Files
templates-default/APC_UPS_Galaxy_3500_by_SNMP.yaml

1556 lines
66 KiB
YAML

zabbix_export:
version: '7.0'
template_groups:
- uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
name: Templates/Power
templates:
- uuid: 5d3971cd973b46e7915d7ae0750bac57
template: 'APC UPS Galaxy 3500 by SNMP'
name: 'APC UPS Galaxy 3500 by SNMP'
description: |
Template Power APC UPS Galaxy 3500
MIBs used:
HOST-RESOURCES-MIB
PowerNet-MIB
SNMPv2-MIB
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
Generated by official Zabbix template tool "Templator"
vendor:
name: Zabbix
version: 7.0-4
groups:
- name: Templates/Power
items:
- uuid: 70ebcb1dee674a60a1410895d60e8245
name: 'Battery capacity'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.1.0]'
key: 'battery.capacity[upsHighPrecBatteryCapacity]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The remaining battery capacity expressed as
percentage of full capacity.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: 1800690ba0504df9940a4e667c846132
expression: 'last(/APC UPS Galaxy 3500 by SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}'
name: 'APC UPS Galaxy: Battery has low capacity'
event_name: 'APC UPS Galaxy: Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%)'
opdata: 'Current capacity: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: capacity
- uuid: 2b417eadc988460a89db04efdaca4ffc
name: 'External battery packs count'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.5.0]'
key: 'battery.external_packs_count[upsAdvBatteryNumOfBattPacks]'
delay: 1h
description: |
MIB: PowerNet-MIB
The number of external battery packs connected to the UPS. If
the UPS does not use smart cells then the agent reports
ERROR_NO_SUCH_NAME.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: 98af792142464656b925a452e5ebf1cc
name: 'Battery last replace date'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.1.3.0]'
key: 'battery.last_replace_date[upsBasicBatteryLastReplaceDate]'
delay: 1h
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The date when the UPS system's batteries were last replaced
in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value
is originally set at the factory. When the UPS batteries
are replaced, this value should be reset by the administrator.
For Symmetra PX 250/500 this OID is read-only and is configurable in the local display only.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: b7614652ff6f4e0890f366b8e0831b80
name: 'Battery replace indicator'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.4.0]'
key: 'battery.replace_indicator[upsAdvBatteryReplaceIndicator]'
description: |
MIB: PowerNet-MIB
Indicates whether the UPS batteries need replacement.
valuemap:
name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: b4d10f8908f4473facde6d2db1520e0f
expression: 'last(/APC UPS Galaxy 3500 by SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2'
name: 'APC UPS Galaxy: Battery needs replacement'
priority: HIGH
description: 'A battery installed has an internal error condition.'
tags:
- tag: scope
value: notice
- uuid: 89cca909c60745fe824d02aa0d4bc3d7
name: 'Battery runtime remaining'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.3.0]'
key: 'battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]'
value_type: FLOAT
units: s
description: |
MIB: PowerNet-MIB
The UPS battery run time remaining before battery
exhaustion.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.01'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 22a95e447ad74d43a191f368346fde59
name: 'Battery status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.1.1.0]'
key: 'battery.status[upsBasicBatteryStatus]'
description: |
MIB: PowerNet-MIB
The status of the UPS batteries. A batteryLow(3) value
indicates the UPS will be unable to sustain the current
load, and its services will be lost if power is not restored.
The amount of run time in reserve at the time of low battery
can be configured by the upsAdvConfigLowBatteryRunTime.
A batteryInFaultCondition(4)value indicates that a battery
installed has an internal error condition.
valuemap:
name: 'PowerNet-MIB::upsBasicBatteryStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
triggers:
- uuid: d84ec0d0b8d84e3294cbe7ffaed0c83e
expression: 'last(/APC UPS Galaxy 3500 by SNMP/battery.status[upsBasicBatteryStatus])=4'
name: 'APC UPS Galaxy: Battery has an internal error condition'
priority: AVERAGE
description: 'A battery installed has an internal error condition.'
tags:
- tag: scope
value: notice
- uuid: 8f569ce6c916456581e1cb2cdd8d4dba
expression: 'last(/APC UPS Galaxy 3500 by SNMP/battery.status[upsBasicBatteryStatus])=3'
name: 'APC UPS Galaxy: Battery is Low'
priority: AVERAGE
description: 'The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.'
tags:
- tag: scope
value: capacity
- uuid: 7a0a2b5e702f473fa1144eaf499367b2
name: 'Battery temperature'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.2.0]'
key: 'battery.temperature[upsHighPrecBatteryTemperature]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The current internal UPS temperature in Celsius.
Temperatures below zero read as 0.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: temperature
triggers:
- uuid: 0e1f47f0604d4b1b8769e497d7f328b9
expression: 'min(/APC UPS Galaxy 3500 by SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
name: 'APC UPS Galaxy: Battery has high temperature'
event_name: 'APC UPS Galaxy: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})'
opdata: 'Current temperature: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 756f727fe8374aeba9d1afd7bbe77f02
name: 'Battery voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.4.0]'
key: 'battery.voltage[upsHighPrecBatteryActualVoltage]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The actual battery bus voltage in Volts.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 9069a1c0d9304e7fa5f2df133dbb46cd
name: 'Input fail cause'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.3.2.5.0]'
key: 'input.fail[upsAdvInputLineFailCause]'
description: |
MIB: PowerNet-MIB
The reason for the occurrence of the last transfer to UPS
battery power. The variable is set to:
- noTransfer(1) -- if there is no transfer yet.
- highLineVoltage(2) -- if the transfer to battery is caused
by an over voltage greater than the high transfer voltage.
- brownout(3) -- if the duration of the outage is greater than
five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- blackout(4) -- if the duration of the outage is greater than five
seconds and the line voltage is between 40% of the rated
output voltage and ground.
- smallMomentarySag(5) -- if the duration of the outage is less
than five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- deepMomentarySag(6) -- if the duration of the outage is less
than five seconds and the line voltage is between 40% of the
rated output voltage and ground. The variable is set to
- smallMomentarySpike(7) -- if the line failure is caused by a
rate of change of input voltage less than ten volts per cycle.
- largeMomentarySpike(8) -- if the line failure is caused by
a rate of change of input voltage greater than ten volts per cycle.
- selfTest(9) -- if the UPS was commanded to do a self test.
- rateOfVoltageChange(10) -- if the failure is due to the rate of change of
the line voltage.
valuemap:
name: 'PowerNet-MIB::upsAdvInputLineFailCause'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 3a64740655ca455ab0280592b5f0055f
name: 'Input frequency'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.3.3.4.0]'
key: 'input.frequency[upsHighPrecInputFrequency]'
value_type: FLOAT
units: Hz
description: |
MIB: PowerNet-MIB
The current input frequency to the UPS system in Hz.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: 786d9928356e41ad9b6b2de3b4f3a96f
expression: 'min(/APC UPS Galaxy 3500 by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Galaxy 3500 by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Galaxy 3500 by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})'
name: 'APC UPS Galaxy: Unacceptable input frequency'
event_name: 'APC UPS Galaxy: Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD})'
opdata: 'Current frequency: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 89bb663e356c4420bcbe2a9470ae3195
name: 'Input voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.3.3.1.0]'
key: 'input.voltage[upsHighPrecInputLineVoltage]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The current utility line voltage in VAC.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: de88ed3b64644d3f9ad1cc3f965757bc
expression: 'min(/APC UPS Galaxy 3500 by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Galaxy 3500 by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Galaxy 3500 by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})'
name: 'APC UPS Galaxy: Unacceptable input voltage'
event_name: 'APC UPS Galaxy: Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current voltage: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: a6737781029b422ca7a8bbfa0ed80b56
name: 'Output current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.3.4.0]'
key: 'output.current[upsHighPrecOutputCurrent]'
value_type: FLOAT
units: A
description: |
MIB: PowerNet-MIB
The current in amperes drawn by the load on the UPS.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 5774ead79e8b4d63a4a31bc091d1c52a
name: 'Output load'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.3.3.0]'
key: 'output.load[upsHighPrecOutputLoad]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The current UPS load expressed as percentage
of rated capacity.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: fb7ca4b92e714fda95152b698cf1aa92
expression: 'min(/APC UPS Galaxy 3500 by SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}'
name: 'APC UPS Galaxy: Output load is high'
event_name: 'APC UPS Galaxy: Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD})'
opdata: 'Current load: {ITEM.LASTVALUE1}'
priority: HIGH
description: 'A battery installed has an internal error condition.'
tags:
- tag: scope
value: notice
- uuid: 8a6c9b134ebc4fd19876cf5d50dfc17b
name: 'Output status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.1.1.0]'
key: 'output.status[upsBasicOutputStatus]'
description: |
MIB: PowerNet-MIB
The current state of the UPS. If the UPS is unable to
determine the state of the UPS this variable is set
to unknown(1).
During self-test most UPSes report onBattery(3) but
some that support it will report onBatteryTest(15).
To determine self-test status across all UPSes, refer
to the upsBasicStateOutputState OID.
valuemap:
name: 'PowerNet-MIB::upsBasicOutputStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
triggers:
- uuid: efed1ccf301740c1a29e71cd89e5659f
expression: 'last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=16'
name: 'APC UPS Galaxy: UPS is Emergency Static Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 44394841911641c4972165b59b8f6a5b
expression: 'last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=10'
name: 'APC UPS Galaxy: UPS is Hardware Failure Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: d60b075bfaaa4aeea2398d058fb79c92
expression: 'last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=7'
name: 'APC UPS Galaxy: UPS is Off'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 4d54e6e979f94801a3c1e9d6080886bb
expression: 'last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=3'
name: 'APC UPS Galaxy: UPS is on battery'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: eb430f5409a24f89b0a9e56fb28087c4
expression: 'last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=4'
name: 'APC UPS Galaxy: UPS is on Smart Boost'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 77dbd58283b542cfbca9a9255344e97e
expression: 'last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=12'
name: 'APC UPS Galaxy: UPS is On Smart Trim'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 3856ff4ac1d64f8e80c4e0cbb1e04c1a
expression: 'last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=8'
name: 'APC UPS Galaxy: UPS is Rebooting'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 10d8d392f93a492b9be767c7ccdf06ed
expression: 'last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=11'
name: 'APC UPS Galaxy: UPS is Sleeping Until Power Return'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 2ab92cb281754de6ad5245509c20056d
expression: 'last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=6'
name: 'APC UPS Galaxy: UPS is Software Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 8fabe8958cfd4dbbabd70648dff1be06
expression: 'last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=9'
name: 'APC UPS Galaxy: UPS is Switched Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 9846ac1bbf024e63a05a83e2c02de7ba
expression: 'last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=5'
name: 'APC UPS Galaxy: UPS is Timed Sleeping'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 4ec893da7b8540548d60a91ee7e2df83
name: 'Output voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.3.1.0]'
key: 'output.voltage[upsHighPrecOutputVoltage]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The output voltage of the UPS system in VAC.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 7d20aa252c5143c98de837dbd2f0cd53
name: 'SNMP traps (fallback)'
type: SNMP_TRAP
key: snmptrap.fallback
delay: '0'
value_type: LOG
trends: '0'
description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items'
logtimefmt: 'hh:mm:sszyyyy/MM/dd'
tags:
- tag: component
value: network
- uuid: aa5e85ef78504fc080b97342baf6cb35
name: 'System contact details'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.4.0]'
key: 'system.contact[sysContact.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
The textual identification of the contact person for this managed
node, together with information on how to contact this person. If no contact
information is known, the value is the zero-length string.
inventory_link: CONTACT
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 12h
tags:
- tag: component
value: system
- uuid: f1df592a2b114677a1beabec33ce01f9
name: 'System description'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.1.0]'
key: 'system.descr[sysDescr.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
A textual description of the entity. This value should
include the full name and version identification of the system's hardware type, software operating-system, and
networking software.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 12h
tags:
- tag: component
value: system
- uuid: b73fb48b4da84a53b7a4b7e81d6037aa
name: 'Uptime (hardware)'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.25.1.1.0]'
key: 'system.hw.uptime[hrSystemUptime.0]'
delay: 30s
trends: '0'
units: uptime
description: |
MIB: HOST-RESOURCES-MIB
The amount of time since this host was last initialized. Note that this is different from sysUpTime in the SNMPv2-MIB [RFC1907] because sysUpTime is the uptime of the network management portion of the system.
preprocessing:
- type: CHECK_NOT_SUPPORTED
parameters:
- '-1'
error_handler: CUSTOM_VALUE
error_handler_params: '0'
- type: MULTIPLIER
parameters:
- '0.01'
tags:
- tag: component
value: system
- uuid: b109475e72e74e76846aa478e9937101
name: 'System location'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.6.0]'
key: 'system.location[sysLocation.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
The physical location of this node (e.g., `telephone closet, 3rd floor'). If the location is unknown, the value is the zero-length string.
inventory_link: LOCATION
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: system
- uuid: 93b6e128e95a4a96bde38ef15d74d510
name: Model
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.1.1.1.0]'
key: 'system.model[upsBasicIdentModel]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The UPS model name (e.g. 'APC Smart-UPS 600').
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: d6f2c9770c28487d9fa6af2b63917958
name: 'System name'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.5.0]'
key: 'system.name[sysName.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
An administratively-assigned name for this managed node.By convention, this is the node's fully-qualified domain name. If the name is unknown, the value is the zero-length string.
inventory_link: NAME
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: system
triggers:
- uuid: 811ff6e90d904c8c98feadc89a18e733
expression: 'last(/APC UPS Galaxy 3500 by SNMP/system.name[sysName.0],#1)<>last(/APC UPS Galaxy 3500 by SNMP/system.name[sysName.0],#2) and length(last(/APC UPS Galaxy 3500 by SNMP/system.name[sysName.0]))>0'
name: 'APC UPS Galaxy: System name has changed'
event_name: 'APC UPS Galaxy: System name has changed (new name: {ITEM.VALUE})'
priority: INFO
description: 'The name of the system has changed. Acknowledge to close the problem manually.'
manual_close: 'YES'
tags:
- tag: scope
value: notice
- tag: scope
value: security
- uuid: fc207a1df4324fcf99ba1da262527fe3
name: 'Uptime (network)'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.3.0]'
key: 'system.net.uptime[sysUpTime.0]'
delay: 30s
trends: '0'
units: uptime
description: |
MIB: SNMPv2-MIB
The time (in hundredths of a second) since the network management portion of the system was last re-initialized.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.01'
tags:
- tag: component
value: system
- uuid: 5497f3649b9348dca290c55e94f48597
name: 'System object ID'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.2.0]'
key: 'system.objectid[sysObjectID.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
The vendor's authoritative identification of the network management subsystem contained in the entity. This value is allocated within the SMI enterprises subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1 to its `Fred Router'.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: system
- uuid: ef25b1e818534420920ff6260fa2932e
name: 'Serial number'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.1.2.3.0]'
key: 'system.sn[upsAdvIdentSerialNumber]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
An 8-character string identifying the serial number of
the UPS internal microprocessor. This number is set at
the factory. NOTE: This number does NOT correspond to
the serial number on the rear of the UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: efad5c028c0d4c11b57a19dc04830ea7
name: 'SNMP agent availability'
type: INTERNAL
key: 'zabbix[host,snmp,available]'
description: |
Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.
Possible values:
0 - not available
1 - available
2 - unknown
valuemap:
name: zabbix.host.available
tags:
- tag: component
value: health
- tag: component
value: network
triggers:
- uuid: e12b11324a634eeba56db1aec1834d5f
expression: 'max(/APC UPS Galaxy 3500 by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
name: 'APC UPS Galaxy: No SNMP data collection'
opdata: 'Current state: {ITEM.LASTVALUE1}'
priority: WARNING
description: 'SNMP is not available for polling. Please check device connectivity and SNMP settings.'
tags:
- tag: scope
value: availability
discovery_rules:
- uuid: 54a867c14c814e4ab4803c5a59082e44
name: 'External bad battery packs discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#EXTERNAL_PACKS},1.3.6.1.4.1.318.1.1.1.2.2.6]'
key: battery.packs.bad.discovery
delay: 1h
filter:
evaltype: AND
conditions:
- macro: '{#EXTERNAL_PACKS}'
value: '-1'
operator: NOT_MATCHES_REGEX
formulaid: A
description: 'Discovery of the number of external defective battery packs.'
item_prototypes:
- uuid: 2a60e35fabb44c78bd827e22293166d9
name: '{#SNMPINDEX}: External battery packs bad'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.6.0]'
key: 'battery.external_packs_bad[upsAdvBatteryNumOfBadBattPacks.{#SNMPINDEX}]'
delay: 15m
description: |
MIB: PowerNet-MIB
The number of external battery packs connected to the UPS that
are defective. If the UPS does not use smart cells then the
agent reports ERROR_NO_SUCH_NAME.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: 0c8fc55bbe984d919c3b87a096d900d5
name: 'External battery packs discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#CARTRIDGE_STATUS},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7,{#BATTERY_PACK},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1,{#CARTRIDGE_INDEX},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2]'
key: battery.packs.discovery
delay: 1h
filter:
evaltype: AND
conditions:
- macro: '{#CARTRIDGE_STATUS}'
value: ^$
operator: NOT_MATCHES_REGEX
formulaid: A
item_prototypes:
- uuid: a7023eed55484d1d9f0754ccb1ec9f87
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery estimated replace date'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8.{#SNMPINDEX}]'
key: 'battery.estimated_replace_date[upsHighPrecBatteryPackCartridgeReplaceDate.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
delay: 1h
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The battery cartridge estimated battery replace date.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- tag: component
value: power
- uuid: 41cd82bb312344b7bdb9c7c5aac2eb21
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7.{#SNMPINDEX}]'
key: 'battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The battery cartridge health.
bit 0 Battery lifetime okay
bit 1 Battery lifetime near end, order replacement cartridge
bit 2 Battery lifetime exceeded, replace battery
bit 3 Battery lifetime near end acknowledged, order replacement cartridge
bit 4 Battery lifetime exceeded acknowledged, replace battery
bit 5 Battery measured lifetime near end, order replacement cartridge
bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: 94e469f639cb4ae4ab3ac23918cfa651
expression: 'find(/APC UPS Galaxy 3500 by SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1'
name: 'APC UPS Galaxy: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay'
opdata: 'Current bit set: {ITEM.LASTVALUE1}'
priority: WARNING
description: |
The battery cartridge health.
bit 0 Battery lifetime okay
bit 1 Battery lifetime near end, order replacement cartridge
bit 2 Battery lifetime exceeded, replace battery
bit 3 Battery lifetime near end acknowledged, order replacement cartridge
bit 4 Battery lifetime exceeded acknowledged, replace battery
bit 5 Battery measured lifetime near end, order replacement cartridge
bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge
tags:
- tag: scope
value: notice
- uuid: 241efd4ef6204c58adc04e4e04660845
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10.{#SNMPINDEX}]'
key: 'battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The status of the UPS batteries. A batteryLow(3) value
indicates the UPS will be unable to sustain the current
load, and its services will be lost if power is not restored.
The amount of run time in reserve at the time of low battery
can be configured by the upsAdvConfigLowBatteryRunTime.
A batteryInFaultCondition(4)value indicates that a battery
installed has an internal error condition.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: 60bf7de80cd741caa1c622e797da1d69
expression: 'find(/APC UPS Galaxy 3500 by SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0'
name: 'APC UPS Galaxy: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay'
opdata: 'Current bit set: {ITEM.LASTVALUE1}'
priority: WARNING
description: |
The battery cartridge status:
bit 0 Disconnected
bit 1 Overvoltage
bit 2 NeedsReplacement
bit 3 OvertemperatureCritical
bit 4 Charger
bit 5 TemperatureSensor
bit 6 BusSoftStart
bit 7 OvertemperatureWarning
bit 8 GeneralError
bit 9 Communication
bit 10 DisconnectedFrame
bit 11 FirmwareMismatch
tags:
- tag: scope
value: notice
- uuid: a55dd3033a2645aab5592f356043c342
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperature'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5.{#SNMPINDEX}]'
key: 'battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The current internal UPS temperature in Celsius.
Temperatures below zero read as 0.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: temperature
trigger_prototypes:
- uuid: bdd4bb9fac784bc0b0dc72db3ac9e040
expression: 'min(/APC UPS Galaxy 3500 by SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
name: 'APC UPS Galaxy: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature'
event_name: 'APC UPS Galaxy: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})'
opdata: 'Current temperature: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 8ea7d066a5ae4141b4cd0af13d96c40c
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4.{#SNMPINDEX}]'
key: 'system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
An 8-character string identifying the serial number of
the UPS internal microprocessor. This number is set at
the factory. NOTE: This number does NOT correspond to
the serial number on the rear of the UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: ffb60da941114174932b219e14892be9
name: 'External sensor port 1 discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#EXTERNAL_SENSOR1_NAME},1.3.6.1.4.1.318.1.1.25.1.2.1.3]'
key: external.sensor1.discovery
delay: 1h
description: uioSensorStatusTable
item_prototypes:
- uuid: f2bcca2221e94e828755a90f98c98495
name: '{#EXTERNAL_SENSOR1_NAME}: Humidity sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.1.7.{#SNMPINDEX}]'
key: 'external.sensor.humidity[uioSensorStatusHumidity.1.{#SNMPINDEX}]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The sensor's current humidity reading - a relative humidity
percentage. -1 indicates an invalid reading due to either a
sensor that doesn't read humidity or lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: humidity
- tag: component
value: power
- uuid: 1a41c120082948bdb6865413bdc09917
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.1.9.{#SNMPINDEX}]'
key: 'external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}]'
description: |
MIB: PowerNet-MIB
The alarm status of the sensor. Possible values:
uioNormal (1),
uioWarning (2),
uioCritical (3),
sensorStatusNotApplicable (4)
valuemap:
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: 93d474d1badc45d5a48fe0e610744ff6
expression: 'last(/APC UPS Galaxy 3500 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3'
name: 'APC UPS Galaxy: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical'
priority: HIGH
description: 'The external sensor has returned a value greater than the critical threshold.'
tags:
- tag: scope
value: notice
- uuid: 48fa5f120bd5495185a9d6f86fc823fd
expression: 'last(/APC UPS Galaxy 3500 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4'
name: 'APC UPS Galaxy: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable'
priority: INFO
description: 'The external sensor does not work or is not connected.'
tags:
- tag: scope
value: notice
- uuid: b0652e627c10477c9e61786d85560d93
expression: 'last(/APC UPS Galaxy 3500 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2'
name: 'APC UPS Galaxy: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning'
priority: AVERAGE
description: 'The external sensor has returned a value greater than the warning threshold.'
tags:
- tag: scope
value: notice
- uuid: a191d2ff066e4f4ba04aede67cd6876d
name: '{#EXTERNAL_SENSOR1_NAME}: Temperature sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.1.6.{#SNMPINDEX}]'
key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.1.{#SNMPINDEX}]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The sensor's current temperature reading in Celsius.
-1 indicates an invalid reading due to lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- tag: component
value: temperature
overrides:
- name: Temp
step: '1'
filter:
conditions:
- macro: '{#EXTERNAL_SENSOR1_NAME}'
value: Temp
formulaid: A
operations:
- operationobject: ITEM_PROTOTYPE
operator: LIKE
value: Humidity
discover: NO_DISCOVER
- uuid: 463ed9f01f3a4cf6ba91f2707baded15
name: 'External sensor port 2 discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#EXTERNAL_SENSOR2_NAME},1.3.6.1.4.1.318.1.1.25.1.2.2.3]'
key: external.sensor2.discovery
delay: 1h
description: uioSensorStatusTable
item_prototypes:
- uuid: e2200965a13541b1a100e4880d8363ff
name: '{#EXTERNAL_SENSOR2_NAME}: Humidity sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.2.7.{#SNMPINDEX}]'
key: 'external.sensor.humidity[uioSensorStatusHumidity.2.{#SNMPINDEX}]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The sensor's current humidity reading - a relative humidity
percentage. -1 indicates an invalid reading due to either a
sensor that doesn't read humidity or lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: humidity
- tag: component
value: power
- uuid: 492835d959d644d7b95fc480cba5d3dc
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.2.9.{#SNMPINDEX}]'
key: 'external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}]'
description: |
MIB: PowerNet-MIB
The alarm status of the sensor. Possible values:
uioNormal (1),
uioWarning (2),
uioCritical (3),
sensorStatusNotApplicable (4)
valuemap:
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: 55acc85739e04ebea3414059907ef2e4
expression: 'last(/APC UPS Galaxy 3500 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3'
name: 'APC UPS Galaxy: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical'
priority: HIGH
description: 'The external sensor has returned a value greater than the critical threshold.'
tags:
- tag: scope
value: notice
- uuid: e8753aa5ca16449c8dc21af6c8c2a727
expression: 'last(/APC UPS Galaxy 3500 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4'
name: 'APC UPS Galaxy: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable'
priority: INFO
description: 'The external sensor does not work or is not connected.'
tags:
- tag: scope
value: notice
- uuid: d16c60a30b5d46459237eef4df38df9f
expression: 'last(/APC UPS Galaxy 3500 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2'
name: 'APC UPS Galaxy: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning'
priority: AVERAGE
description: 'The external sensor has returned a value greater than the warning threshold.'
tags:
- tag: scope
value: notice
- uuid: 2cf2d697c95845ba8ec61af2ec698f4c
name: '{#EXTERNAL_SENSOR2_NAME}: Temperature sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.2.6.{#SNMPINDEX}]'
key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.2.{#SNMPINDEX}]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The sensor's current temperature reading in Celsius.
-1 indicates an invalid reading due to lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- tag: component
value: temperature
overrides:
- name: Temp
step: '1'
filter:
conditions:
- macro: '{#EXTERNAL_SENSOR2_NAME}'
value: Temp
formulaid: A
operations:
- operationobject: ITEM_PROTOTYPE
operator: LIKE
value: Humidity
discover: NO_DISCOVER
- uuid: f16f2ab100614ae6bccf66e5a840c7db
name: 'Input phases discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.2.3.1.2.1.1]'
key: input.phases.discovery
delay: 1h
description: 'The input phase identifier. OID upsPhaseInputPhaseIndex.1.1'
item_prototypes:
- uuid: 7c0490500bed4258a8663777cd62e378
name: '{#PHASEINDEX}: Phase input current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.2.3.1.6.1.1.{#PHASEINDEX}]'
key: 'phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: A
description: |
MIB: PowerNet-MIB
The input current in 0.1 amperes, or -0.1 if it's
unsupported by this UPS.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 7356945fc0e94026a2ca04d297fdf953
name: '{#PHASEINDEX}: Phase input voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.2.3.1.3.1.1.{#PHASEINDEX}]'
key: 'phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The input voltage in VAC, or -1 if it's unsupported
by this UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
trigger_prototypes:
- uuid: 1824f0be30284d13bad9f895f7adaa0e
expression: 'min(/APC UPS Galaxy 3500 by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Galaxy 3500 by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
name: 'APC UPS Galaxy: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage'
event_name: 'APC UPS Galaxy: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 518ca26562f04d7b8e5af9d26317d138
name: 'Output phases discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.3.3.1.2.1.1]'
key: output.phases.discovery
delay: 1h
description: 'The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1'
item_prototypes:
- uuid: c3888f41e7f246b1a30d21325f814695
name: '{#PHASEINDEX}: Phase output current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.3.3.1.4.1.1.{#PHASEINDEX}]'
key: 'phase.output.current[upsPhaseOutputCurrent.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: A
description: |
MIB: PowerNet-MIB
The output current in 0.1 amperes drawn
by the load on the UPS, or -1 if it's unsupported
by this UPS.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 3eb001cece8340d59cd0e7f59812f149
name: '{#PHASEINDEX}: Phase output load, %'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.3.3.1.10.1.1.{#PHASEINDEX}]'
key: 'phase.output.load.percent[upsPhaseOutputPercentLoad.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The percentage of the UPS load capacity in VA at
redundancy @ (n + x) presently being used on this
output phase, or -1 if it's unsupported by this UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: f09e23dcb5b24170b356556a36bb39cc
name: '{#PHASEINDEX}: Phase output voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.3.3.1.3.1.1.{#PHASEINDEX}]'
key: 'phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The output voltage in VAC, or -1 if it's unsupported
by this UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
trigger_prototypes:
- uuid: 675dc7c59e974f7eadd5d1562dec00ce
expression: 'min(/APC UPS Galaxy 3500 by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Galaxy 3500 by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
name: 'APC UPS Galaxy: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage'
event_name: 'APC UPS Galaxy: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
tags:
- tag: class
value: power
- tag: target
value: apc
- tag: target
value: apc-ups-galaxy-3500
macros:
- macro: '{$BATTERY.CAPACITY.MIN.WARN}'
value: '50'
description: 'Minimum battery capacity percentage for trigger expression.'
- macro: '{$BATTERY.TEMP.MAX.WARN}'
value: '55'
description: 'Maximum battery temperature for trigger expression.'
- macro: '{$SNMP.TIMEOUT}'
value: 5m
description: 'The time interval for SNMP agent availability trigger expression.'
- macro: '{$TIME.PERIOD}'
value: 15m
description: 'Time period for trigger expression.'
- macro: '{$UPS.INPUT_FREQ.MAX.WARN}'
value: '50.3'
description: 'Maximum input frequency for trigger expression.'
- macro: '{$UPS.INPUT_FREQ.MIN.WARN}'
value: '49.7'
description: 'Minimum input frequency for trigger expression.'
- macro: '{$UPS.INPUT_VOLT.MAX.WARN}'
value: '243'
description: 'Maximum input voltage for trigger expression.'
- macro: '{$UPS.INPUT_VOLT.MIN.WARN}'
value: '197'
description: 'Minimum input voltage for trigger expression.'
- macro: '{$UPS.OUTPUT.MAX.WARN}'
value: '80'
description: 'Maximum output load in % for trigger expression.'
dashboards:
- uuid: e9b5ac78d15147af9c6ea4b9d44ed57c
name: 'APC UPS Galaxy 3500: General'
pages:
- name: 'APC UPS Galaxy 3500: General'
widgets:
- type: graph
name: Voltage
width: '36'
height: '5'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'APC UPS Galaxy 3500 by SNMP'
name: 'APC UPS Galaxy 3500: Voltage'
- type: STRING
name: reference
value: AAAAA
- type: graph
name: 'Capacity of the UPS batteries'
'y': '5'
width: '36'
height: '5'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'APC UPS Galaxy 3500 by SNMP'
name: 'APC UPS Galaxy 3500: Capacity of the UPS batteries'
- type: STRING
name: reference
value: AAAAC
- type: graph
name: Output
x: '36'
width: '36'
height: '5'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'APC UPS Galaxy 3500 by SNMP'
name: 'APC UPS Galaxy 3500: Output'
- type: STRING
name: reference
value: AAAAB
valuemaps:
- uuid: 30a78904cbc94fc58609dc1a11aa48ef
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
mappings:
- value: '1'
newvalue: Normal
- value: '2'
newvalue: Warning
- value: '3'
newvalue: Critical
- value: '4'
newvalue: 'Not applicable'
- uuid: ace379c23ae247f3b92ccffb9eef920c
name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator'
mappings:
- value: '1'
newvalue: 'no Battery Needs Replacing'
- value: '2'
newvalue: 'battery Needs Replacing'
- uuid: 19686fc030ee4c6bb69aacd3b9c735ca
name: 'PowerNet-MIB::upsAdvInputLineFailCause'
mappings:
- value: '1'
newvalue: 'no Transfer'
- value: '2'
newvalue: 'High Line Voltage'
- value: '3'
newvalue: Brownout
- value: '4'
newvalue: Blackout
- value: '5'
newvalue: 'Small Momentary Sag'
- value: '6'
newvalue: 'Deep Momentary Sag'
- value: '7'
newvalue: 'Small Momentary Spike'
- value: '8'
newvalue: 'Large Momentary Spike'
- value: '9'
newvalue: 'Self Test'
- value: '10'
newvalue: 'Rate of Voltage Change'
- uuid: 80593b554d0a431aa89a0c4960f8565c
name: 'PowerNet-MIB::upsBasicBatteryStatus'
mappings:
- value: '1'
newvalue: Unknown
- value: '2'
newvalue: Normal
- value: '3'
newvalue: Low
- value: '4'
newvalue: 'In Fault Condition'
- uuid: f41b7d5469e64557ab0cdb81526aeac0
name: 'PowerNet-MIB::upsBasicOutputStatus'
mappings:
- value: '1'
newvalue: Unknown
- value: '2'
newvalue: Online
- value: '3'
newvalue: 'On Battery'
- value: '4'
newvalue: 'On Smart Boost'
- value: '5'
newvalue: 'Timed Sleeping'
- value: '6'
newvalue: 'Software Bypass'
- value: '7'
newvalue: 'Off'
- value: '8'
newvalue: Rebooting
- value: '9'
newvalue: 'Switched Bypass'
- value: '10'
newvalue: 'Hardware Failure Bypass'
- value: '11'
newvalue: 'Sleeping Until Power Return'
- value: '12'
newvalue: 'On Smart Trim'
- value: '13'
newvalue: 'Eco Mode'
- value: '14'
newvalue: 'Hot Standby'
- value: '15'
newvalue: 'On Battery Test'
- value: '16'
newvalue: 'Emergency Static Bypass'
- value: '17'
newvalue: 'Static Bypass Standby'
- value: '18'
newvalue: 'Power Saving Mode'
- value: '19'
newvalue: 'Spot Mode'
- value: '20'
newvalue: E-Conversion
- value: '21'
newvalue: 'Charger Spotmode'
- value: '22'
newvalue: 'Inverter Spotmode'
- value: '23'
newvalue: 'Active Load'
- value: '24'
newvalue: 'Battery Discharge Spotmode'
- value: '25'
newvalue: 'Inverter Standby'
- value: '26'
newvalue: 'Charger Only'
- uuid: edd7578bf71146dd88770a39eec537e0
name: zabbix.host.available
mappings:
- value: '0'
newvalue: 'not available'
- value: '1'
newvalue: available
- value: '2'
newvalue: unknown
triggers:
- uuid: 5c50881846c649dbb47adcfb3dfc7d68
expression: |
(last(/APC UPS Galaxy 3500 by SNMP/system.hw.uptime[hrSystemUptime.0])>0 and last(/APC UPS Galaxy 3500 by SNMP/system.hw.uptime[hrSystemUptime.0])<10m)
or (last(/APC UPS Galaxy 3500 by SNMP/system.hw.uptime[hrSystemUptime.0])=0 and last(/APC UPS Galaxy 3500 by SNMP/system.net.uptime[sysUpTime.0])<10m)
name: 'APC UPS Galaxy: Host has been restarted'
event_name: 'APC UPS Galaxy: {HOST.NAME} has been restarted (uptime < 10m)'
priority: WARNING
description: 'Uptime is less than 10 minutes.'
manual_close: 'YES'
dependencies:
- name: 'APC UPS Galaxy: No SNMP data collection'
expression: 'max(/APC UPS Galaxy 3500 by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
tags:
- tag: scope
value: notice
graphs:
- uuid: c4f0ae3090394d1d8918227f1a002702
name: 'APC UPS Galaxy 3500: Capacity of the UPS batteries'
type: PIE
graph_items:
- color: 199C0D
item:
host: 'APC UPS Galaxy 3500 by SNMP'
key: 'battery.capacity[upsHighPrecBatteryCapacity]'
- uuid: d8c7c0451bfd40bf9feb085fb6c5fcf0
name: 'APC UPS Galaxy 3500: Output'
graph_items:
- color: 199C0D
item:
host: 'APC UPS Galaxy 3500 by SNMP'
key: 'output.current[upsHighPrecOutputCurrent]'
- sortorder: '1'
color: F63100
item:
host: 'APC UPS Galaxy 3500 by SNMP'
key: 'output.load[upsHighPrecOutputLoad]'
- uuid: ad9f9b407ae24dd8ba7d2a652bb21fe7
name: 'APC UPS Galaxy 3500: Voltage'
graph_items:
- color: 199C0D
item:
host: 'APC UPS Galaxy 3500 by SNMP'
key: 'input.voltage[upsHighPrecInputLineVoltage]'
- sortorder: '1'
color: F63100
item:
host: 'APC UPS Galaxy 3500 by SNMP'
key: 'output.voltage[upsHighPrecOutputVoltage]'