zabbix_export:
version: '7.0'
template_groups:
- uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
name: Templates/Power
templates:
- uuid: 32d3c78ff44c4c3c9ff5b893ad7f5fc9
template: 'APC Smart-UPS RT 1000 XL by SNMP'
name: 'APC Smart-UPS RT 1000 XL by SNMP'
description: |
Template Power APC Smart-UPS RT 1000 XL
MIBs used:
HOST-RESOURCES-MIB
PowerNet-MIB
SNMPv2-MIB
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
Generated by official Zabbix template tool "Templator"
vendor:
name: Zabbix
version: 7.0-4
groups:
- name: Templates/Power
items:
- uuid: 6ac68411ef214cc7aa49d39d58ce3c6a
name: 'Battery capacity'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.1.0]'
key: 'battery.capacity[upsHighPrecBatteryCapacity]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The remaining battery capacity expressed as
percentage of full capacity.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: b5d618c6090447429191fe4d07e85afa
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}'
name: 'APC Smart-UPS: Battery has low capacity'
event_name: 'APC Smart-UPS: Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%)'
opdata: 'Current capacity: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: capacity
- uuid: 7f3b05afa58142d5b8670c40c196baf8
name: 'External battery packs count'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.5.0]'
key: 'battery.external_packs_count[upsAdvBatteryNumOfBattPacks]'
delay: 1h
description: |
MIB: PowerNet-MIB
The number of external battery packs connected to the UPS. If
the UPS does not use smart cells then the agent reports
ERROR_NO_SUCH_NAME.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: 87b91005f5ff4ba5b0086e25eaa799bd
name: 'Battery last replace date'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.1.3.0]'
key: 'battery.last_replace_date[upsBasicBatteryLastReplaceDate]'
delay: 1h
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The date when the UPS system's batteries were last replaced
in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value
is originally set at the factory. When the UPS batteries
are replaced, this value should be reset by the administrator.
For Symmetra PX 250/500 this OID is read-only and is configurable in the local display only.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: 44a33eba233e4bd7ac51ca2dcabf2939
name: 'Battery replace indicator'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.4.0]'
key: 'battery.replace_indicator[upsAdvBatteryReplaceIndicator]'
description: |
MIB: PowerNet-MIB
Indicates whether the UPS batteries need replacement.
valuemap:
name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: dc92c19a5b7e43a4b155d6d51912aaf8
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2'
name: 'APC Smart-UPS: Battery needs replacement'
priority: HIGH
description: 'A battery installed has an internal error condition.'
tags:
- tag: scope
value: notice
- uuid: 95749270e6234d6cbd1edb0c5e1118e0
name: 'Battery runtime remaining'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.3.0]'
key: 'battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]'
value_type: FLOAT
units: s
description: |
MIB: PowerNet-MIB
The UPS battery run time remaining before battery
exhaustion.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.01'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 047a5a3a957949d288588eb11f36f25e
name: 'Battery status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.1.1.0]'
key: 'battery.status[upsBasicBatteryStatus]'
description: |
MIB: PowerNet-MIB
The status of the UPS batteries. A batteryLow(3) value
indicates the UPS will be unable to sustain the current
load, and its services will be lost if power is not restored.
The amount of run time in reserve at the time of low battery
can be configured by the upsAdvConfigLowBatteryRunTime.
A batteryInFaultCondition(4)value indicates that a battery
installed has an internal error condition.
valuemap:
name: 'PowerNet-MIB::upsBasicBatteryStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
triggers:
- uuid: 70c32834ea40487c8f13a55b7ed7c88f
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/battery.status[upsBasicBatteryStatus])=4'
name: 'APC Smart-UPS: Battery has an internal error condition'
priority: AVERAGE
description: 'A battery installed has an internal error condition.'
tags:
- tag: scope
value: notice
- uuid: e7aeaae896664729b66b42a94f626f9b
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/battery.status[upsBasicBatteryStatus])=3'
name: 'APC Smart-UPS: Battery is Low'
priority: AVERAGE
description: 'The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.'
tags:
- tag: scope
value: capacity
- uuid: 04cd5e06823846b58ad57e2c358f346e
name: 'Battery temperature'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.2.0]'
key: 'battery.temperature[upsHighPrecBatteryTemperature]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The current internal UPS temperature in Celsius.
Temperatures below zero read as 0.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: temperature
triggers:
- uuid: 33695c02cf6141f78e21ca899af10c03
expression: 'min(/APC Smart-UPS RT 1000 XL by SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
name: 'APC Smart-UPS: Battery has high temperature'
event_name: 'APC Smart-UPS: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})'
opdata: 'Current temperature: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 8ee98deaf4bf46afb06f694d19757237
name: 'Battery voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.4.0]'
key: 'battery.voltage[upsHighPrecBatteryActualVoltage]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The actual battery bus voltage in Volts.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 4cb80c94f3d14674bc7a3933c7571eac
name: 'Input fail cause'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.3.2.5.0]'
key: 'input.fail[upsAdvInputLineFailCause]'
description: |
MIB: PowerNet-MIB
The reason for the occurrence of the last transfer to UPS
battery power. The variable is set to:
- noTransfer(1) -- if there is no transfer yet.
- highLineVoltage(2) -- if the transfer to battery is caused
by an over voltage greater than the high transfer voltage.
- brownout(3) -- if the duration of the outage is greater than
five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- blackout(4) -- if the duration of the outage is greater than five
seconds and the line voltage is between 40% of the rated
output voltage and ground.
- smallMomentarySag(5) -- if the duration of the outage is less
than five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- deepMomentarySag(6) -- if the duration of the outage is less
than five seconds and the line voltage is between 40% of the
rated output voltage and ground. The variable is set to
- smallMomentarySpike(7) -- if the line failure is caused by a
rate of change of input voltage less than ten volts per cycle.
- largeMomentarySpike(8) -- if the line failure is caused by
a rate of change of input voltage greater than ten volts per cycle.
- selfTest(9) -- if the UPS was commanded to do a self test.
- rateOfVoltageChange(10) -- if the failure is due to the rate of change of
the line voltage.
valuemap:
name: 'PowerNet-MIB::upsAdvInputLineFailCause'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 700a78a4ab3c441496ecafc5ddde6a9d
name: 'Input frequency'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.3.3.4.0]'
key: 'input.frequency[upsHighPrecInputFrequency]'
value_type: FLOAT
units: Hz
description: |
MIB: PowerNet-MIB
The current input frequency to the UPS system in Hz.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: 167de2d832984944878767571b0b5fe4
expression: 'min(/APC Smart-UPS RT 1000 XL by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 XL by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})'
name: 'APC Smart-UPS: Unacceptable input frequency'
event_name: 'APC Smart-UPS: Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD})'
opdata: 'Current frequency: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: e2b5b824c4704293ad68185971e9fb03
name: 'Input voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.3.3.1.0]'
key: 'input.voltage[upsHighPrecInputLineVoltage]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The current utility line voltage in VAC.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: b8741bc0081a4a9db2824c9f93ecb399
expression: 'min(/APC Smart-UPS RT 1000 XL by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 XL by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})'
name: 'APC Smart-UPS: Unacceptable input voltage'
event_name: 'APC Smart-UPS: Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current voltage: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 861757e4bb1a4dc6ac1c8ef94d973328
name: 'Output current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.3.4.0]'
key: 'output.current[upsHighPrecOutputCurrent]'
value_type: FLOAT
units: A
description: |
MIB: PowerNet-MIB
The current in amperes drawn by the load on the UPS.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 1d9d7ef724ff41eda4fd536df6af93cb
name: 'Output load'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.3.3.0]'
key: 'output.load[upsHighPrecOutputLoad]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The current UPS load expressed as percentage
of rated capacity.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: a4faec3975134cd59e83f1ca7fa3ef7d
expression: 'min(/APC Smart-UPS RT 1000 XL by SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}'
name: 'APC Smart-UPS: Output load is high'
event_name: 'APC Smart-UPS: Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD})'
opdata: 'Current load: {ITEM.LASTVALUE1}'
priority: HIGH
description: 'A battery installed has an internal error condition.'
tags:
- tag: scope
value: notice
- uuid: 3edf5e7776ae4cc6aebcedcbf4ab8d78
name: 'Output status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.1.1.0]'
key: 'output.status[upsBasicOutputStatus]'
description: |
MIB: PowerNet-MIB
The current state of the UPS. If the UPS is unable to
determine the state of the UPS this variable is set
to unknown(1).
During self-test most UPSes report onBattery(3) but
some that support it will report onBatteryTest(15).
To determine self-test status across all UPSes, refer
to the upsBasicStateOutputState OID.
valuemap:
name: 'PowerNet-MIB::upsBasicOutputStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
triggers:
- uuid: deedd977f1ed4b9fbb5cc161dde0c116
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=16'
name: 'APC Smart-UPS: UPS is Emergency Static Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: a7bbe6ca410743919f7c611a6faec9ba
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=10'
name: 'APC Smart-UPS: UPS is Hardware Failure Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 974042a124b945068c6c16c4a01433dc
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=7'
name: 'APC Smart-UPS: UPS is Off'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 90e810043e41467b8460278fc7923397
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=3'
name: 'APC Smart-UPS: UPS is on battery'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 656ae233f3a946799c3ed3d48914c0b0
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=4'
name: 'APC Smart-UPS: UPS is on Smart Boost'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 3fcbd14931854831ac603a254ffea0c3
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=12'
name: 'APC Smart-UPS: UPS is On Smart Trim'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 65085178eef54189afdaf4937de49177
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=8'
name: 'APC Smart-UPS: UPS is Rebooting'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 0aa402907ee446c0a13fa086b500fa87
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=11'
name: 'APC Smart-UPS: UPS is Sleeping Until Power Return'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: be6cdd1fc22a4f0eacdbce4361cd6788
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=6'
name: 'APC Smart-UPS: UPS is Software Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: b4375fc980ae4bee87531d18ea9a5397
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=9'
name: 'APC Smart-UPS: UPS is Switched Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 7ae9e31ac32944928065d1cefb2c4e2f
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=5'
name: 'APC Smart-UPS: UPS is Timed Sleeping'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: bcb28618699448ea8d9d056bad203a0e
name: 'Output voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.3.1.0]'
key: 'output.voltage[upsHighPrecOutputVoltage]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The output voltage of the UPS system in VAC.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: d633cd3273e74209a1b0c6b761028e0a
name: 'SNMP traps (fallback)'
type: SNMP_TRAP
key: snmptrap.fallback
delay: '0'
value_type: LOG
trends: '0'
description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items'
logtimefmt: 'hh:mm:sszyyyy/MM/dd'
tags:
- tag: component
value: network
- uuid: 50cc8e7cea0c40948c006623dfa94dae
name: 'System contact details'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.4.0]'
key: 'system.contact[sysContact.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
The textual identification of the contact person for this managed
node, together with information on how to contact this person. If no contact
information is known, the value is the zero-length string.
inventory_link: CONTACT
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 12h
tags:
- tag: component
value: system
- uuid: e0d638ab398f40e8a9555925cd8ba907
name: 'System description'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.1.0]'
key: 'system.descr[sysDescr.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
A textual description of the entity. This value should
include the full name and version identification of the system's hardware type, software operating-system, and
networking software.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 12h
tags:
- tag: component
value: system
- uuid: 4def354a520e42d78d67b2e8b1cd8eb4
name: 'Uptime (hardware)'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.25.1.1.0]'
key: 'system.hw.uptime[hrSystemUptime.0]'
delay: 30s
trends: '0'
units: uptime
description: |
MIB: HOST-RESOURCES-MIB
The amount of time since this host was last initialized. Note that this is different from sysUpTime in the SNMPv2-MIB [RFC1907] because sysUpTime is the uptime of the network management portion of the system.
preprocessing:
- type: CHECK_NOT_SUPPORTED
parameters:
- '-1'
error_handler: CUSTOM_VALUE
error_handler_params: '0'
- type: MULTIPLIER
parameters:
- '0.01'
tags:
- tag: component
value: system
- uuid: 031b9d385cae4641b9ecfb76c4174262
name: 'System location'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.6.0]'
key: 'system.location[sysLocation.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
The physical location of this node (e.g., `telephone closet, 3rd floor'). If the location is unknown, the value is the zero-length string.
inventory_link: LOCATION
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: system
- uuid: 320221ba30744ca78b8dce03dccd549b
name: Model
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.1.1.1.0]'
key: 'system.model[upsBasicIdentModel]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The UPS model name (e.g. 'APC Smart-UPS 600').
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: e4d9441075954c068b6fd92bbff49cef
name: 'System name'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.5.0]'
key: 'system.name[sysName.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
An administratively-assigned name for this managed node.By convention, this is the node's fully-qualified domain name. If the name is unknown, the value is the zero-length string.
inventory_link: NAME
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: system
triggers:
- uuid: 31bb0ff1ea334cd59d9f8b8f489611ef
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS RT 1000 XL by SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS RT 1000 XL by SNMP/system.name[sysName.0]))>0'
name: 'APC Smart-UPS: System name has changed'
event_name: 'APC Smart-UPS: System name has changed (new name: {ITEM.VALUE})'
priority: INFO
description: 'The name of the system has changed. Acknowledge to close the problem manually.'
manual_close: 'YES'
tags:
- tag: scope
value: notice
- tag: scope
value: security
- uuid: bbcb555846df4169bc7aead77403e8eb
name: 'Uptime (network)'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.3.0]'
key: 'system.net.uptime[sysUpTime.0]'
delay: 30s
trends: '0'
units: uptime
description: |
MIB: SNMPv2-MIB
The time (in hundredths of a second) since the network management portion of the system was last re-initialized.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.01'
tags:
- tag: component
value: system
- uuid: 4e7a9b6aa8dd4371b83bf47f8246cebf
name: 'System object ID'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.2.0]'
key: 'system.objectid[sysObjectID.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
The vendor's authoritative identification of the network management subsystem contained in the entity. This value is allocated within the SMI enterprises subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1 to its `Fred Router'.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: system
- uuid: 9ebb979a5e4a45fd9acf956df034f9be
name: 'Serial number'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.1.2.3.0]'
key: 'system.sn[upsAdvIdentSerialNumber]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
An 8-character string identifying the serial number of
the UPS internal microprocessor. This number is set at
the factory. NOTE: This number does NOT correspond to
the serial number on the rear of the UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: f24fc7ed9ffa4884891a01a0f1565fc4
name: 'SNMP agent availability'
type: INTERNAL
key: 'zabbix[host,snmp,available]'
description: |
Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.
Possible values:
0 - not available
1 - available
2 - unknown
valuemap:
name: zabbix.host.available
tags:
- tag: component
value: health
- tag: component
value: network
triggers:
- uuid: 21fc3a198f3b423fa14676278f53a4be
expression: 'max(/APC Smart-UPS RT 1000 XL by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
name: 'APC Smart-UPS: No SNMP data collection'
opdata: 'Current state: {ITEM.LASTVALUE1}'
priority: WARNING
description: 'SNMP is not available for polling. Please check device connectivity and SNMP settings.'
tags:
- tag: scope
value: availability
discovery_rules:
- uuid: 9389b159502e4242b02a11104124bae5
name: 'External bad battery packs discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#EXTERNAL_PACKS},1.3.6.1.4.1.318.1.1.1.2.2.6]'
key: battery.packs.bad.discovery
delay: 1h
filter:
evaltype: AND
conditions:
- macro: '{#EXTERNAL_PACKS}'
value: '-1'
operator: NOT_MATCHES_REGEX
formulaid: A
description: 'Discovery of the number of external defective battery packs.'
item_prototypes:
- uuid: 202a5c9f91c64011a915157a07245a6d
name: '{#SNMPINDEX}: External battery packs bad'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.6.0]'
key: 'battery.external_packs_bad[upsAdvBatteryNumOfBadBattPacks.{#SNMPINDEX}]'
delay: 15m
description: |
MIB: PowerNet-MIB
The number of external battery packs connected to the UPS that
are defective. If the UPS does not use smart cells then the
agent reports ERROR_NO_SUCH_NAME.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: ec66331f2ae64801a3ef51d6dec5a00f
name: 'External battery packs discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#CARTRIDGE_STATUS},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7,{#BATTERY_PACK},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1,{#CARTRIDGE_INDEX},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2]'
key: battery.packs.discovery
delay: 1h
filter:
evaltype: AND
conditions:
- macro: '{#CARTRIDGE_STATUS}'
value: ^$
operator: NOT_MATCHES_REGEX
formulaid: A
item_prototypes:
- uuid: 8d1574f1c1d442529509580309153564
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery estimated replace date'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8.{#SNMPINDEX}]'
key: 'battery.estimated_replace_date[upsHighPrecBatteryPackCartridgeReplaceDate.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
delay: 1h
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The battery cartridge estimated battery replace date.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- tag: component
value: power
- uuid: 3c829e3adec64fb39334dbacc03a3229
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7.{#SNMPINDEX}]'
key: 'battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The battery cartridge health.
bit 0 Battery lifetime okay
bit 1 Battery lifetime near end, order replacement cartridge
bit 2 Battery lifetime exceeded, replace battery
bit 3 Battery lifetime near end acknowledged, order replacement cartridge
bit 4 Battery lifetime exceeded acknowledged, replace battery
bit 5 Battery measured lifetime near end, order replacement cartridge
bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: c353d8e0b0584c6c8ba81514f5c66995
expression: 'find(/APC Smart-UPS RT 1000 XL by SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1'
name: 'APC Smart-UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay'
opdata: 'Current bit set: {ITEM.LASTVALUE1}'
priority: WARNING
description: |
The battery cartridge health.
bit 0 Battery lifetime okay
bit 1 Battery lifetime near end, order replacement cartridge
bit 2 Battery lifetime exceeded, replace battery
bit 3 Battery lifetime near end acknowledged, order replacement cartridge
bit 4 Battery lifetime exceeded acknowledged, replace battery
bit 5 Battery measured lifetime near end, order replacement cartridge
bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge
tags:
- tag: scope
value: notice
- uuid: 15f52cb076cb414fb794113e9981fdde
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10.{#SNMPINDEX}]'
key: 'battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The status of the UPS batteries. A batteryLow(3) value
indicates the UPS will be unable to sustain the current
load, and its services will be lost if power is not restored.
The amount of run time in reserve at the time of low battery
can be configured by the upsAdvConfigLowBatteryRunTime.
A batteryInFaultCondition(4)value indicates that a battery
installed has an internal error condition.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: 26535b11c27b4fbe92285b56cbbf5a73
expression: 'find(/APC Smart-UPS RT 1000 XL by SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0'
name: 'APC Smart-UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay'
opdata: 'Current bit set: {ITEM.LASTVALUE1}'
priority: WARNING
description: |
The battery cartridge status:
bit 0 Disconnected
bit 1 Overvoltage
bit 2 NeedsReplacement
bit 3 OvertemperatureCritical
bit 4 Charger
bit 5 TemperatureSensor
bit 6 BusSoftStart
bit 7 OvertemperatureWarning
bit 8 GeneralError
bit 9 Communication
bit 10 DisconnectedFrame
bit 11 FirmwareMismatch
tags:
- tag: scope
value: notice
- uuid: e0d8f68302264c1b9420284f3e3a0272
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperature'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5.{#SNMPINDEX}]'
key: 'battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The current internal UPS temperature in Celsius.
Temperatures below zero read as 0.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: temperature
trigger_prototypes:
- uuid: 7f8613d752524d588e60aa1cab2c60bd
expression: 'min(/APC Smart-UPS RT 1000 XL by SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
name: 'APC Smart-UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature'
event_name: 'APC Smart-UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})'
opdata: 'Current temperature: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: bca352c952174256b9cfbcffb86fbf90
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4.{#SNMPINDEX}]'
key: 'system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
An 8-character string identifying the serial number of
the UPS internal microprocessor. This number is set at
the factory. NOTE: This number does NOT correspond to
the serial number on the rear of the UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: 19379361227740c3bf8bc9852886538d
name: 'External sensor port 1 discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#EXTERNAL_SENSOR1_NAME},1.3.6.1.4.1.318.1.1.25.1.2.1.3]'
key: external.sensor1.discovery
delay: 1h
description: uioSensorStatusTable
item_prototypes:
- uuid: d9c8acbf3a90411582404c9d5cfa9f70
name: '{#EXTERNAL_SENSOR1_NAME}: Humidity sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.1.7.{#SNMPINDEX}]'
key: 'external.sensor.humidity[uioSensorStatusHumidity.1.{#SNMPINDEX}]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The sensor's current humidity reading - a relative humidity
percentage. -1 indicates an invalid reading due to either a
sensor that doesn't read humidity or lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: humidity
- tag: component
value: power
- uuid: 1a475822bc324bbf8c4aa15c34734270
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.1.9.{#SNMPINDEX}]'
key: 'external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}]'
description: |
MIB: PowerNet-MIB
The alarm status of the sensor. Possible values:
uioNormal (1),
uioWarning (2),
uioCritical (3),
sensorStatusNotApplicable (4)
valuemap:
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: 40e22c5379f34edf87d1ea52ffae60b8
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3'
name: 'APC Smart-UPS: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical'
priority: HIGH
description: 'The external sensor has returned a value greater than the critical threshold.'
tags:
- tag: scope
value: notice
- uuid: a482de04a5d34807874fc7a7c506dd40
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4'
name: 'APC Smart-UPS: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable'
priority: INFO
description: 'The external sensor does not work or is not connected.'
tags:
- tag: scope
value: notice
- uuid: dca875c511b04dc1857de74223c4f27b
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2'
name: 'APC Smart-UPS: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning'
priority: AVERAGE
description: 'The external sensor has returned a value greater than the warning threshold.'
tags:
- tag: scope
value: notice
- uuid: 6d1005b2b6ad41369174d93b1ebe1959
name: '{#EXTERNAL_SENSOR1_NAME}: Temperature sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.1.6.{#SNMPINDEX}]'
key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.1.{#SNMPINDEX}]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The sensor's current temperature reading in Celsius.
-1 indicates an invalid reading due to lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- tag: component
value: temperature
overrides:
- name: Temp
step: '1'
filter:
evaltype: AND
conditions:
- macro: '{#EXTERNAL_SENSOR1_NAME}'
value: Temp
formulaid: A
operations:
- operationobject: ITEM_PROTOTYPE
operator: LIKE
value: Humidity
discover: NO_DISCOVER
- uuid: c4df3e0e0eba4585bdd01358f9d7f5d9
name: 'External sensor port 2 discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#EXTERNAL_SENSOR2_NAME},1.3.6.1.4.1.318.1.1.25.1.2.2.3]'
key: external.sensor2.discovery
delay: 1h
description: uioSensorStatusTable
item_prototypes:
- uuid: 7d08e2a5df41454f863f5b50a911f819
name: '{#EXTERNAL_SENSOR2_NAME}: Humidity sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.2.7.{#SNMPINDEX}]'
key: 'external.sensor.humidity[uioSensorStatusHumidity.2.{#SNMPINDEX}]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The sensor's current humidity reading - a relative humidity
percentage. -1 indicates an invalid reading due to either a
sensor that doesn't read humidity or lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: humidity
- tag: component
value: power
- uuid: 4774fd152aab49de9064490cf7ec1d0a
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.2.9.{#SNMPINDEX}]'
key: 'external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}]'
description: |
MIB: PowerNet-MIB
The alarm status of the sensor. Possible values:
uioNormal (1),
uioWarning (2),
uioCritical (3),
sensorStatusNotApplicable (4)
valuemap:
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: 650a1d16e56c45188c6246e960d62857
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3'
name: 'APC Smart-UPS: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical'
priority: HIGH
description: 'The external sensor has returned a value greater than the critical threshold.'
tags:
- tag: scope
value: notice
- uuid: 7518ae06e3a14866b9e6d90a224055f7
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4'
name: 'APC Smart-UPS: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable'
priority: INFO
description: 'The external sensor does not work or is not connected.'
tags:
- tag: scope
value: notice
- uuid: 65aa8a5380f141498dd9c718972110b3
expression: 'last(/APC Smart-UPS RT 1000 XL by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2'
name: 'APC Smart-UPS: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning'
priority: AVERAGE
description: 'The external sensor has returned a value greater than the warning threshold.'
tags:
- tag: scope
value: notice
- uuid: d94425f2025045459af40e8fcb72734e
name: '{#EXTERNAL_SENSOR2_NAME}: Temperature sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.2.6.{#SNMPINDEX}]'
key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.2.{#SNMPINDEX}]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The sensor's current temperature reading in Celsius.
-1 indicates an invalid reading due to lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- tag: component
value: temperature
overrides:
- name: Temp
step: '1'
filter:
conditions:
- macro: '{#EXTERNAL_SENSOR2_NAME}'
value: Temp
formulaid: A
operations:
- operationobject: ITEM_PROTOTYPE
operator: LIKE
value: Humidity
discover: NO_DISCOVER
- uuid: 68610f5b6df44229bcb0ad4b0fa1c3f8
name: 'Input phases discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.2.3.1.2.1.1]'
key: input.phases.discovery
delay: 1h
description: 'The input phase identifier. OID upsPhaseInputPhaseIndex.1.1'
item_prototypes:
- uuid: d17e9bb868b143dca508c4f79092cd6e
name: '{#PHASEINDEX}: Phase input current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.2.3.1.6.1.1.{#PHASEINDEX}]'
key: 'phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: A
description: |
MIB: PowerNet-MIB
The input current in 0.1 amperes, or -0.1 if it's
unsupported by this UPS.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: cf03abf328754a4082017f480051292f
name: '{#PHASEINDEX}: Phase input voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.2.3.1.3.1.1.{#PHASEINDEX}]'
key: 'phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The input voltage in VAC, or -1 if it's unsupported
by this UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
trigger_prototypes:
- uuid: 8c9226411afb4b32ba3e9d6232ff4710
expression: 'min(/APC Smart-UPS RT 1000 XL by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
name: 'APC Smart-UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage'
event_name: 'APC Smart-UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: a7b39188df294ec182c3e1f2a2417154
name: 'Output phases discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.3.3.1.2.1.1]'
key: output.phases.discovery
delay: 1h
description: 'The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1'
item_prototypes:
- uuid: 638c63c2f4ad4cad8ed71a796d78705b
name: '{#PHASEINDEX}: Phase output current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.3.3.1.4.1.1.{#PHASEINDEX}]'
key: 'phase.output.current[upsPhaseOutputCurrent.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: A
description: |
MIB: PowerNet-MIB
The output current in 0.1 amperes drawn
by the load on the UPS, or -1 if it's unsupported
by this UPS.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: ba4a2ae8abea4e2692b9a43231783648
name: '{#PHASEINDEX}: Phase output load, %'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.3.3.1.10.1.1.{#PHASEINDEX}]'
key: 'phase.output.load.percent[upsPhaseOutputPercentLoad.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The percentage of the UPS load capacity in VA at
redundancy @ (n + x) presently being used on this
output phase, or -1 if it's unsupported by this UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 4e22c7f6d7e14b20b3720e082042fd4f
name: '{#PHASEINDEX}: Phase output voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.3.3.1.3.1.1.{#PHASEINDEX}]'
key: 'phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The output voltage in VAC, or -1 if it's unsupported
by this UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
trigger_prototypes:
- uuid: 58e0697a9a9147a4b1dfda251f2b593e
expression: 'min(/APC Smart-UPS RT 1000 XL by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
name: 'APC Smart-UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage'
event_name: 'APC Smart-UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
tags:
- tag: class
value: power
- tag: target
value: apc
- tag: target
value: apc-smart-ups-rt-1000-xl
macros:
- macro: '{$BATTERY.CAPACITY.MIN.WARN}'
value: '50'
description: 'Minimum battery capacity percentage for trigger expression.'
- macro: '{$BATTERY.TEMP.MAX.WARN}'
value: '55'
description: 'Maximum battery temperature for trigger expression.'
- macro: '{$SNMP.TIMEOUT}'
value: 5m
description: 'The time interval for SNMP agent availability trigger expression.'
- macro: '{$TIME.PERIOD}'
value: 15m
description: 'Time period for trigger expression.'
- macro: '{$UPS.INPUT_FREQ.MAX.WARN}'
value: '50.3'
description: 'Maximum input frequency for trigger expression.'
- macro: '{$UPS.INPUT_FREQ.MIN.WARN}'
value: '49.7'
description: 'Minimum input frequency for trigger expression.'
- macro: '{$UPS.INPUT_VOLT.MAX.WARN}'
value: '243'
description: 'Maximum input voltage for trigger expression.'
- macro: '{$UPS.INPUT_VOLT.MIN.WARN}'
value: '197'
description: 'Minimum input voltage for trigger expression.'
- macro: '{$UPS.OUTPUT.MAX.WARN}'
value: '80'
description: 'Maximum output load in % for trigger expression.'
dashboards:
- uuid: 498b4d5a91574c25a798e90c529eb100
name: 'APC Smart-UPS RT 1000 XL: General'
pages:
- name: 'APC Smart-UPS RT 1000 XL: General'
widgets:
- type: graph
name: Voltage
width: '36'
height: '5'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'APC Smart-UPS RT 1000 XL by SNMP'
name: 'APC Smart-UPS RT 1000 XL: Voltage'
- type: STRING
name: reference
value: AAAAA
- type: graph
name: 'Capacity of the UPS batteries'
'y': '5'
width: '36'
height: '5'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'APC Smart-UPS RT 1000 XL by SNMP'
name: 'APC Smart-UPS RT 1000 XL: Capacity of the UPS batteries'
- type: STRING
name: reference
value: AAAAC
- type: graph
name: Output
x: '36'
width: '36'
height: '5'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'APC Smart-UPS RT 1000 XL by SNMP'
name: 'APC Smart-UPS RT 1000 XL: Output'
- type: STRING
name: reference
value: AAAAB
valuemaps:
- uuid: b2af1e2dcb874d43949c383f9b347f36
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
mappings:
- value: '1'
newvalue: Normal
- value: '2'
newvalue: Warning
- value: '3'
newvalue: Critical
- value: '4'
newvalue: 'Not applicable'
- uuid: b06b54b07e6840e5a0c52ba7a6acf86a
name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator'
mappings:
- value: '1'
newvalue: 'no Battery Needs Replacing'
- value: '2'
newvalue: 'battery Needs Replacing'
- uuid: a62f96735c47467da94b6bcf98cc013d
name: 'PowerNet-MIB::upsAdvInputLineFailCause'
mappings:
- value: '1'
newvalue: 'no Transfer'
- value: '2'
newvalue: 'High Line Voltage'
- value: '3'
newvalue: Brownout
- value: '4'
newvalue: Blackout
- value: '5'
newvalue: 'Small Momentary Sag'
- value: '6'
newvalue: 'Deep Momentary Sag'
- value: '7'
newvalue: 'Small Momentary Spike'
- value: '8'
newvalue: 'Large Momentary Spike'
- value: '9'
newvalue: 'Self Test'
- value: '10'
newvalue: 'Rate of Voltage Change'
- uuid: ed12e8780c384caba8035fbb1c78e115
name: 'PowerNet-MIB::upsBasicBatteryStatus'
mappings:
- value: '1'
newvalue: Unknown
- value: '2'
newvalue: Normal
- value: '3'
newvalue: Low
- value: '4'
newvalue: 'In Fault Condition'
- uuid: ae2ed0c2c99a4ad496f7a35226e3d4f0
name: 'PowerNet-MIB::upsBasicOutputStatus'
mappings:
- value: '1'
newvalue: Unknown
- value: '2'
newvalue: Online
- value: '3'
newvalue: 'On Battery'
- value: '4'
newvalue: 'On Smart Boost'
- value: '5'
newvalue: 'Timed Sleeping'
- value: '6'
newvalue: 'Software Bypass'
- value: '7'
newvalue: 'Off'
- value: '8'
newvalue: Rebooting
- value: '9'
newvalue: 'Switched Bypass'
- value: '10'
newvalue: 'Hardware Failure Bypass'
- value: '11'
newvalue: 'Sleeping Until Power Return'
- value: '12'
newvalue: 'On Smart Trim'
- value: '13'
newvalue: 'Eco Mode'
- value: '14'
newvalue: 'Hot Standby'
- value: '15'
newvalue: 'On Battery Test'
- value: '16'
newvalue: 'Emergency Static Bypass'
- value: '17'
newvalue: 'Static Bypass Standby'
- value: '18'
newvalue: 'Power Saving Mode'
- value: '19'
newvalue: 'Spot Mode'
- value: '20'
newvalue: E-Conversion
- value: '21'
newvalue: 'Charger Spotmode'
- value: '22'
newvalue: 'Inverter Spotmode'
- value: '23'
newvalue: 'Active Load'
- value: '24'
newvalue: 'Battery Discharge Spotmode'
- value: '25'
newvalue: 'Inverter Standby'
- value: '26'
newvalue: 'Charger Only'
- uuid: 8cddc4f99ecb4866b1638b82b145ea8b
name: zabbix.host.available
mappings:
- value: '0'
newvalue: 'not available'
- value: '1'
newvalue: available
- value: '2'
newvalue: unknown
triggers:
- uuid: 860d3beb50c0400283a71c2c4b4ea5e2
expression: |
(last(/APC Smart-UPS RT 1000 XL by SNMP/system.hw.uptime[hrSystemUptime.0])>0 and last(/APC Smart-UPS RT 1000 XL by SNMP/system.hw.uptime[hrSystemUptime.0])<10m)
or (last(/APC Smart-UPS RT 1000 XL by SNMP/system.hw.uptime[hrSystemUptime.0])=0 and last(/APC Smart-UPS RT 1000 XL by SNMP/system.net.uptime[sysUpTime.0])<10m)
name: 'APC Smart-UPS: Host has been restarted'
event_name: 'APC Smart-UPS: {HOST.NAME} has been restarted (uptime < 10m)'
priority: WARNING
description: 'Uptime is less than 10 minutes.'
manual_close: 'YES'
dependencies:
- name: 'APC Smart-UPS: No SNMP data collection'
expression: 'max(/APC Smart-UPS RT 1000 XL by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
tags:
- tag: scope
value: notice
graphs:
- uuid: a0d8e0338b8d4fd2bd6fdf537373d63c
name: 'APC Smart-UPS RT 1000 XL: Capacity of the UPS batteries'
type: PIE
graph_items:
- color: 199C0D
item:
host: 'APC Smart-UPS RT 1000 XL by SNMP'
key: 'battery.capacity[upsHighPrecBatteryCapacity]'
- uuid: 0817d2550d9642fe95ce182dce5cefd8
name: 'APC Smart-UPS RT 1000 XL: Output'
graph_items:
- color: 199C0D
item:
host: 'APC Smart-UPS RT 1000 XL by SNMP'
key: 'output.current[upsHighPrecOutputCurrent]'
- sortorder: '1'
color: F63100
item:
host: 'APC Smart-UPS RT 1000 XL by SNMP'
key: 'output.load[upsHighPrecOutputLoad]'
- uuid: ce2f4070e7a14d8283d0a8aff0fcd5e6
name: 'APC Smart-UPS RT 1000 XL: Voltage'
graph_items:
- color: 199C0D
item:
host: 'APC Smart-UPS RT 1000 XL by SNMP'
key: 'input.voltage[upsHighPrecInputLineVoltage]'
- sortorder: '1'
color: F63100
item:
host: 'APC Smart-UPS RT 1000 XL by SNMP'
key: 'output.voltage[upsHighPrecOutputVoltage]'