zabbix_export:
version: '7.0'
template_groups:
- uuid: 36bff6c29af64692839d077febfc7079
name: 'Templates/Network devices'
templates:
- uuid: f1336fd88ab0415a9c02892a71e50032
template: 'Morningstar SunSaver MPPT by SNMP'
name: 'Morningstar SunSaver MPPT by SNMP'
description: |
MIBs used:
SUNSAVER-MPPT
Generated by official Zabbix template tool "Templator"
vendor:
name: Zabbix
version: 7.0-2
groups:
- name: 'Templates/Network devices'
items:
- uuid: 9836b1fc81b84a44b2a708291bd5bf1a
name: 'Array: Sweep Pmax'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.57.0]'
key: 'array.sweep_pmax[arrayMaxPowerSweep.0]'
value_type: FLOAT
units: W
description: |
MIB: SUNSAVER-MPPT
Description:Array Open Circuit Voltage
Scaling Factor:0.0030517578125
Units:V
Range:[0.0, 80.0]
Modbus address:0x002A
preprocessing:
- type: MULTIPLIER
parameters:
- '0.01509857178'
- type: REGEX
parameters:
- '^(\d+)(\.\d{1,2})?'
- \1\2
tags:
- tag: component
value: array
- uuid: 0842746ca41c44128a575113307259e2
name: 'Array: Sweep Vmp'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.56.0]'
key: 'array.sweep_vmp[arrayVmp.0]'
value_type: FLOAT
units: V
description: |
MIB: SUNSAVER-MPPT
Description:Array Max. Power Point Voltage
Scaling Factor:0.0030517578125
Units:V
Range:[0.0, 5000.0]
Modbus address:0x0028
preprocessing:
- type: MULTIPLIER
parameters:
- '0.003051757813'
- type: REGEX
parameters:
- '^(\d+)(\.\d{1,2})?'
- \1\2
tags:
- tag: component
value: array
- uuid: 0e3371208513416ab1b9afdf2c3b2c08
name: 'Array: Sweep Voc'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.58.0]'
key: 'array.sweep_voc[arrayVoc.0]'
value_type: FLOAT
units: V
description: |
MIB: SUNSAVER-MPPT
Description:Array Open Circuit Voltage
Scaling Factor:0.0030517578125
Units:V
Range:[0.0, 80.0]
Modbus address:0x002A
preprocessing:
- type: MULTIPLIER
parameters:
- '0.003051757813'
- type: REGEX
parameters:
- '^(\d+)(\.\d{1,2})?'
- \1\2
tags:
- tag: component
value: array
- uuid: da1f347b28dd4fbeb123f228adefb0ed
name: 'Array: Voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.31.0]'
key: 'array.voltage[arrayVoltage.0]'
value_type: FLOAT
units: V
description: |
MIB: SUNSAVER-MPPT
Description:Array Voltage
Scaling Factor:0.0030517578125
Units:V
Range:[0, 80]
Modbus address:0x0009
preprocessing:
- type: MULTIPLIER
parameters:
- '0.003051757813'
- type: REGEX
parameters:
- '^(\d+)(\.\d{1,2})?'
- \1\2
tags:
- tag: component
value: array
- uuid: f8803a1390b745f08673d4ea998548a9
name: 'Battery: Battery Voltage discovery'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.30.0]'
key: 'battery.voltage.discovery[batteryVoltage.0]'
delay: 15m
history: '0'
value_type: FLOAT
units: V
description: 'MIB: SUNSAVER-MPPT'
preprocessing:
- type: MULTIPLIER
parameters:
- '0.003051757813'
tags:
- tag: component
value: battery
- tag: component
value: discovery
- tag: component
value: raw
- uuid: a36313ef0933403788a42de8a62b4838
name: 'Battery: Charge Current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.33.0]'
key: 'charge.current[chargeCurrent.0]'
value_type: FLOAT
units: A
description: |
MIB: SUNSAVER-MPPT
Description:Target Regulation Voltage
Scaling Factor:0.0030517578125
Units:V
Range:[0.0, 80.0]
Modbus address:0x0014
preprocessing:
- type: MULTIPLIER
parameters:
- '0.002415771484'
- type: REGEX
parameters:
- '^(\d+)(\.\d{1,2})?'
- \1\2
tags:
- tag: component
value: battery
- uuid: 4da765c8e26540c190ea07be08b87abc
name: 'Battery: Charge State'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.39.0]'
key: 'charge.state[chargeState.0]'
value_type: FLOAT
description: |
MIB: SUNSAVER-MPPT
Description:Control State
Modbus address:0x0011
0: Start
1: NightCheck
2: Disconnect
3: Night
4: Fault
5: BulkMppt
6: Pwm
7: Float
8: Equalize
valuemap:
name: 'SunSaver MPPT charge state'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
tags:
- tag: component
value: battery
triggers:
- uuid: 0362139c66f4464db8c022b9ffce5502
expression: 'last(/Morningstar SunSaver MPPT by SNMP/charge.state[chargeState.0])={$CHARGE.STATE.CRIT}'
name: 'Morningstar SunSaver MPPT: Battery: Device charge in critical state'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: d5439cee53b148ecb4186286c4e93ada
expression: 'last(/Morningstar SunSaver MPPT by SNMP/charge.state[chargeState.0])={$CHARGE.STATE.WARN}'
name: 'Morningstar SunSaver MPPT: Battery: Device charge in warning state'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar SunSaver MPPT: Battery: Device charge in critical state'
expression: 'last(/Morningstar SunSaver MPPT by SNMP/charge.state[chargeState.0])={$CHARGE.STATE.CRIT}'
tags:
- tag: scope
value: notice
- uuid: 149545b9154044e3af27b4e9ad809c0e
name: 'Counter: Charge Amp-hours'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.43.0]'
key: 'counter.charge_amp_hours[ahChargeResettable.0]'
value_type: FLOAT
units: Ah
description: |
MIB: SUNSAVER-MPPT
Description:Ah Charge(Resettable)
Scaling Factor:0.1
Units:Ah
Range:[0.0, 4294967294]
Modbus addresses:H=0x0015 L=0x0016
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
tags:
- tag: component
value: counter
- uuid: f6d0f89c747b4418ad34c32b5ac9a5b9
name: 'Counter: Charge KW-hours'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.45.0]'
key: 'counter.charge_kw_hours[kwhCharge.0]'
units: '!kWh'
description: 'MIB: SUNSAVER-MPPT'
tags:
- tag: component
value: counter
- uuid: 28e679eace174d289ca5ccf90f3b9150
name: 'Counter: Load Amp-hours'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.49.0]'
key: 'counter.load_amp_hours[ahLoadResettable.0]'
value_type: FLOAT
units: Ah
description: |
MIB: SUNSAVER-MPPT
Description:Ah Load(Resettable)
Scaling Factor:0.1
Units:Ah
Range:[0.0, 4294967294]
Modbus addresses:H=0x001D L=0x001E
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
tags:
- tag: component
value: counter
- uuid: 6491ee507d9a4c099852d33e57df48a9
name: 'Load: Current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.34.0]'
key: 'load.current[loadCurrent.0]'
value_type: FLOAT
units: A
description: |
MIB: SUNSAVER-MPPT
Description:Load Current
Scaling Factor:0.002415771484375
Units:A
Range:[0, 60]
Modbus address:0x000C
preprocessing:
- type: MULTIPLIER
parameters:
- '0.002415771484'
- type: REGEX
parameters:
- '^(\d+)(\.\d{1,2})?'
- \1\2
tags:
- tag: component
value: load
- uuid: c5dfef2deee445ec88e2d63dbfbbaf68
name: 'Load: State'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.46.0]'
key: 'load.state[loadState.0]'
value_type: FLOAT
description: |
MIB: SUNSAVER-MPPT
Description:Load State
Modbus address:0x001A
0: Start
1: Normal
2: LvdWarning
3: Lvd
4: Fault
5: Disconnect
6: NormalOff
7: Override
8: NotUsed
valuemap:
name: 'SunSaver MPPT load state'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
tags:
- tag: component
value: load
triggers:
- uuid: bbd3a89b012a40daa646ec7113d43e43
expression: 'last(/Morningstar SunSaver MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.CRIT:"lvd"} or last(/Morningstar SunSaver MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.CRIT:"fault"}'
name: 'Morningstar SunSaver MPPT: Load: Device load in critical state'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 8f6967c1b577431c995a3c13f8cdb1c1
expression: 'last(/Morningstar SunSaver MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.WARN:"lvdWarning"} or last(/Morningstar SunSaver MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.WARN:"override"}'
name: 'Morningstar SunSaver MPPT: Load: Device load in warning state'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar SunSaver MPPT: Load: Device load in critical state'
expression: 'last(/Morningstar SunSaver MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.CRIT:"lvd"} or last(/Morningstar SunSaver MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.CRIT:"fault"}'
tags:
- tag: scope
value: notice
- uuid: a9ca69fcedbb4524a8eb4b92b975008e
name: 'Load: Voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.32.0]'
key: 'load.voltage[loadVoltage.0]'
value_type: FLOAT
units: V
description: |
MIB: SUNSAVER-MPPT
Description:Load Voltage
Scaling Factor:0.0030517578125
Units:V
Range:[0, 80]
Modbus address:0x000A
preprocessing:
- type: MULTIPLIER
parameters:
- '0.003051757813'
- type: REGEX
parameters:
- '^(\d+)(\.\d{1,2})?'
- \1\2
tags:
- tag: component
value: load
- uuid: 91f2c1893b594e808032eb0140247d7a
name: 'Status: Alarms'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.52.0]'
key: 'status.alarms[alarms.0]'
history: 1h
value_type: TEXT
trends: '0'
description: |
MIB: SUNSAVER-MPPT
Description:Alarms
Modbus addresses:H=0x0023 L=0x0024
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
- type: JAVASCRIPT
parameters:
- |
var FIELDS = [
'rtsOpen',
'rtsShorted',
'rtsDisconnected',
'heatsinkTempSensorOpen',
'heatsinkTempSensorShorted',
'sspptHot',
'currentLimit',
'currentOffset',
'undefined',
'undefined1',
'uncalibrated',
'rtsMiswire',
'undefined12',
'undefined123',
'systemMiswire',
'mosfetSOpen',
'p12VoltageReferenceOff',
'highVaCurrentLimit',
];
var flags = parseInt(value.replace(/\x20/g, ''), 16),
result = [];
for (var i = 0, f = 1 << 31 >>> 0, l = FIELDS.length; i < l; i++, f >>>= 1) {
if (flags & f) {
result.push(FIELDS[i]);
}
}
return result.length ? result.join('\n') : 'No alarms';
tags:
- tag: component
value: status
triggers:
- uuid: 86220f6cc9164490b6d80be4a249e749
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.alarms[alarms.0],#3,"like","currentLimit")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "currentLimit" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 69016ea6a1204435b3ddb8de6b8944dc
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.alarms[alarms.0],#3,"like","currentOffset")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "currentOffset" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 2c02465ea74e4c63ab783d235c8f1a30
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.alarms[alarms.0],#3,"like","heatsinkTempSensorOpen")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "heatsinkTempSensorOpen" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 1aa289c68f0b4b44a043281e6df9e462
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.alarms[alarms.0],#3,"like","heatsinkTempSensorShorted")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "heatsinkTempSensorShorted" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 6d0ce7d6e2cc407ba0f4d989bdd9a141
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.alarms[alarms.0],#3,"like","highVaCurrentLimit")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "highVaCurrentLimit" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 718a3426363040e1ab82864635444056
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.alarms[alarms.0],#3,"like","mosfetSOpen")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "mosfetSOpen" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 4eb4df0b4cf04a198190312cdb33538f
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.alarms[alarms.0],#3,"like","p12VoltageReferenceOff")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "p12VoltageReferenceOff" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: e2ac890bb16d4e0798b0410f33c8a860
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.alarms[alarms.0],#3,"like","rtsDisconnected")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "rtsDisconnected" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 3b02b27bd4674ae3b820730cee8e611a
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.alarms[alarms.0],#3,"like","rtsMiswire")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "rtsMiswire" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: d253c037d5974ee38e888162687b96ef
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.alarms[alarms.0],#3,"like","rtsShorted")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "rtsShorted" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 1bea0c0e01314dbaa1cfdfa5a0625755
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.alarms[alarms.0],#3,"like","sspptHot")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "sspptHot" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: d28d0e51500a45859ccb6969d9b5493f
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.alarms[alarms.0],#3,"like","systemMiswire")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "systemMiswire" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: 427f75a98d4440a38e40522bccec03bb
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.alarms[alarms.0],#3,"like","uncalibrated")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "uncalibrated" alarm flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
tags:
- tag: scope
value: notice
- uuid: f44756455697466cb905aa6ae4d0220d
name: 'Status: Array Faults'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.40.0]'
key: 'status.array_faults[arrayFaults.0]'
history: 1h
value_type: TEXT
trends: '0'
description: |
MIB: SUNSAVER-MPPT
Description:Array Faults
Modbus address:0x0012
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
- type: JAVASCRIPT
parameters:
- |
var FIELDS = [
'overcurrent',
'mosfetSShorted',
'softwareFault',
'batteryHvd',
'arrayHvd',
'customSettingsEdit',
'rtsShorted',
'rtsNoLongerValid',
'localTempSensorDamaged',
];
var flags = parseInt(value.replace(/\x20/g, ''), 16),
result = [];
for (var i = 0, f = 1 << 31 >>> 0, l = FIELDS.length; i < l; i++, f >>>= 1) {
if (flags & f) {
result.push(FIELDS[i]);
}
}
return result.length ? result.join('\n') : 'No faults';
tags:
- tag: component
value: status
triggers:
- uuid: 2d8b0bdeb95c49d68771af384d985311
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","arrayHvd")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "arrayHvd" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 2e07c5d51691462ca0961d77ea974bd5
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","batteryHvd")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "batteryHvd" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 65d2cd1ff93f45db9d7f572ee0a8f568
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","customSettingsEdit")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "customSettingsEdit" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: fe217d10399044d7b1008f0010691e1e
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","localTempSensorDamaged")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "localTempSensorDamaged" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: fa62f9e4f0f84e278938ba18785a1b5f
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","mosfetSShorted")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "mosfetSShorted" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 6f450621a12e46369745b2a0fed018ac
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","overcurrent")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "overcurrent" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 7ea38daa41a94ab3a9c1efc34276b17b
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","rtsNoLongerValid")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "rtsNoLongerValid" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 91edc885c3f140cc85bb6085f06e6820
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","rtsShorted")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "rtsShorted" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: cae74543a0da478d80b9302a2431fe4b
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","softwareFault")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "softwareFault" array faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 76a660b88bb74e90971bdaec703d3c17
name: 'Status: Uptime (hardware)'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.25.1.1.0]'
key: status.hw.uptime
units: uptime
description: 'The amount of time since this host was last initialized. Note that this is different from sysUpTime in the SNMPv2-MIB [RFC1907] because sysUpTime is the uptime of the network management portion of the system.'
preprocessing:
- type: CHECK_NOT_SUPPORTED
parameters:
- '-1'
error_handler: CUSTOM_VALUE
error_handler_params: '0'
- type: MULTIPLIER
parameters:
- '0.01'
tags:
- tag: component
value: status
- uuid: 24762b0c264745548150a4bd5913156f
name: 'Status: Load Faults'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.47.0]'
key: 'status.load_faults[loadFaults.0]'
history: 1h
value_type: TEXT
trends: '0'
description: |
MIB: SUNSAVER-MPPT
Description:Array Faults
Modbus address:0x0012
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 1h
- type: JAVASCRIPT
parameters:
- |
var FIELDS = [
'externalShortCircuit',
'overcurrent',
'mosfetShorted',
'software',
'loadHvd',
'highTempDisconnect',
'customSettingsEdit',
'unknownLoadFault'
];
var flags = parseInt(value.replace(/\x20/g, ''), 16),
result = [];
for (var i = 0, f = 1 << 31 >>> 0, l = FIELDS.length; i < l; i++, f >>>= 1) {
if (flags & f) {
result.push(FIELDS[i]);
}
}
return result.length ? result.join('\n') : 'No faults';
tags:
- tag: component
value: status
triggers:
- uuid: d086fbb093344723a4bb5fe928e984ff
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","customSettingsEdit")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "customSettingsEdit" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 5743ed062a954330928092fb8574002a
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","externalShortCircuit")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "externalShortCircuit" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 354a1512bca5468585a489dd14fc793d
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","highTempDisconnect")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "highTempDisconnect" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 3640e470580846ac9e1651cba186d0a3
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","loadHvd")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "loadHvd" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: d3911d64792e4b88b31cb51a405a1a2e
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","mosfetShorted")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "mosfetShorted" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: d1bfa4177c0844ec9fc2bc7270c09338
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","overcurrent")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "overcurrent" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: baaba919b58546f08cdcd1e2791feb27
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","software")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "software" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 41e47074c983421a83b1e500d4591188
expression: 'count(/Morningstar SunSaver MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","unknownLoadFault")=2'
name: 'Morningstar SunSaver MPPT: Status: Device has "unknownLoadFault" load faults flag'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 63512390f2a04885bf8d0e19653a72b1
name: 'Status: Uptime (network)'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.3.0]'
key: status.net.uptime
units: uptime
description: 'The time (in hundredths of a second) since the network management portion of the system was last re-initialized.'
preprocessing:
- type: MULTIPLIER
parameters:
- '0.01'
tags:
- tag: component
value: status
triggers:
- uuid: 72e6e08faed647a98a027bd25b6a7106
expression: 'nodata(/Morningstar SunSaver MPPT by SNMP/status.net.uptime,5m)=1'
name: 'Morningstar SunSaver MPPT: Status: Failed to fetch data'
event_name: 'Morningstar SunSaver MPPT: Status: Failed to fetch data (or no data for 5m)'
priority: WARNING
description: 'Zabbix has not received data for items for the last 5 minutes.'
manual_close: 'YES'
tags:
- tag: scope
value: availability
- uuid: 52afa576b83b49e69ec8d379fbc42965
name: 'Battery: Target Voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.42.0]'
key: 'target.voltage[targetVoltage.0]'
value_type: FLOAT
units: V
description: |
MIB: SUNSAVER-MPPT
Description:Target Regulation Voltage
Scaling Factor:0.0030517578125
Units:V
Range:[0.0, 80.0]
Modbus address:0x0014
preprocessing:
- type: MULTIPLIER
parameters:
- '0.003051757813'
- type: REGEX
parameters:
- '^(\d+)(\.\d{1,2})?'
- \1\2
tags:
- tag: component
value: battery
- uuid: 430cf6fcb9b74943a8ca7f1d9d06fa56
name: 'Temperature: Ambient'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.37.0]'
key: 'temp.ambient[ambientTemperature.0]'
value_type: FLOAT
units: C
description: |
MIB: SUNSAVER-MPPT
Description:Ambient Temperature
Scaling Factor:1.0
Units:deg C
Range:[-128, 127]
Modbus address:0x000F
tags:
- tag: component
value: temperature
- uuid: 157faa85ae244950b4a114b95bad6d50
name: 'Temperature: Battery'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.36.0]'
key: 'temp.battery[batteryTemperature.0]'
value_type: FLOAT
units: C
description: |
MIB: SUNSAVER-MPPT
Description:Heatsink Temperature
Scaling Factor:1.0
Units:deg C
Range:[-128, 127]
Modbus address:0x000D
tags:
- tag: component
value: temperature
triggers:
- uuid: cc121c44be05440a82d3344c530456e5
expression: 'min(/Morningstar SunSaver MPPT by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.CRIT}'
name: 'Morningstar SunSaver MPPT: Temperature: Critically high battery temperature'
event_name: 'Morningstar SunSaver MPPT: Temperature: Critically high battery temperature (over {$BATTERY.TEMP.MAX.CRIT}C for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 9e0d552b93ae402d98c327420c99d160
expression: 'max(/Morningstar SunSaver MPPT by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.CRIT}'
name: 'Morningstar SunSaver MPPT: Temperature: Critically low battery temperature'
event_name: 'Morningstar SunSaver MPPT: Temperature: Critically low battery temperature (below {$BATTERY.TEMP.MIN.WARN}C for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 95b600e280b94949b41422eb60def010
expression: 'min(/Morningstar SunSaver MPPT by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.WARN}'
name: 'Morningstar SunSaver MPPT: Temperature: High battery temperature'
event_name: 'Morningstar SunSaver MPPT: Temperature: High battery temperature (over {$BATTERY.TEMP.MAX.WARN}C for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar SunSaver MPPT: Temperature: Critically high battery temperature'
expression: 'min(/Morningstar SunSaver MPPT by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.CRIT}'
tags:
- tag: scope
value: notice
- uuid: e351922a0a8c4c53972d9477d47af528
expression: 'max(/Morningstar SunSaver MPPT by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.WARN}'
name: 'Morningstar SunSaver MPPT: Temperature: Low battery temperature'
event_name: 'Morningstar SunSaver MPPT: Temperature: Low battery temperature (below {$BATTERY.TEMP.MIN.WARN}C for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar SunSaver MPPT: Temperature: Critically low battery temperature'
expression: 'max(/Morningstar SunSaver MPPT by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.CRIT}'
tags:
- tag: scope
value: notice
- uuid: 5f238fe557a7412cad5f3864e407284e
name: 'Temperature: Heatsink'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.35.0]'
key: 'temp.heatsink[heatsinkTemperature.0]'
value_type: FLOAT
units: C
description: |
MIB: SUNSAVER-MPPT
Description:Battery Temperature
Scaling Factor:1.0
Units:deg C
Range:[-128, 127]
Modbus address:0x000E
tags:
- tag: component
value: temperature
discovery_rules:
- uuid: 81b324d81e6549d59cbf14163181fb48
name: 'Battery voltage discovery'
type: DEPENDENT
key: battery.voltage.discovery
delay: '0'
description: 'Discovery for battery voltage triggers'
item_prototypes:
- uuid: 903b96b7eb37482da469fc802d3da1b0
name: 'Battery: Voltage{#SINGLETON}'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.33333.3.30.0]'
key: 'battery.voltage[batteryVoltage.0{#SINGLETON}]'
value_type: FLOAT
units: V
description: |
MIB: SUNSAVER-MPPT
Description:Control State
Modbus address:0x0011
preprocessing:
- type: MULTIPLIER
parameters:
- '0.003051757813'
- type: REGEX
parameters:
- '^(\d+)(\.\d{1,2})?'
- \1\2
tags:
- tag: component
value: battery
trigger_prototypes:
- uuid: bf4ad2cee8cf41baafa3d81df5fbe4d3
expression: 'min(/Morningstar SunSaver MPPT by SNMP/battery.voltage[batteryVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.CRIT}'
name: 'Morningstar SunSaver MPPT: Battery: Critically high battery voltage'
event_name: 'Morningstar SunSaver MPPT: Battery: Critically high battery voltage (over {#VOLTAGE.MAX.CRIT}V for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: capacity
- uuid: 2aedfef9b8764881a4768e6b32793820
expression: 'max(/Morningstar SunSaver MPPT by SNMP/battery.voltage[batteryVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.CRIT}'
name: 'Morningstar SunSaver MPPT: Battery: Critically low battery voltage'
event_name: 'Morningstar SunSaver MPPT: Battery: Critically low battery voltage (below {#VOLTAGE.MIN.CRIT}V for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: capacity
- uuid: bec4c7a6a1ab44a4adc8e4286b9a41d9
expression: 'min(/Morningstar SunSaver MPPT by SNMP/battery.voltage[batteryVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.WARN}'
name: 'Morningstar SunSaver MPPT: Battery: High battery voltage'
event_name: 'Morningstar SunSaver MPPT: Battery: High battery voltage (over {#VOLTAGE.MAX.WARN}V for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar SunSaver MPPT: Battery: Critically high battery voltage'
expression: 'min(/Morningstar SunSaver MPPT by SNMP/battery.voltage[batteryVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.CRIT}'
tags:
- tag: scope
value: capacity
- uuid: c06425d8a0a24b5f80fd0591be61b3f0
expression: 'max(/Morningstar SunSaver MPPT by SNMP/battery.voltage[batteryVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.WARN}'
name: 'Morningstar SunSaver MPPT: Battery: Low battery voltage'
event_name: 'Morningstar SunSaver MPPT: Battery: Low battery voltage (below {#VOLTAGE.MIN.WARN}V for 5m)'
opdata: 'Current value: {ITEM.LASTVALUE1}'
priority: WARNING
dependencies:
- name: 'Morningstar SunSaver MPPT: Battery: Critically low battery voltage'
expression: 'max(/Morningstar SunSaver MPPT by SNMP/battery.voltage[batteryVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.CRIT}'
tags:
- tag: scope
value: capacity
graph_prototypes:
- uuid: b3520796c85a45df954633bc5f87d80b
name: 'Voltage: Battery/Load{#SINGLETON}'
graph_items:
- drawtype: GRADIENT_LINE
color: 199C0D
item:
host: 'Morningstar SunSaver MPPT by SNMP'
key: 'battery.voltage[batteryVoltage.0{#SINGLETON}]'
- sortorder: '1'
drawtype: GRADIENT_LINE
color: F63100
item:
host: 'Morningstar SunSaver MPPT by SNMP'
key: 'load.voltage[loadVoltage.0]'
master_item:
key: 'battery.voltage.discovery[batteryVoltage.0]'
preprocessing:
- type: JAVASCRIPT
parameters:
- |
var v_range = [
[[0, 18], [12, 15, 11.5, 15.5]],
[[18, 36], [24, 30, 23, 31]],
[[36, 99], [48, 60, 46, 62]],
],
result = [];
for (var idx in v_range) {
if (v_range[idx][0][0] < value && value <= v_range[idx][0][1]) {
result = [{
'{#VOLTAGE.MIN.WARN}': parseInt({$VOLTAGE.MIN.WARN}) || v_range[idx][1][0],
'{#VOLTAGE.MAX.WARN}': parseInt({$VOLTAGE.MAX.WARN}) || v_range[idx][1][1],
'{#VOLTAGE.MIN.CRIT}': parseInt({$VOLTAGE.MIN.CRIT}) || v_range[idx][1][2],
'{#VOLTAGE.MAX.CRIT}': parseInt({$VOLTAGE.MAX.CRIT}) || v_range[idx][1][3],
'{#SINGLETON}': ''
}];
break;
}
}
return JSON.stringify(result);
tags:
- tag: class
value: power
- tag: target
value: morningstar
macros:
- macro: '{$BATTERY.TEMP.MAX.CRIT}'
value: '60'
description: 'Battery high temperature critical value'
- macro: '{$BATTERY.TEMP.MAX.WARN}'
value: '45'
description: 'Battery high temperature warning value'
- macro: '{$BATTERY.TEMP.MIN.CRIT}'
value: '-20'
description: 'Battery low temperature critical value'
- macro: '{$BATTERY.TEMP.MIN.WARN}'
value: '0'
description: 'Battery low temperature warning value'
- macro: '{$CHARGE.STATE.CRIT}'
value: '4'
description: fault
- macro: '{$CHARGE.STATE.WARN}'
value: '2'
description: disconnect
- macro: '{$LOAD.STATE.CRIT:"fault"}'
value: '4'
description: fault
- macro: '{$LOAD.STATE.CRIT:"lvd"}'
value: '3'
description: lvd
- macro: '{$LOAD.STATE.WARN:"disconnect"}'
value: '5'
description: disconnect
- macro: '{$LOAD.STATE.WARN:"lvdWarning"}'
value: '2'
description: lvdWarning
- macro: '{$LOAD.STATE.WARN:"override"}'
value: '7'
description: override
- macro: '{$VOLTAGE.MAX.CRIT}'
- macro: '{$VOLTAGE.MAX.WARN}'
- macro: '{$VOLTAGE.MIN.CRIT}'
- macro: '{$VOLTAGE.MIN.WARN}'
dashboards:
- uuid: 154e1f8f24fc4a3080e003a5bdd81ff8
name: 'Morningstar SunSaver MPPT: Overview'
pages:
- widgets:
- type: graph
width: '72'
height: '4'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'Morningstar SunSaver MPPT by SNMP'
name: 'Array: Voltage'
- type: STRING
name: reference
value: AAAAA
- type: graph
'y': '4'
width: '72'
height: '4'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'Morningstar SunSaver MPPT by SNMP'
name: 'Current: Charge/Load'
- type: STRING
name: reference
value: AAAAB
- type: graph
'y': '8'
width: '72'
height: '4'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'Morningstar SunSaver MPPT by SNMP'
name: 'Temperature: Ambient/Battery/Heatsink'
- type: STRING
name: reference
value: AAAAC
valuemaps:
- uuid: b51b9440e801481fbb76f28b4a5431d1
name: 'SunSaver MPPT charge state'
mappings:
- value: '0'
newvalue: Start
- value: '1'
newvalue: NightCheck
- value: '2'
newvalue: Disconnect
- value: '3'
newvalue: Night
- value: '4'
newvalue: Fault
- value: '5'
newvalue: BulkMppt
- value: '6'
newvalue: Pwm
- value: '7'
newvalue: Float
- value: '8'
newvalue: Equalize
- uuid: f21076ed51104b84ba4d78dd74bd1a5b
name: 'SunSaver MPPT load state'
mappings:
- value: '0'
newvalue: Start
- value: '1'
newvalue: Normal
- value: '2'
newvalue: LvdWarning
- value: '3'
newvalue: Lvd
- value: '4'
newvalue: Fault
- value: '5'
newvalue: Disconnect
- value: '6'
newvalue: NormalOff
- value: '7'
newvalue: Override
- value: '8'
newvalue: NotUsed
triggers:
- uuid: fd5dcb256d4547da9c432c1b9c01b0ae
expression: '(last(/Morningstar SunSaver MPPT by SNMP/status.hw.uptime)>0 and last(/Morningstar SunSaver MPPT by SNMP/status.hw.uptime)<10m) or (last(/Morningstar SunSaver MPPT by SNMP/status.hw.uptime)=0 and last(/Morningstar SunSaver MPPT by SNMP/status.net.uptime)<10m)'
name: 'Morningstar SunSaver MPPT: Status: Device has been restarted'
event_name: 'Morningstar SunSaver MPPT: Status: Device has been restarted (uptime < 10m)'
priority: INFO
description: 'Uptime is less than 10 minutes.'
manual_close: 'YES'
tags:
- tag: scope
value: notice
graphs:
- uuid: 6090c266226d431193b00fb3db49ae07
name: 'Array: Voltage'
graph_items:
- drawtype: GRADIENT_LINE
color: 199C0D
item:
host: 'Morningstar SunSaver MPPT by SNMP'
key: 'array.sweep_vmp[arrayVmp.0]'
- sortorder: '1'
drawtype: GRADIENT_LINE
color: F63100
item:
host: 'Morningstar SunSaver MPPT by SNMP'
key: 'array.sweep_voc[arrayVoc.0]'
- sortorder: '2'
drawtype: GRADIENT_LINE
color: 00611C
item:
host: 'Morningstar SunSaver MPPT by SNMP'
key: 'array.voltage[arrayVoltage.0]'
- uuid: ad5b73c7352747a6930c9d8647f70bf1
name: 'Current: Charge/Load'
graph_items:
- drawtype: GRADIENT_LINE
color: 199C0D
item:
host: 'Morningstar SunSaver MPPT by SNMP'
key: 'charge.current[chargeCurrent.0]'
- sortorder: '1'
drawtype: GRADIENT_LINE
color: F63100
item:
host: 'Morningstar SunSaver MPPT by SNMP'
key: 'load.current[loadCurrent.0]'
- uuid: 7b96265600a748728d881f5dfee485d2
name: 'Temperature: Ambient/Battery/Heatsink'
graph_items:
- drawtype: GRADIENT_LINE
color: 199C0D
item:
host: 'Morningstar SunSaver MPPT by SNMP'
key: 'temp.ambient[ambientTemperature.0]'
- sortorder: '1'
drawtype: GRADIENT_LINE
color: F63100
item:
host: 'Morningstar SunSaver MPPT by SNMP'
key: 'temp.battery[batteryTemperature.0]'
- sortorder: '2'
drawtype: GRADIENT_LINE
color: 00611C
item:
host: 'Morningstar SunSaver MPPT by SNMP'
key: 'temp.heatsink[heatsinkTemperature.0]'