templates-default/APC_UPS_Symmetra_LX_by_SNMP.yaml
T

1556 lines
67 KiB
YAML

zabbix_export:
version: '7.0'
template_groups:
- uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
name: Templates/Power
templates:
- uuid: 0b9a899ff8f1467c9fdf999d02b9fd77
template: 'APC UPS Symmetra LX by SNMP'
name: 'APC UPS Symmetra LX by SNMP'
description: |
Template Power APC UPS Symmetra LX
MIBs used:
HOST-RESOURCES-MIB
PowerNet-MIB
SNMPv2-MIB
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
Generated by official Zabbix template tool "Templator"
vendor:
name: Zabbix
version: 7.0-4
groups:
- name: Templates/Power
items:
- uuid: 560d838206844447b8f79fd4500557b2
name: 'Battery capacity'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.1.0]'
key: 'battery.capacity[upsHighPrecBatteryCapacity]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The remaining battery capacity expressed as
percentage of full capacity.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: fdece80f2fc44ac1974fafe190ce186f
expression: 'last(/APC UPS Symmetra LX by SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}'
name: 'APC UPS Symmetra: Battery has low capacity'
event_name: 'APC UPS Symmetra: Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%)'
opdata: 'Current capacity: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: capacity
- uuid: 3fea9d328d5342b5bae6b643a0b45495
name: 'External battery packs count'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.5.0]'
key: 'battery.external_packs_count[upsAdvBatteryNumOfBattPacks]'
delay: 1h
description: |
MIB: PowerNet-MIB
The number of external battery packs connected to the UPS. If
the UPS does not use smart cells then the agent reports
ERROR_NO_SUCH_NAME.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: f4bd3a4a637640e29f50ebd36fb510e5
name: 'Battery last replace date'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.1.3.0]'
key: 'battery.last_replace_date[upsBasicBatteryLastReplaceDate]'
delay: 1h
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The date when the UPS system's batteries were last replaced
in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value
is originally set at the factory. When the UPS batteries
are replaced, this value should be reset by the administrator.
For Symmetra PX 250/500 this OID is read-only and is configurable in the local display only.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: 731d350450f742d880d81ff2be69e67e
name: 'Battery replace indicator'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.4.0]'
key: 'battery.replace_indicator[upsAdvBatteryReplaceIndicator]'
description: |
MIB: PowerNet-MIB
Indicates whether the UPS batteries need replacement.
valuemap:
name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: a1bd434a249b48b2ac0ef69ede417a72
expression: 'last(/APC UPS Symmetra LX by SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2'
name: 'APC UPS Symmetra: Battery needs replacement'
priority: HIGH
description: 'A battery installed has an internal error condition.'
tags:
- tag: scope
value: notice
- uuid: 8340b775b76f4e8aad6d3984c63632e9
name: 'Battery runtime remaining'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.3.0]'
key: 'battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]'
value_type: FLOAT
units: s
description: |
MIB: PowerNet-MIB
The UPS battery run time remaining before battery
exhaustion.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.01'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: c1d818ee115343c8bb41bedb8de7f2bd
name: 'Battery status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.1.1.0]'
key: 'battery.status[upsBasicBatteryStatus]'
description: |
MIB: PowerNet-MIB
The status of the UPS batteries. A batteryLow(3) value
indicates the UPS will be unable to sustain the current
load, and its services will be lost if power is not restored.
The amount of run time in reserve at the time of low battery
can be configured by the upsAdvConfigLowBatteryRunTime.
A batteryInFaultCondition(4)value indicates that a battery
installed has an internal error condition.
valuemap:
name: 'PowerNet-MIB::upsBasicBatteryStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
triggers:
- uuid: 955d79a0cf5447dd9a11d4608758e983
expression: 'last(/APC UPS Symmetra LX by SNMP/battery.status[upsBasicBatteryStatus])=4'
name: 'APC UPS Symmetra: Battery has an internal error condition'
priority: AVERAGE
description: 'A battery installed has an internal error condition.'
tags:
- tag: scope
value: notice
- uuid: 3ca8156ecc1c4ee4b5623c4a085b993f
expression: 'last(/APC UPS Symmetra LX by SNMP/battery.status[upsBasicBatteryStatus])=3'
name: 'APC UPS Symmetra: Battery is Low'
priority: AVERAGE
description: 'The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.'
tags:
- tag: scope
value: capacity
- uuid: 6d581eae836342bb8280eb09d7894533
name: 'Battery temperature'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.2.0]'
key: 'battery.temperature[upsHighPrecBatteryTemperature]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The current internal UPS temperature in Celsius.
Temperatures below zero read as 0.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: temperature
triggers:
- uuid: 5b43659a10644a51861282bc72116f9f
expression: 'min(/APC UPS Symmetra LX by SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
name: 'APC UPS Symmetra: Battery has high temperature'
event_name: 'APC UPS Symmetra: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})'
opdata: 'Current temperature: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: ab0f5d86a40b421ba136506f7854bbbd
name: 'Battery voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.4.0]'
key: 'battery.voltage[upsHighPrecBatteryActualVoltage]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The actual battery bus voltage in Volts.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 13c0d202d19f4b64a52141062c4be6bb
name: 'Input fail cause'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.3.2.5.0]'
key: 'input.fail[upsAdvInputLineFailCause]'
description: |
MIB: PowerNet-MIB
The reason for the occurrence of the last transfer to UPS
battery power. The variable is set to:
- noTransfer(1) -- if there is no transfer yet.
- highLineVoltage(2) -- if the transfer to battery is caused
by an over voltage greater than the high transfer voltage.
- brownout(3) -- if the duration of the outage is greater than
five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- blackout(4) -- if the duration of the outage is greater than five
seconds and the line voltage is between 40% of the rated
output voltage and ground.
- smallMomentarySag(5) -- if the duration of the outage is less
than five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- deepMomentarySag(6) -- if the duration of the outage is less
than five seconds and the line voltage is between 40% of the
rated output voltage and ground. The variable is set to
- smallMomentarySpike(7) -- if the line failure is caused by a
rate of change of input voltage less than ten volts per cycle.
- largeMomentarySpike(8) -- if the line failure is caused by
a rate of change of input voltage greater than ten volts per cycle.
- selfTest(9) -- if the UPS was commanded to do a self test.
- rateOfVoltageChange(10) -- if the failure is due to the rate of change of
the line voltage.
valuemap:
name: 'PowerNet-MIB::upsAdvInputLineFailCause'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 05ccf5bd85414ee9b5860c80f6e8323f
name: 'Input frequency'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.3.3.4.0]'
key: 'input.frequency[upsHighPrecInputFrequency]'
value_type: FLOAT
units: Hz
description: |
MIB: PowerNet-MIB
The current input frequency to the UPS system in Hz.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: 94a5c26b89e2416f96b61bbfc6e60a97
expression: 'min(/APC UPS Symmetra LX by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra LX by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Symmetra LX by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})'
name: 'APC UPS Symmetra: Unacceptable input frequency'
event_name: 'APC UPS Symmetra: Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD})'
opdata: 'Current frequency: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 5764182c547143b3b044ec1adb54c1ce
name: 'Input voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.3.3.1.0]'
key: 'input.voltage[upsHighPrecInputLineVoltage]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The current utility line voltage in VAC.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: 2b640b94d48446609802ce6e57c7bd46
expression: 'min(/APC UPS Symmetra LX by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra LX by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra LX by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})'
name: 'APC UPS Symmetra: Unacceptable input voltage'
event_name: 'APC UPS Symmetra: Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current voltage: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: bbb33508be95488680bcb644a44626ef
name: 'Output current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.3.4.0]'
key: 'output.current[upsHighPrecOutputCurrent]'
value_type: FLOAT
units: A
description: |
MIB: PowerNet-MIB
The current in amperes drawn by the load on the UPS.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: d27e991fc0f64b4f9704fb8183567e8d
name: 'Output load'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.3.3.0]'
key: 'output.load[upsHighPrecOutputLoad]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The current UPS load expressed as percentage
of rated capacity.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: 34562b5c734d492c89c386902dfd6e90
expression: 'min(/APC UPS Symmetra LX by SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}'
name: 'APC UPS Symmetra: Output load is high'
event_name: 'APC UPS Symmetra: Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD})'
opdata: 'Current load: {ITEM.LASTVALUE1}'
priority: HIGH
description: 'A battery installed has an internal error condition.'
tags:
- tag: scope
value: notice
- uuid: 978a7ee6923c40cd8097afb60c81244f
name: 'Output status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.1.1.0]'
key: 'output.status[upsBasicOutputStatus]'
description: |
MIB: PowerNet-MIB
The current state of the UPS. If the UPS is unable to
determine the state of the UPS this variable is set
to unknown(1).
During self-test most UPSes report onBattery(3) but
some that support it will report onBatteryTest(15).
To determine self-test status across all UPSes, refer
to the upsBasicStateOutputState OID.
valuemap:
name: 'PowerNet-MIB::upsBasicOutputStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
triggers:
- uuid: 6ade2b9fb9ad432596d16b3df6237ec4
expression: 'last(/APC UPS Symmetra LX by SNMP/output.status[upsBasicOutputStatus])=16'
name: 'APC UPS Symmetra: UPS is Emergency Static Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: da9a0fa7669e454b8ba44c0458a94ea8
expression: 'last(/APC UPS Symmetra LX by SNMP/output.status[upsBasicOutputStatus])=10'
name: 'APC UPS Symmetra: UPS is Hardware Failure Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 01a2bcb5f20b4fe889a48e4bed2a2a63
expression: 'last(/APC UPS Symmetra LX by SNMP/output.status[upsBasicOutputStatus])=7'
name: 'APC UPS Symmetra: UPS is Off'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: d0b154dd92424af8bb841d91d4e7ddd5
expression: 'last(/APC UPS Symmetra LX by SNMP/output.status[upsBasicOutputStatus])=3'
name: 'APC UPS Symmetra: UPS is on battery'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: afc071d0ccfb4226a3c5ee3058270937
expression: 'last(/APC UPS Symmetra LX by SNMP/output.status[upsBasicOutputStatus])=4'
name: 'APC UPS Symmetra: UPS is on Smart Boost'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 12259f4a961a40b39de12d0202d41c56
expression: 'last(/APC UPS Symmetra LX by SNMP/output.status[upsBasicOutputStatus])=12'
name: 'APC UPS Symmetra: UPS is On Smart Trim'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: ef9d1e4b1ec244f6bcf36d19a9e7c9c7
expression: 'last(/APC UPS Symmetra LX by SNMP/output.status[upsBasicOutputStatus])=8'
name: 'APC UPS Symmetra: UPS is Rebooting'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: c673928e7b764b5db0fa3168edd2cc67
expression: 'last(/APC UPS Symmetra LX by SNMP/output.status[upsBasicOutputStatus])=11'
name: 'APC UPS Symmetra: UPS is Sleeping Until Power Return'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: c9b24aa16e124d8c9cd6cfb188ded816
expression: 'last(/APC UPS Symmetra LX by SNMP/output.status[upsBasicOutputStatus])=6'
name: 'APC UPS Symmetra: UPS is Software Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 02904426801d4d42b3f634267f8697e7
expression: 'last(/APC UPS Symmetra LX by SNMP/output.status[upsBasicOutputStatus])=9'
name: 'APC UPS Symmetra: UPS is Switched Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: fa08f8a60c2c4d88a3f9ebf317fcd06e
expression: 'last(/APC UPS Symmetra LX by SNMP/output.status[upsBasicOutputStatus])=5'
name: 'APC UPS Symmetra: UPS is Timed Sleeping'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 9cf495d14fdf4059b6c35e7857d7a18c
name: 'Output voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.3.1.0]'
key: 'output.voltage[upsHighPrecOutputVoltage]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The output voltage of the UPS system in VAC.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 102179b315b548e289df3459bc5860c1
name: 'SNMP traps (fallback)'
type: SNMP_TRAP
key: snmptrap.fallback
delay: '0'
value_type: LOG
trends: '0'
description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items'
logtimefmt: 'hh:mm:sszyyyy/MM/dd'
tags:
- tag: component
value: network
- uuid: 8dd800fbbcde431aa421eeb5a33eb798
name: 'System contact details'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.4.0]'
key: 'system.contact[sysContact.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
The textual identification of the contact person for this managed
node, together with information on how to contact this person. If no contact
information is known, the value is the zero-length string.
inventory_link: CONTACT
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 12h
tags:
- tag: component
value: system
- uuid: e8c576f27f4c49ef9acd1ba7198ffbb6
name: 'System description'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.1.0]'
key: 'system.descr[sysDescr.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
A textual description of the entity. This value should
include the full name and version identification of the system's hardware type, software operating-system, and
networking software.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 12h
tags:
- tag: component
value: system
- uuid: e5a92d45430b4bd6bdef42870141d141
name: 'Uptime (hardware)'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.25.1.1.0]'
key: 'system.hw.uptime[hrSystemUptime.0]'
delay: 30s
trends: '0'
units: uptime
description: |
MIB: HOST-RESOURCES-MIB
The amount of time since this host was last initialized. Note that this is different from sysUpTime in the SNMPv2-MIB [RFC1907] because sysUpTime is the uptime of the network management portion of the system.
preprocessing:
- type: CHECK_NOT_SUPPORTED
parameters:
- '-1'
error_handler: CUSTOM_VALUE
error_handler_params: '0'
- type: MULTIPLIER
parameters:
- '0.01'
tags:
- tag: component
value: system
- uuid: 6a06715ef4c44534a0ebc45f4e5adb5b
name: 'System location'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.6.0]'
key: 'system.location[sysLocation.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
The physical location of this node (e.g., `telephone closet, 3rd floor'). If the location is unknown, the value is the zero-length string.
inventory_link: LOCATION
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: system
- uuid: 64d56d199021432886452fff5a4c6d22
name: Model
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.1.1.1.0]'
key: 'system.model[upsBasicIdentModel]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The UPS model name (e.g. 'APC Smart-UPS 600').
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: b15628c68d4c4e8ca761ad9fa7e40a1c
name: 'System name'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.5.0]'
key: 'system.name[sysName.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
An administratively-assigned name for this managed node.By convention, this is the node's fully-qualified domain name. If the name is unknown, the value is the zero-length string.
inventory_link: NAME
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: system
triggers:
- uuid: 61d0836efd33437894e1edd595373f1e
expression: 'last(/APC UPS Symmetra LX by SNMP/system.name[sysName.0],#1)<>last(/APC UPS Symmetra LX by SNMP/system.name[sysName.0],#2) and length(last(/APC UPS Symmetra LX by SNMP/system.name[sysName.0]))>0'
name: 'APC UPS Symmetra: System name has changed'
event_name: 'APC UPS Symmetra: System name has changed (new name: {ITEM.VALUE})'
priority: INFO
description: 'The name of the system has changed. Acknowledge to close the problem manually.'
manual_close: 'YES'
tags:
- tag: scope
value: notice
- tag: scope
value: security
- uuid: 0810681a8ae74ad8b28ea38119a93f59
name: 'Uptime (network)'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.3.0]'
key: 'system.net.uptime[sysUpTime.0]'
delay: 30s
trends: '0'
units: uptime
description: |
MIB: SNMPv2-MIB
The time (in hundredths of a second) since the network management portion of the system was last re-initialized.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.01'
tags:
- tag: component
value: system
- uuid: 9f858f7eaed545b8a35ac24e858b0826
name: 'System object ID'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.2.0]'
key: 'system.objectid[sysObjectID.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
The vendor's authoritative identification of the network management subsystem contained in the entity. This value is allocated within the SMI enterprises subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1 to its `Fred Router'.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: system
- uuid: 3f61bd561e7d42fbb55b71df9ea3b5b1
name: 'Serial number'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.1.2.3.0]'
key: 'system.sn[upsAdvIdentSerialNumber]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
An 8-character string identifying the serial number of
the UPS internal microprocessor. This number is set at
the factory. NOTE: This number does NOT correspond to
the serial number on the rear of the UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: 9562f60b1cbd4fe08614221e69efd811
name: 'SNMP agent availability'
type: INTERNAL
key: 'zabbix[host,snmp,available]'
description: |
Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.
Possible values:
0 - not available
1 - available
2 - unknown
valuemap:
name: zabbix.host.available
tags:
- tag: component
value: health
- tag: component
value: network
triggers:
- uuid: aeaaa7e2bd2d46a481f9d8b33ec18cb5
expression: 'max(/APC UPS Symmetra LX by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
name: 'APC UPS Symmetra: No SNMP data collection'
opdata: 'Current state: {ITEM.LASTVALUE1}'
priority: WARNING
description: 'SNMP is not available for polling. Please check device connectivity and SNMP settings.'
tags:
- tag: scope
value: availability
discovery_rules:
- uuid: 35a885d8f181416db86f2ffe73a30f7f
name: 'External bad battery packs discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#EXTERNAL_PACKS},1.3.6.1.4.1.318.1.1.1.2.2.6]'
key: battery.packs.bad.discovery
delay: 1h
filter:
evaltype: AND
conditions:
- macro: '{#EXTERNAL_PACKS}'
value: '-1'
operator: NOT_MATCHES_REGEX
formulaid: A
description: 'Discovery of the number of external defective battery packs.'
item_prototypes:
- uuid: b0b3bb219c534b40ad07f89ac8c43797
name: '{#SNMPINDEX}: External battery packs bad'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.6.0]'
key: 'battery.external_packs_bad[upsAdvBatteryNumOfBadBattPacks.{#SNMPINDEX}]'
delay: 15m
description: |
MIB: PowerNet-MIB
The number of external battery packs connected to the UPS that
are defective. If the UPS does not use smart cells then the
agent reports ERROR_NO_SUCH_NAME.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: 168bfbfc58ca46509caf54ae3562f0bc
name: 'External battery packs discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#CARTRIDGE_STATUS},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7,{#BATTERY_PACK},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1,{#CARTRIDGE_INDEX},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2]'
key: battery.packs.discovery
delay: 1h
filter:
evaltype: AND
conditions:
- macro: '{#CARTRIDGE_STATUS}'
value: ^$
operator: NOT_MATCHES_REGEX
formulaid: A
item_prototypes:
- uuid: 3d2e62971cfb4b0a92b51ece740e1a58
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery estimated replace date'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8.{#SNMPINDEX}]'
key: 'battery.estimated_replace_date[upsHighPrecBatteryPackCartridgeReplaceDate.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
delay: 1h
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The battery cartridge estimated battery replace date.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- tag: component
value: power
- uuid: b49b4836472f45e3b4947048dcd64cf8
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7.{#SNMPINDEX}]'
key: 'battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The battery cartridge health.
bit 0 Battery lifetime okay
bit 1 Battery lifetime near end, order replacement cartridge
bit 2 Battery lifetime exceeded, replace battery
bit 3 Battery lifetime near end acknowledged, order replacement cartridge
bit 4 Battery lifetime exceeded acknowledged, replace battery
bit 5 Battery measured lifetime near end, order replacement cartridge
bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: 2ea1a8d2bd3746dabafed72e1f6216fd
expression: 'find(/APC UPS Symmetra LX by SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1'
name: 'APC UPS Symmetra: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay'
opdata: 'Current bit set: {ITEM.LASTVALUE1}'
priority: WARNING
description: |
The battery cartridge health.
bit 0 Battery lifetime okay
bit 1 Battery lifetime near end, order replacement cartridge
bit 2 Battery lifetime exceeded, replace battery
bit 3 Battery lifetime near end acknowledged, order replacement cartridge
bit 4 Battery lifetime exceeded acknowledged, replace battery
bit 5 Battery measured lifetime near end, order replacement cartridge
bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge
tags:
- tag: scope
value: notice
- uuid: df73a5fd0d964c67857178a936c2dc7d
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10.{#SNMPINDEX}]'
key: 'battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The status of the UPS batteries. A batteryLow(3) value
indicates the UPS will be unable to sustain the current
load, and its services will be lost if power is not restored.
The amount of run time in reserve at the time of low battery
can be configured by the upsAdvConfigLowBatteryRunTime.
A batteryInFaultCondition(4)value indicates that a battery
installed has an internal error condition.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: 3870634ad8c1414dabeebc10c510fba3
expression: 'find(/APC UPS Symmetra LX by SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0'
name: 'APC UPS Symmetra: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay'
opdata: 'Current bit set: {ITEM.LASTVALUE1}'
priority: WARNING
description: |
The battery cartridge status:
bit 0 Disconnected
bit 1 Overvoltage
bit 2 NeedsReplacement
bit 3 OvertemperatureCritical
bit 4 Charger
bit 5 TemperatureSensor
bit 6 BusSoftStart
bit 7 OvertemperatureWarning
bit 8 GeneralError
bit 9 Communication
bit 10 DisconnectedFrame
bit 11 FirmwareMismatch
tags:
- tag: scope
value: notice
- uuid: 18c46e7d50ee4eefb669705d62e2224c
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperature'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5.{#SNMPINDEX}]'
key: 'battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The current internal UPS temperature in Celsius.
Temperatures below zero read as 0.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: temperature
trigger_prototypes:
- uuid: 730bdb68d90f4bc6aaf6cb22e04e1845
expression: 'min(/APC UPS Symmetra LX by SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
name: 'APC UPS Symmetra: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature'
event_name: 'APC UPS Symmetra: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})'
opdata: 'Current temperature: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 5fadf217f7444f58ba3dca52bc6cff76
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4.{#SNMPINDEX}]'
key: 'system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
An 8-character string identifying the serial number of
the UPS internal microprocessor. This number is set at
the factory. NOTE: This number does NOT correspond to
the serial number on the rear of the UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: 598521a7c59d425d9deb58c9829e344e
name: 'External sensor port 1 discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#EXTERNAL_SENSOR1_NAME},1.3.6.1.4.1.318.1.1.25.1.2.1.3]'
key: external.sensor1.discovery
delay: 1h
description: uioSensorStatusTable
item_prototypes:
- uuid: 2db30af657574f8f9390002f94b7e249
name: '{#EXTERNAL_SENSOR1_NAME}: Humidity sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.1.7.{#SNMPINDEX}]'
key: 'external.sensor.humidity[uioSensorStatusHumidity.1.{#SNMPINDEX}]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The sensor's current humidity reading - a relative humidity
percentage. -1 indicates an invalid reading due to either a
sensor that doesn't read humidity or lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: humidity
- tag: component
value: power
- uuid: 6182750c55f24110b076d95c2cdbd1fa
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.1.9.{#SNMPINDEX}]'
key: 'external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}]'
description: |
MIB: PowerNet-MIB
The alarm status of the sensor. Possible values:
uioNormal (1),
uioWarning (2),
uioCritical (3),
sensorStatusNotApplicable (4)
valuemap:
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: 97b4078788d244d0b501e9465c659ff7
expression: 'last(/APC UPS Symmetra LX by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3'
name: 'APC UPS Symmetra: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical'
priority: HIGH
description: 'The external sensor has returned a value greater than the critical threshold.'
tags:
- tag: scope
value: notice
- uuid: 86cd9908372045618672d6ff82bca705
expression: 'last(/APC UPS Symmetra LX by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4'
name: 'APC UPS Symmetra: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable'
priority: INFO
description: 'The external sensor does not work or is not connected.'
tags:
- tag: scope
value: notice
- uuid: 4ba13efc27da411785410109340b6a26
expression: 'last(/APC UPS Symmetra LX by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2'
name: 'APC UPS Symmetra: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning'
priority: AVERAGE
description: 'The external sensor has returned a value greater than the warning threshold.'
tags:
- tag: scope
value: notice
- uuid: fc394520f4964a86ac93e87da2fc541b
name: '{#EXTERNAL_SENSOR1_NAME}: Temperature sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.1.6.{#SNMPINDEX}]'
key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.1.{#SNMPINDEX}]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The sensor's current temperature reading in Celsius.
-1 indicates an invalid reading due to lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- tag: component
value: temperature
overrides:
- name: Temp
step: '1'
filter:
conditions:
- macro: '{#EXTERNAL_SENSOR1_NAME}'
value: Temp
formulaid: A
operations:
- operationobject: ITEM_PROTOTYPE
operator: LIKE
value: Humidity
discover: NO_DISCOVER
- uuid: 14e6acae826e4e87b68c04beee67a5cb
name: 'External sensor port 2 discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#EXTERNAL_SENSOR2_NAME},1.3.6.1.4.1.318.1.1.25.1.2.2.3]'
key: external.sensor2.discovery
delay: 1h
description: uioSensorStatusTable
item_prototypes:
- uuid: 5f5df15d6cc4455083f9fa6932d86656
name: '{#EXTERNAL_SENSOR2_NAME}: Humidity sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.2.7.{#SNMPINDEX}]'
key: 'external.sensor.humidity[uioSensorStatusHumidity.2.{#SNMPINDEX}]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The sensor's current humidity reading - a relative humidity
percentage. -1 indicates an invalid reading due to either a
sensor that doesn't read humidity or lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: humidity
- tag: component
value: power
- uuid: ecc2e5c49b004027bb9ccd5498e3d169
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.2.9.{#SNMPINDEX}]'
key: 'external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}]'
description: |
MIB: PowerNet-MIB
The alarm status of the sensor. Possible values:
uioNormal (1),
uioWarning (2),
uioCritical (3),
sensorStatusNotApplicable (4)
valuemap:
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: 3155c8cf446c40d896755a25a46ec90b
expression: 'last(/APC UPS Symmetra LX by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3'
name: 'APC UPS Symmetra: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical'
priority: HIGH
description: 'The external sensor has returned a value greater than the critical threshold.'
tags:
- tag: scope
value: notice
- uuid: 9ef9a4dc80c84087b44b5f0e8aa94202
expression: 'last(/APC UPS Symmetra LX by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4'
name: 'APC UPS Symmetra: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable'
priority: INFO
description: 'The external sensor does not work or is not connected.'
tags:
- tag: scope
value: notice
- uuid: 74a3585b0cc74a4887eb3683fb1e6f64
expression: 'last(/APC UPS Symmetra LX by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2'
name: 'APC UPS Symmetra: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning'
priority: AVERAGE
description: 'The external sensor has returned a value greater than the warning threshold.'
tags:
- tag: scope
value: notice
- uuid: f2cd5bb0c8a64b09868ddff9b14e4cbd
name: '{#EXTERNAL_SENSOR2_NAME}: Temperature sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.2.6.{#SNMPINDEX}]'
key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.2.{#SNMPINDEX}]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The sensor's current temperature reading in Celsius.
-1 indicates an invalid reading due to lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- tag: component
value: temperature
overrides:
- name: Temp
step: '1'
filter:
conditions:
- macro: '{#EXTERNAL_SENSOR2_NAME}'
value: Temp
formulaid: A
operations:
- operationobject: ITEM_PROTOTYPE
operator: LIKE
value: Humidity
discover: NO_DISCOVER
- uuid: b4f271299e9a47bf8543863a7d9be479
name: 'Input phases discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.2.3.1.2.1.1]'
key: input.phases.discovery
delay: 1h
description: 'The input phase identifier. OID upsPhaseInputPhaseIndex.1.1'
item_prototypes:
- uuid: 161257625bc84427be6cfcd86023c2ec
name: '{#PHASEINDEX}: Phase input current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.2.3.1.6.1.1.{#PHASEINDEX}]'
key: 'phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: A
description: |
MIB: PowerNet-MIB
The input current in 0.1 amperes, or -0.1 if it's
unsupported by this UPS.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 080719150b424168999c21ff597e6948
name: '{#PHASEINDEX}: Phase input voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.2.3.1.3.1.1.{#PHASEINDEX}]'
key: 'phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The input voltage in VAC, or -1 if it's unsupported
by this UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
trigger_prototypes:
- uuid: 90e3258375e047b594deb0ecf7300c22
expression: 'min(/APC UPS Symmetra LX by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra LX by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
name: 'APC UPS Symmetra: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage'
event_name: 'APC UPS Symmetra: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 4232ad35daa3403da085f1ba6c7af348
name: 'Output phases discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.3.3.1.2.1.1]'
key: output.phases.discovery
delay: 1h
description: 'The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1'
item_prototypes:
- uuid: 2834306ba5464ffaa472c0adddc3d829
name: '{#PHASEINDEX}: Phase output current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.3.3.1.4.1.1.{#PHASEINDEX}]'
key: 'phase.output.current[upsPhaseOutputCurrent.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: A
description: |
MIB: PowerNet-MIB
The output current in 0.1 amperes drawn
by the load on the UPS, or -1 if it's unsupported
by this UPS.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 7b0f22672b38492e92c8551c3009baef
name: '{#PHASEINDEX}: Phase output load, %'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.3.3.1.10.1.1.{#PHASEINDEX}]'
key: 'phase.output.load.percent[upsPhaseOutputPercentLoad.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The percentage of the UPS load capacity in VA at
redundancy @ (n + x) presently being used on this
output phase, or -1 if it's unsupported by this UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: a590ab8671574e119fe3335110fdee49
name: '{#PHASEINDEX}: Phase output voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.3.3.1.3.1.1.{#PHASEINDEX}]'
key: 'phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The output voltage in VAC, or -1 if it's unsupported
by this UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
trigger_prototypes:
- uuid: b8c42d5d66d9403eba697920439ae956
expression: 'min(/APC UPS Symmetra LX by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra LX by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
name: 'APC UPS Symmetra: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage'
event_name: 'APC UPS Symmetra: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
tags:
- tag: class
value: power
- tag: target
value: apc
- tag: target
value: apc-ups-symmetra-lx
macros:
- macro: '{$BATTERY.CAPACITY.MIN.WARN}'
value: '50'
description: 'Minimum battery capacity percentage for trigger expression.'
- macro: '{$BATTERY.TEMP.MAX.WARN}'
value: '55'
description: 'Maximum battery temperature for trigger expression.'
- macro: '{$SNMP.TIMEOUT}'
value: 5m
description: 'The time interval for SNMP agent availability trigger expression.'
- macro: '{$TIME.PERIOD}'
value: 15m
description: 'Time period for trigger expression.'
- macro: '{$UPS.INPUT_FREQ.MAX.WARN}'
value: '50.3'
description: 'Maximum input frequency for trigger expression.'
- macro: '{$UPS.INPUT_FREQ.MIN.WARN}'
value: '49.7'
description: 'Minimum input frequency for trigger expression.'
- macro: '{$UPS.INPUT_VOLT.MAX.WARN}'
value: '243'
description: 'Maximum input voltage for trigger expression.'
- macro: '{$UPS.INPUT_VOLT.MIN.WARN}'
value: '197'
description: 'Minimum input voltage for trigger expression.'
- macro: '{$UPS.OUTPUT.MAX.WARN}'
value: '80'
description: 'Maximum output load in % for trigger expression.'
dashboards:
- uuid: ff52b4f8ce124ee78849babbee2797ab
name: 'APC UPS Symmetra LX: General'
pages:
- name: 'APC UPS Symmetra LX: General'
widgets:
- type: graph
name: Voltage
width: '36'
height: '5'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'APC UPS Symmetra LX by SNMP'
name: 'APC UPS Symmetra LX: Voltage'
- type: STRING
name: reference
value: AAAAA
- type: graph
name: 'Capacity of the UPS batteries'
'y': '5'
width: '36'
height: '5'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'APC UPS Symmetra LX by SNMP'
name: 'APC UPS Symmetra LX: Capacity of the UPS batteries'
- type: STRING
name: reference
value: AAAAC
- type: graph
name: Output
x: '36'
width: '36'
height: '5'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'APC UPS Symmetra LX by SNMP'
name: 'APC UPS Symmetra LX: Output'
- type: STRING
name: reference
value: AAAAB
valuemaps:
- uuid: aec3362485c242ec928cb8ecfe5e61cf
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
mappings:
- value: '1'
newvalue: Normal
- value: '2'
newvalue: Warning
- value: '3'
newvalue: Critical
- value: '4'
newvalue: 'Not applicable'
- uuid: 912d8834176b4fe4a2f6bd12ef3ee3c1
name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator'
mappings:
- value: '1'
newvalue: 'no Battery Needs Replacing'
- value: '2'
newvalue: 'battery Needs Replacing'
- uuid: e079fa8cc9614245b0fecf4b8f42feca
name: 'PowerNet-MIB::upsAdvInputLineFailCause'
mappings:
- value: '1'
newvalue: 'no Transfer'
- value: '2'
newvalue: 'High Line Voltage'
- value: '3'
newvalue: Brownout
- value: '4'
newvalue: Blackout
- value: '5'
newvalue: 'Small Momentary Sag'
- value: '6'
newvalue: 'Deep Momentary Sag'
- value: '7'
newvalue: 'Small Momentary Spike'
- value: '8'
newvalue: 'Large Momentary Spike'
- value: '9'
newvalue: 'Self Test'
- value: '10'
newvalue: 'Rate of Voltage Change'
- uuid: 24229472978c42739cdbe7aa47e1d34c
name: 'PowerNet-MIB::upsBasicBatteryStatus'
mappings:
- value: '1'
newvalue: Unknown
- value: '2'
newvalue: Normal
- value: '3'
newvalue: Low
- value: '4'
newvalue: 'In Fault Condition'
- uuid: 8c2c9721615c4408976f7632180ecfe3
name: 'PowerNet-MIB::upsBasicOutputStatus'
mappings:
- value: '1'
newvalue: Unknown
- value: '2'
newvalue: Online
- value: '3'
newvalue: 'On Battery'
- value: '4'
newvalue: 'On Smart Boost'
- value: '5'
newvalue: 'Timed Sleeping'
- value: '6'
newvalue: 'Software Bypass'
- value: '7'
newvalue: 'Off'
- value: '8'
newvalue: Rebooting
- value: '9'
newvalue: 'Switched Bypass'
- value: '10'
newvalue: 'Hardware Failure Bypass'
- value: '11'
newvalue: 'Sleeping Until Power Return'
- value: '12'
newvalue: 'On Smart Trim'
- value: '13'
newvalue: 'Eco Mode'
- value: '14'
newvalue: 'Hot Standby'
- value: '15'
newvalue: 'On Battery Test'
- value: '16'
newvalue: 'Emergency Static Bypass'
- value: '17'
newvalue: 'Static Bypass Standby'
- value: '18'
newvalue: 'Power Saving Mode'
- value: '19'
newvalue: 'Spot Mode'
- value: '20'
newvalue: E-Conversion
- value: '21'
newvalue: 'Charger Spotmode'
- value: '22'
newvalue: 'Inverter Spotmode'
- value: '23'
newvalue: 'Active Load'
- value: '24'
newvalue: 'Battery Discharge Spotmode'
- value: '25'
newvalue: 'Inverter Standby'
- value: '26'
newvalue: 'Charger Only'
- uuid: 625f28bd49f14e49a1a7a4da01429906
name: zabbix.host.available
mappings:
- value: '0'
newvalue: 'not available'
- value: '1'
newvalue: available
- value: '2'
newvalue: unknown
triggers:
- uuid: 9d0c32f93c0c44f69b54c91fabfa1529
expression: |
(last(/APC UPS Symmetra LX by SNMP/system.hw.uptime[hrSystemUptime.0])>0 and last(/APC UPS Symmetra LX by SNMP/system.hw.uptime[hrSystemUptime.0])<10m)
or (last(/APC UPS Symmetra LX by SNMP/system.hw.uptime[hrSystemUptime.0])=0 and last(/APC UPS Symmetra LX by SNMP/system.net.uptime[sysUpTime.0])<10m)
name: 'APC UPS Symmetra: Host has been restarted'
event_name: 'APC UPS Symmetra: {HOST.NAME} has been restarted (uptime < 10m)'
priority: WARNING
description: 'Uptime is less than 10 minutes.'
manual_close: 'YES'
dependencies:
- name: 'APC UPS Symmetra: No SNMP data collection'
expression: 'max(/APC UPS Symmetra LX by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
tags:
- tag: scope
value: notice
graphs:
- uuid: 265f3050b3b94cbeae6fefdae02ea992
name: 'APC UPS Symmetra LX: Capacity of the UPS batteries'
type: PIE
graph_items:
- color: 199C0D
item:
host: 'APC UPS Symmetra LX by SNMP'
key: 'battery.capacity[upsHighPrecBatteryCapacity]'
- uuid: 2ef61780d42c4d61bcb89faf08691d08
name: 'APC UPS Symmetra LX: Output'
graph_items:
- color: 199C0D
item:
host: 'APC UPS Symmetra LX by SNMP'
key: 'output.current[upsHighPrecOutputCurrent]'
- sortorder: '1'
color: F63100
item:
host: 'APC UPS Symmetra LX by SNMP'
key: 'output.load[upsHighPrecOutputLoad]'
- uuid: 4432ed7ca97d4d989b253383037f48ee
name: 'APC UPS Symmetra LX: Voltage'
graph_items:
- color: 199C0D
item:
host: 'APC UPS Symmetra LX by SNMP'
key: 'input.voltage[upsHighPrecInputLineVoltage]'
- sortorder: '1'
color: F63100
item:
host: 'APC UPS Symmetra LX by SNMP'
key: 'output.voltage[upsHighPrecOutputVoltage]'