overview'
pages:
- widgets:
- type: graph
width: '72'
height: '4'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'Morningstar ProStar MPPT by SNMP'
name: 'Array: Voltage'
- type: STRING
name: reference
value: AAAAA
- type: graph
'y': '4'
width: '72'
height: '4'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'Morningstar ProStar MPPT by SNMP'
name: 'Current: Charge/Load'
- type: STRING
name: reference
value: AAAAB
- type: graph
'y': '8'
width: '72'
height: '4'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'Morningstar ProStar MPPT by SNMP'
name: 'Temperature: Ambient/Battery/Heatsink'
- type: STRING
name: reference
value: AAAAC
valuemaps:
- uuid: 1703c3aeb1b24641821e1c6d2cb4c8b7
name: 'ProStar MPPT charge state'
mappings:
- value: '0'
newvalue: Start
- value: '1'
newvalue: NightCheck
- value: '2'
newvalue: Disconnect
- value: '3'
newvalue: Night
- value: '4'
newvalue: Fault
- value: '5'
newvalue: BulkMppt
- value: '6'
newvalue: Absorption
- value: '7'
newvalue: Float
- value: '8'
newvalue: Equalize
- value: '9'
newvalue: Slave
- value: '10'
newvalue: Fixed
- uuid: b5403a0805a54b9294f69a1e11a438b1
name: 'ProStar MPPT load state'
mappings:
- value: '0'
newvalue: Start
- value: '1'
newvalue: Normal
- value: '2'
newvalue: LvdWarning
- value: '3'
newvalue: Lvd
- value: '4'
newvalue: Fault
- value: '5'
newvalue: Disconnect
- value: '6'
newvalue: NormalOff
- value: '7'
newvalue: Override
- value: '8'
newvalue: NotUsed
triggers:
- uuid: ca65a39c019046c29a522a6ca93ceb75
expression: '(last(/Morningstar ProStar MPPT by SNMP/status.hw.uptime)>0 and last(/Morningstar ProStar MPPT by SNMP/status.hw.uptime)<10m) or (last(/Morningstar ProStar MPPT by SNMP/status.hw.uptime)=0 and last(/Morningstar ProStar MPPT by SNMP/status.net.uptime)<10m)'
name: 'Morningstar ProStar MPPT: Status: Device has been restarted'
event_name: 'Morningstar ProStar MPPT: Status: Device has been restarted (uptime < 10m)'
priority: INFO
description: 'Uptime is less than 10 minutes.'
manual_close: 'YES'
tags:
- tag: scope
value: notice
graphs:
- uuid: 0662dc480c2b487e9f9afc389166a15b
name: 'Array: Voltage'
graph_items:
- drawtype: GRADIENT_LINE
color: 199C0D
item:
host: 'Morningstar ProStar MPPT by SNMP'
key: 'array.sweep_vmp[arrayVmp.0]'
- sortorder: '1'
drawtype: GRADIENT_LINE
color: F63100
item:
host: 'Morningstar ProStar MPPT by SNMP'
key: 'array.sweep_voc[arrayVoc.0]'
- sortorder: '2'
drawtype: GRADIENT_LINE
color: 00611C
item:
host: 'Morningstar ProStar MPPT by SNMP'
key: 'array.voltage[arrayVoltage.0]'
- uuid: 94bbfd8a60a8412998ff617011db9372
name: 'Current: Charge/Load'
graph_items:
- drawtype: GRADIENT_LINE
color: 199C0D
item:
host: 'Morningstar ProStar MPPT by SNMP'
key: 'charge.current[chargeCurrent.0]'
- sortorder: '1'
drawtype: GRADIENT_LINE
color: F63100
item:
host: 'Morningstar ProStar MPPT by SNMP'
key: 'load.current[loadCurrent.0]'
- uuid: 02652b1251244702bf28f691e72ba27e
name: 'Temperature: Ambient/Battery/Heatsink'
graph_items:
- drawtype: GRADIENT_LINE
color: 199C0D
item:
host: 'Morningstar ProStar MPPT by SNMP'
key: 'temp.ambient[ambientTemperature.0]'
- sortorder: '1'
drawtype: GRADIENT_LINE
color: F63100
item:
host: 'Morningstar ProStar MPPT by SNMP'
key: 'temp.battery[batteryTemperature.0]'
- sortorder: '2'
drawtype: GRADIENT_LINE
color: 00611C
item:
host: 'Morningstar ProStar MPPT by SNMP'
key: 'temp.heatsink[heatsinkTemperature.0]'