Files
templates-default/APC_Smart-UPS_SRT_8000_by_SNMP.yaml

1556 lines
67 KiB
YAML

zabbix_export:
version: '7.0'
template_groups:
- uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
name: Templates/Power
templates:
- uuid: b3caafda8c5345cc832ac3be3cefa615
template: 'APC Smart-UPS SRT 8000 by SNMP'
name: 'APC Smart-UPS SRT 8000 by SNMP'
description: |
Template Power APC Smart-UPS SRT 8000
MIBs used:
HOST-RESOURCES-MIB
PowerNet-MIB
SNMPv2-MIB
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
Generated by official Zabbix template tool "Templator"
vendor:
name: Zabbix
version: 7.0-4
groups:
- name: Templates/Power
items:
- uuid: c4f4a85105f24292a3b566d0d1bcc090
name: 'Battery capacity'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.1.0]'
key: 'battery.capacity[upsHighPrecBatteryCapacity]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The remaining battery capacity expressed as
percentage of full capacity.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: 92e6a65ffc6d4a6bae62303ee2796580
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}'
name: 'APC Smart-UPS: Battery has low capacity'
event_name: 'APC Smart-UPS: Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%)'
opdata: 'Current capacity: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: capacity
- uuid: 7d7c2b962e9843b8a6cf72c04ff1e479
name: 'External battery packs count'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.5.0]'
key: 'battery.external_packs_count[upsAdvBatteryNumOfBattPacks]'
delay: 1h
description: |
MIB: PowerNet-MIB
The number of external battery packs connected to the UPS. If
the UPS does not use smart cells then the agent reports
ERROR_NO_SUCH_NAME.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: 552e030c272d43a0998bc2648f15ae44
name: 'Battery last replace date'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.1.3.0]'
key: 'battery.last_replace_date[upsBasicBatteryLastReplaceDate]'
delay: 1h
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The date when the UPS system's batteries were last replaced
in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value
is originally set at the factory. When the UPS batteries
are replaced, this value should be reset by the administrator.
For Symmetra PX 250/500 this OID is read-only and is configurable in the local display only.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: 4cdd4bbff845477194a6d96a31431d23
name: 'Battery replace indicator'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.4.0]'
key: 'battery.replace_indicator[upsAdvBatteryReplaceIndicator]'
description: |
MIB: PowerNet-MIB
Indicates whether the UPS batteries need replacement.
valuemap:
name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: 0e8030c0028144728361153c2b47016b
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2'
name: 'APC Smart-UPS: Battery needs replacement'
priority: HIGH
description: 'A battery installed has an internal error condition.'
tags:
- tag: scope
value: notice
- uuid: ae8a19896d21405ca99a5bfbd5de1f95
name: 'Battery runtime remaining'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.3.0]'
key: 'battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]'
value_type: FLOAT
units: s
description: |
MIB: PowerNet-MIB
The UPS battery run time remaining before battery
exhaustion.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.01'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: ceed5ddfc9964aabaebb0b97875b1bd9
name: 'Battery status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.1.1.0]'
key: 'battery.status[upsBasicBatteryStatus]'
description: |
MIB: PowerNet-MIB
The status of the UPS batteries. A batteryLow(3) value
indicates the UPS will be unable to sustain the current
load, and its services will be lost if power is not restored.
The amount of run time in reserve at the time of low battery
can be configured by the upsAdvConfigLowBatteryRunTime.
A batteryInFaultCondition(4)value indicates that a battery
installed has an internal error condition.
valuemap:
name: 'PowerNet-MIB::upsBasicBatteryStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
triggers:
- uuid: cf186014cfd94ccbad3cc4cbd22b6aa1
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/battery.status[upsBasicBatteryStatus])=4'
name: 'APC Smart-UPS: Battery has an internal error condition'
priority: AVERAGE
description: 'A battery installed has an internal error condition.'
tags:
- tag: scope
value: notice
- uuid: e1957ee82be847e7bfb171560fc59293
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/battery.status[upsBasicBatteryStatus])=3'
name: 'APC Smart-UPS: Battery is Low'
priority: AVERAGE
description: 'The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.'
tags:
- tag: scope
value: capacity
- uuid: 533041b6831c451cb72991d3fdeca535
name: 'Battery temperature'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.2.0]'
key: 'battery.temperature[upsHighPrecBatteryTemperature]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The current internal UPS temperature in Celsius.
Temperatures below zero read as 0.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: temperature
triggers:
- uuid: 1e883961b65e445997c57870734a58ca
expression: 'min(/APC Smart-UPS SRT 8000 by SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
name: 'APC Smart-UPS: Battery has high temperature'
event_name: 'APC Smart-UPS: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})'
opdata: 'Current temperature: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: fa8256c826954defa82083ddc742624e
name: 'Battery voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.4.0]'
key: 'battery.voltage[upsHighPrecBatteryActualVoltage]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The actual battery bus voltage in Volts.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 07754bb421d0435995abbc49d4597908
name: 'Input fail cause'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.3.2.5.0]'
key: 'input.fail[upsAdvInputLineFailCause]'
description: |
MIB: PowerNet-MIB
The reason for the occurrence of the last transfer to UPS
battery power. The variable is set to:
- noTransfer(1) -- if there is no transfer yet.
- highLineVoltage(2) -- if the transfer to battery is caused
by an over voltage greater than the high transfer voltage.
- brownout(3) -- if the duration of the outage is greater than
five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- blackout(4) -- if the duration of the outage is greater than five
seconds and the line voltage is between 40% of the rated
output voltage and ground.
- smallMomentarySag(5) -- if the duration of the outage is less
than five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- deepMomentarySag(6) -- if the duration of the outage is less
than five seconds and the line voltage is between 40% of the
rated output voltage and ground. The variable is set to
- smallMomentarySpike(7) -- if the line failure is caused by a
rate of change of input voltage less than ten volts per cycle.
- largeMomentarySpike(8) -- if the line failure is caused by
a rate of change of input voltage greater than ten volts per cycle.
- selfTest(9) -- if the UPS was commanded to do a self test.
- rateOfVoltageChange(10) -- if the failure is due to the rate of change of
the line voltage.
valuemap:
name: 'PowerNet-MIB::upsAdvInputLineFailCause'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 7574344f67544554804c4c68e39d3d72
name: 'Input frequency'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.3.3.4.0]'
key: 'input.frequency[upsHighPrecInputFrequency]'
value_type: FLOAT
units: Hz
description: |
MIB: PowerNet-MIB
The current input frequency to the UPS system in Hz.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: b9a134c942da46ffba1acdf85a7832e4
expression: 'min(/APC Smart-UPS SRT 8000 by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS SRT 8000 by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS SRT 8000 by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})'
name: 'APC Smart-UPS: Unacceptable input frequency'
event_name: 'APC Smart-UPS: Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD})'
opdata: 'Current frequency: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: c69418651f75413e95645c62fa3fee7f
name: 'Input voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.3.3.1.0]'
key: 'input.voltage[upsHighPrecInputLineVoltage]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The current utility line voltage in VAC.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: 694ab76079b1447b99ef510d80faab6a
expression: 'min(/APC Smart-UPS SRT 8000 by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS SRT 8000 by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 8000 by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})'
name: 'APC Smart-UPS: Unacceptable input voltage'
event_name: 'APC Smart-UPS: Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current voltage: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: e4d76d857c4e46fd9b0e97405b17988a
name: 'Output current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.3.4.0]'
key: 'output.current[upsHighPrecOutputCurrent]'
value_type: FLOAT
units: A
description: |
MIB: PowerNet-MIB
The current in amperes drawn by the load on the UPS.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 0413f6ef89894dc6ba51e42f6a963f94
name: 'Output load'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.3.3.0]'
key: 'output.load[upsHighPrecOutputLoad]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The current UPS load expressed as percentage
of rated capacity.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: 68f92026e7b345c88bf4aa679f9b642c
expression: 'min(/APC Smart-UPS SRT 8000 by SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}'
name: 'APC Smart-UPS: Output load is high'
event_name: 'APC Smart-UPS: Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD})'
opdata: 'Current load: {ITEM.LASTVALUE1}'
priority: HIGH
description: 'A battery installed has an internal error condition.'
tags:
- tag: scope
value: notice
- uuid: 11c1742beed041999375e5a1ede42546
name: 'Output status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.1.1.0]'
key: 'output.status[upsBasicOutputStatus]'
description: |
MIB: PowerNet-MIB
The current state of the UPS. If the UPS is unable to
determine the state of the UPS this variable is set
to unknown(1).
During self-test most UPSes report onBattery(3) but
some that support it will report onBatteryTest(15).
To determine self-test status across all UPSes, refer
to the upsBasicStateOutputState OID.
valuemap:
name: 'PowerNet-MIB::upsBasicOutputStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
triggers:
- uuid: 9952679fada845228bbbf05bcdada305
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/output.status[upsBasicOutputStatus])=16'
name: 'APC Smart-UPS: UPS is Emergency Static Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: ee306606159f4930bcf580b5084c846a
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/output.status[upsBasicOutputStatus])=10'
name: 'APC Smart-UPS: UPS is Hardware Failure Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: c4623dc4c6ae4c5b9ff4bdf4f43ed8b2
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/output.status[upsBasicOutputStatus])=7'
name: 'APC Smart-UPS: UPS is Off'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 26c0b9b62d864c1ead7b16e0076a7226
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/output.status[upsBasicOutputStatus])=3'
name: 'APC Smart-UPS: UPS is on battery'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 5c8408069c03421cb60b388451869b6f
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/output.status[upsBasicOutputStatus])=4'
name: 'APC Smart-UPS: UPS is on Smart Boost'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 156c5260ed4444c19313ba491ce9352c
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/output.status[upsBasicOutputStatus])=12'
name: 'APC Smart-UPS: UPS is On Smart Trim'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: c233bc86198140659ec3dd609c94ec94
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/output.status[upsBasicOutputStatus])=8'
name: 'APC Smart-UPS: UPS is Rebooting'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 944e49d1b6d44adc8d720bd689d8c8cf
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/output.status[upsBasicOutputStatus])=11'
name: 'APC Smart-UPS: UPS is Sleeping Until Power Return'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 9b376dbd2d614878b681b42bb2c7fe4d
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/output.status[upsBasicOutputStatus])=6'
name: 'APC Smart-UPS: UPS is Software Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 499ac46836c1454dad3c1ffc5714c073
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/output.status[upsBasicOutputStatus])=9'
name: 'APC Smart-UPS: UPS is Switched Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 8a0a5af39647494681e52595d179c336
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/output.status[upsBasicOutputStatus])=5'
name: 'APC Smart-UPS: UPS is Timed Sleeping'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 07059c625de94e618925249492982fb7
name: 'Output voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.3.1.0]'
key: 'output.voltage[upsHighPrecOutputVoltage]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The output voltage of the UPS system in VAC.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: ae4579b14c424c0492acbfcb5aa5dd67
name: 'SNMP traps (fallback)'
type: SNMP_TRAP
key: snmptrap.fallback
delay: '0'
value_type: LOG
trends: '0'
description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items'
logtimefmt: 'hh:mm:sszyyyy/MM/dd'
tags:
- tag: component
value: network
- uuid: e4995e72f6b442bd9b8c90f09eb54f16
name: 'System contact details'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.4.0]'
key: 'system.contact[sysContact.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
The textual identification of the contact person for this managed
node, together with information on how to contact this person. If no contact
information is known, the value is the zero-length string.
inventory_link: CONTACT
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 12h
tags:
- tag: component
value: system
- uuid: 13d3c18413a249d492272a7373ebd772
name: 'System description'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.1.0]'
key: 'system.descr[sysDescr.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
A textual description of the entity. This value should
include the full name and version identification of the system's hardware type, software operating-system, and
networking software.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 12h
tags:
- tag: component
value: system
- uuid: 4e8b6d6a5aa24159b048d1cf28e9418a
name: 'Uptime (hardware)'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.25.1.1.0]'
key: 'system.hw.uptime[hrSystemUptime.0]'
delay: 30s
trends: '0'
units: uptime
description: |
MIB: HOST-RESOURCES-MIB
The amount of time since this host was last initialized. Note that this is different from sysUpTime in the SNMPv2-MIB [RFC1907] because sysUpTime is the uptime of the network management portion of the system.
preprocessing:
- type: CHECK_NOT_SUPPORTED
parameters:
- '-1'
error_handler: CUSTOM_VALUE
error_handler_params: '0'
- type: MULTIPLIER
parameters:
- '0.01'
tags:
- tag: component
value: system
- uuid: 25aa469a757347089191eb8e364d4df9
name: 'System location'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.6.0]'
key: 'system.location[sysLocation.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
The physical location of this node (e.g., `telephone closet, 3rd floor'). If the location is unknown, the value is the zero-length string.
inventory_link: LOCATION
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: system
- uuid: 57f3c4c2aff04eef83b7a7a53fa9f95c
name: Model
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.1.1.1.0]'
key: 'system.model[upsBasicIdentModel]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The UPS model name (e.g. 'APC Smart-UPS 600').
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: 13c26820947442f581c2234c38c052cc
name: 'System name'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.5.0]'
key: 'system.name[sysName.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
An administratively-assigned name for this managed node.By convention, this is the node's fully-qualified domain name. If the name is unknown, the value is the zero-length string.
inventory_link: NAME
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: system
triggers:
- uuid: 852083234a55441aa2fa57b202227bef
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS SRT 8000 by SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS SRT 8000 by SNMP/system.name[sysName.0]))>0'
name: 'APC Smart-UPS: System name has changed'
event_name: 'APC Smart-UPS: System name has changed (new name: {ITEM.VALUE})'
priority: INFO
description: 'The name of the system has changed. Acknowledge to close the problem manually.'
manual_close: 'YES'
tags:
- tag: scope
value: notice
- tag: scope
value: security
- uuid: 320bdbfd8076411bb1dd63fccddec126
name: 'Uptime (network)'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.3.0]'
key: 'system.net.uptime[sysUpTime.0]'
delay: 30s
trends: '0'
units: uptime
description: |
MIB: SNMPv2-MIB
The time (in hundredths of a second) since the network management portion of the system was last re-initialized.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.01'
tags:
- tag: component
value: system
- uuid: b59b3801f5584321a1fca9bdb466f191
name: 'System object ID'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.2.0]'
key: 'system.objectid[sysObjectID.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
The vendor's authoritative identification of the network management subsystem contained in the entity. This value is allocated within the SMI enterprises subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1 to its `Fred Router'.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: system
- uuid: 63852531159c44f1beca7facd8f93fa2
name: 'Serial number'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.1.2.3.0]'
key: 'system.sn[upsAdvIdentSerialNumber]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
An 8-character string identifying the serial number of
the UPS internal microprocessor. This number is set at
the factory. NOTE: This number does NOT correspond to
the serial number on the rear of the UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: 567996748402435d80aae37818d4125e
name: 'SNMP agent availability'
type: INTERNAL
key: 'zabbix[host,snmp,available]'
description: |
Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.
Possible values:
0 - not available
1 - available
2 - unknown
valuemap:
name: zabbix.host.available
tags:
- tag: component
value: health
- tag: component
value: network
triggers:
- uuid: 9a0cb26712c14045a18a0e86de4cdd54
expression: 'max(/APC Smart-UPS SRT 8000 by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
name: 'APC Smart-UPS: No SNMP data collection'
opdata: 'Current state: {ITEM.LASTVALUE1}'
priority: WARNING
description: 'SNMP is not available for polling. Please check device connectivity and SNMP settings.'
tags:
- tag: scope
value: availability
discovery_rules:
- uuid: 912994ce460742ebbb91c89d28d87d73
name: 'External bad battery packs discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#EXTERNAL_PACKS},1.3.6.1.4.1.318.1.1.1.2.2.6]'
key: battery.packs.bad.discovery
delay: 1h
filter:
evaltype: AND
conditions:
- macro: '{#EXTERNAL_PACKS}'
value: '-1'
operator: NOT_MATCHES_REGEX
formulaid: A
description: 'Discovery of the number of external defective battery packs.'
item_prototypes:
- uuid: e74988ed369b429893ca495a57ae9a52
name: '{#SNMPINDEX}: External battery packs bad'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.6.0]'
key: 'battery.external_packs_bad[upsAdvBatteryNumOfBadBattPacks.{#SNMPINDEX}]'
delay: 15m
description: |
MIB: PowerNet-MIB
The number of external battery packs connected to the UPS that
are defective. If the UPS does not use smart cells then the
agent reports ERROR_NO_SUCH_NAME.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: abfe041a98dc4023b21ec6d9e829a94a
name: 'External battery packs discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#CARTRIDGE_STATUS},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7,{#BATTERY_PACK},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1,{#CARTRIDGE_INDEX},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2]'
key: battery.packs.discovery
delay: 1h
filter:
evaltype: AND
conditions:
- macro: '{#CARTRIDGE_STATUS}'
value: ^$
operator: NOT_MATCHES_REGEX
formulaid: A
item_prototypes:
- uuid: b3835f9b8e9c41c98a747c37feaedb50
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery estimated replace date'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8.{#SNMPINDEX}]'
key: 'battery.estimated_replace_date[upsHighPrecBatteryPackCartridgeReplaceDate.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
delay: 1h
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The battery cartridge estimated battery replace date.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- tag: component
value: power
- uuid: 820d8eda050b41a3a9ba2889e290a28a
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7.{#SNMPINDEX}]'
key: 'battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The battery cartridge health.
bit 0 Battery lifetime okay
bit 1 Battery lifetime near end, order replacement cartridge
bit 2 Battery lifetime exceeded, replace battery
bit 3 Battery lifetime near end acknowledged, order replacement cartridge
bit 4 Battery lifetime exceeded acknowledged, replace battery
bit 5 Battery measured lifetime near end, order replacement cartridge
bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: 2d9c4ef006994ebea581b895424203f3
expression: 'find(/APC Smart-UPS SRT 8000 by SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1'
name: 'APC Smart-UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay'
opdata: 'Current bit set: {ITEM.LASTVALUE1}'
priority: WARNING
description: |
The battery cartridge health.
bit 0 Battery lifetime okay
bit 1 Battery lifetime near end, order replacement cartridge
bit 2 Battery lifetime exceeded, replace battery
bit 3 Battery lifetime near end acknowledged, order replacement cartridge
bit 4 Battery lifetime exceeded acknowledged, replace battery
bit 5 Battery measured lifetime near end, order replacement cartridge
bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge
tags:
- tag: scope
value: notice
- uuid: cf709f051aa242799cf14ba923d9a0c0
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10.{#SNMPINDEX}]'
key: 'battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The status of the UPS batteries. A batteryLow(3) value
indicates the UPS will be unable to sustain the current
load, and its services will be lost if power is not restored.
The amount of run time in reserve at the time of low battery
can be configured by the upsAdvConfigLowBatteryRunTime.
A batteryInFaultCondition(4)value indicates that a battery
installed has an internal error condition.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: 5358b97f94aa47f59351be88673407a0
expression: 'find(/APC Smart-UPS SRT 8000 by SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0'
name: 'APC Smart-UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay'
opdata: 'Current bit set: {ITEM.LASTVALUE1}'
priority: WARNING
description: |
The battery cartridge status:
bit 0 Disconnected
bit 1 Overvoltage
bit 2 NeedsReplacement
bit 3 OvertemperatureCritical
bit 4 Charger
bit 5 TemperatureSensor
bit 6 BusSoftStart
bit 7 OvertemperatureWarning
bit 8 GeneralError
bit 9 Communication
bit 10 DisconnectedFrame
bit 11 FirmwareMismatch
tags:
- tag: scope
value: notice
- uuid: 99c570ed628343e99ac086167cec51ee
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperature'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5.{#SNMPINDEX}]'
key: 'battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The current internal UPS temperature in Celsius.
Temperatures below zero read as 0.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: temperature
trigger_prototypes:
- uuid: b88678e600694bc19ebaf57472d8658f
expression: 'min(/APC Smart-UPS SRT 8000 by SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
name: 'APC Smart-UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature'
event_name: 'APC Smart-UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})'
opdata: 'Current temperature: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 597b33ec3d4c4f79bc0acc36edaa6dec
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4.{#SNMPINDEX}]'
key: 'system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
An 8-character string identifying the serial number of
the UPS internal microprocessor. This number is set at
the factory. NOTE: This number does NOT correspond to
the serial number on the rear of the UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: 52e5451d8c7a41478ef9dde6a3c16378
name: 'External sensor port 1 discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#EXTERNAL_SENSOR1_NAME},1.3.6.1.4.1.318.1.1.25.1.2.1.3]'
key: external.sensor1.discovery
delay: 1h
description: uioSensorStatusTable
item_prototypes:
- uuid: 418b37fbca594f6288eeccdbe272bad7
name: '{#EXTERNAL_SENSOR1_NAME}: Humidity sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.1.7.{#SNMPINDEX}]'
key: 'external.sensor.humidity[uioSensorStatusHumidity.1.{#SNMPINDEX}]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The sensor's current humidity reading - a relative humidity
percentage. -1 indicates an invalid reading due to either a
sensor that doesn't read humidity or lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: humidity
- tag: component
value: power
- uuid: 53102fe478cf47bd9fbe5240aab7cf65
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.1.9.{#SNMPINDEX}]'
key: 'external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}]'
description: |
MIB: PowerNet-MIB
The alarm status of the sensor. Possible values:
uioNormal (1),
uioWarning (2),
uioCritical (3),
sensorStatusNotApplicable (4)
valuemap:
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: 33f4ac80a8d44752b97bc4f885a8c95f
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3'
name: 'APC Smart-UPS: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical'
priority: HIGH
description: 'The external sensor has returned a value greater than the critical threshold.'
tags:
- tag: scope
value: notice
- uuid: 1a2080a561394f8c8a0dc639cbf2c812
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4'
name: 'APC Smart-UPS: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable'
priority: INFO
description: 'The external sensor does not work or is not connected.'
tags:
- tag: scope
value: notice
- uuid: a53d5dd33e8548d5bcb73ffb936af910
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2'
name: 'APC Smart-UPS: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning'
priority: AVERAGE
description: 'The external sensor has returned a value greater than the warning threshold.'
tags:
- tag: scope
value: notice
- uuid: 0f44bfc0e17b47919e83246046209bbf
name: '{#EXTERNAL_SENSOR1_NAME}: Temperature sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.1.6.{#SNMPINDEX}]'
key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.1.{#SNMPINDEX}]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The sensor's current temperature reading in Celsius.
-1 indicates an invalid reading due to lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- tag: component
value: temperature
overrides:
- name: Temp
step: '1'
filter:
conditions:
- macro: '{#EXTERNAL_SENSOR1_NAME}'
value: Temp
formulaid: A
operations:
- operationobject: ITEM_PROTOTYPE
operator: LIKE
value: Humidity
discover: NO_DISCOVER
- uuid: 39f516180a1b4727907b1e2974111fe1
name: 'External sensor port 2 discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#EXTERNAL_SENSOR2_NAME},1.3.6.1.4.1.318.1.1.25.1.2.2.3]'
key: external.sensor2.discovery
delay: 1h
description: uioSensorStatusTable
item_prototypes:
- uuid: 2263b22a266a4db091f05522a024a1e4
name: '{#EXTERNAL_SENSOR2_NAME}: Humidity sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.2.7.{#SNMPINDEX}]'
key: 'external.sensor.humidity[uioSensorStatusHumidity.2.{#SNMPINDEX}]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The sensor's current humidity reading - a relative humidity
percentage. -1 indicates an invalid reading due to either a
sensor that doesn't read humidity or lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: humidity
- tag: component
value: power
- uuid: b7af85f894194cf39c369fcba0401cc5
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.2.9.{#SNMPINDEX}]'
key: 'external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}]'
description: |
MIB: PowerNet-MIB
The alarm status of the sensor. Possible values:
uioNormal (1),
uioWarning (2),
uioCritical (3),
sensorStatusNotApplicable (4)
valuemap:
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: 9247973676c44377a4fa550990384eeb
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3'
name: 'APC Smart-UPS: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical'
priority: HIGH
description: 'The external sensor has returned a value greater than the critical threshold.'
tags:
- tag: scope
value: notice
- uuid: 6b054505c2704c8d8e38b096885bbbe5
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4'
name: 'APC Smart-UPS: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable'
priority: INFO
description: 'The external sensor does not work or is not connected.'
tags:
- tag: scope
value: notice
- uuid: f56f165d71084b75a716d04337f5fcb1
expression: 'last(/APC Smart-UPS SRT 8000 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2'
name: 'APC Smart-UPS: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning'
priority: AVERAGE
description: 'The external sensor has returned a value greater than the warning threshold.'
tags:
- tag: scope
value: notice
- uuid: 84af771eee61470d9a61cede04718d88
name: '{#EXTERNAL_SENSOR2_NAME}: Temperature sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.2.6.{#SNMPINDEX}]'
key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.2.{#SNMPINDEX}]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The sensor's current temperature reading in Celsius.
-1 indicates an invalid reading due to lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- tag: component
value: temperature
overrides:
- name: Temp
step: '1'
filter:
conditions:
- macro: '{#EXTERNAL_SENSOR2_NAME}'
value: Temp
formulaid: A
operations:
- operationobject: ITEM_PROTOTYPE
operator: LIKE
value: Humidity
discover: NO_DISCOVER
- uuid: 10363e965d97464a9344baa5fa7a2f53
name: 'Input phases discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.2.3.1.2.1.1]'
key: input.phases.discovery
delay: 1h
description: 'The input phase identifier. OID upsPhaseInputPhaseIndex.1.1'
item_prototypes:
- uuid: a275ab18a7064706bf721498ac7c5605
name: '{#PHASEINDEX}: Phase input current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.2.3.1.6.1.1.{#PHASEINDEX}]'
key: 'phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: A
description: |
MIB: PowerNet-MIB
The input current in 0.1 amperes, or -0.1 if it's
unsupported by this UPS.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 113adf39a65548abab2da39aec20c169
name: '{#PHASEINDEX}: Phase input voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.2.3.1.3.1.1.{#PHASEINDEX}]'
key: 'phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The input voltage in VAC, or -1 if it's unsupported
by this UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
trigger_prototypes:
- uuid: 755f972a32904dbf81a6da77f4ba57f0
expression: 'min(/APC Smart-UPS SRT 8000 by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 8000 by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
name: 'APC Smart-UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage'
event_name: 'APC Smart-UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 0a3159e22ba640e2840789b63bee2bda
name: 'Output phases discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.3.3.1.2.1.1]'
key: output.phases.discovery
delay: 1h
description: 'The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1'
item_prototypes:
- uuid: 3b625f8ab9f54dca882534d78ee0e584
name: '{#PHASEINDEX}: Phase output current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.3.3.1.4.1.1.{#PHASEINDEX}]'
key: 'phase.output.current[upsPhaseOutputCurrent.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: A
description: |
MIB: PowerNet-MIB
The output current in 0.1 amperes drawn
by the load on the UPS, or -1 if it's unsupported
by this UPS.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 99357a267db04c8ca9385aaa15116b79
name: '{#PHASEINDEX}: Phase output load, %'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.3.3.1.10.1.1.{#PHASEINDEX}]'
key: 'phase.output.load.percent[upsPhaseOutputPercentLoad.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The percentage of the UPS load capacity in VA at
redundancy @ (n + x) presently being used on this
output phase, or -1 if it's unsupported by this UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 13315206a94948a09fbb4a9843d2e149
name: '{#PHASEINDEX}: Phase output voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.3.3.1.3.1.1.{#PHASEINDEX}]'
key: 'phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The output voltage in VAC, or -1 if it's unsupported
by this UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
trigger_prototypes:
- uuid: 5846a7a3d56f43de8394823ed64a11ae
expression: 'min(/APC Smart-UPS SRT 8000 by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 8000 by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
name: 'APC Smart-UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage'
event_name: 'APC Smart-UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
tags:
- tag: class
value: power
- tag: target
value: apc
- tag: target
value: apc-smart-ups-srt-8000
macros:
- macro: '{$BATTERY.CAPACITY.MIN.WARN}'
value: '50'
description: 'Minimum battery capacity percentage for trigger expression.'
- macro: '{$BATTERY.TEMP.MAX.WARN}'
value: '55'
description: 'Maximum battery temperature for trigger expression.'
- macro: '{$SNMP.TIMEOUT}'
value: 5m
description: 'The time interval for SNMP agent availability trigger expression.'
- macro: '{$TIME.PERIOD}'
value: 15m
description: 'Time period for trigger expression.'
- macro: '{$UPS.INPUT_FREQ.MAX.WARN}'
value: '50.3'
description: 'Maximum input frequency for trigger expression.'
- macro: '{$UPS.INPUT_FREQ.MIN.WARN}'
value: '49.7'
description: 'Minimum input frequency for trigger expression.'
- macro: '{$UPS.INPUT_VOLT.MAX.WARN}'
value: '243'
description: 'Maximum input voltage for trigger expression.'
- macro: '{$UPS.INPUT_VOLT.MIN.WARN}'
value: '197'
description: 'Minimum input voltage for trigger expression.'
- macro: '{$UPS.OUTPUT.MAX.WARN}'
value: '80'
description: 'Maximum output load in % for trigger expression.'
dashboards:
- uuid: 3a1da069730b43f5a631482f113f3752
name: 'APC Smart-UPS SRT 8000: General'
pages:
- name: 'APC Smart-UPS SRT 8000: General'
widgets:
- type: graph
name: Voltage
width: '36'
height: '5'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'APC Smart-UPS SRT 8000 by SNMP'
name: 'APC Smart-UPS SRT 8000: Voltage'
- type: STRING
name: reference
value: AAAAA
- type: graph
name: 'Capacity of the UPS batteries'
'y': '5'
width: '36'
height: '5'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'APC Smart-UPS SRT 8000 by SNMP'
name: 'APC Smart-UPS SRT 8000: Capacity of the UPS batteries'
- type: STRING
name: reference
value: AAAAC
- type: graph
name: Output
x: '36'
width: '36'
height: '5'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'APC Smart-UPS SRT 8000 by SNMP'
name: 'APC Smart-UPS SRT 8000: Output'
- type: STRING
name: reference
value: AAAAB
valuemaps:
- uuid: 864d59cbfcc8431cb334b812bf7ef3a3
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
mappings:
- value: '1'
newvalue: Normal
- value: '2'
newvalue: Warning
- value: '3'
newvalue: Critical
- value: '4'
newvalue: 'Not applicable'
- uuid: cc42cb7a7fb4417fa1c143e214958c1d
name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator'
mappings:
- value: '1'
newvalue: 'no Battery Needs Replacing'
- value: '2'
newvalue: 'battery Needs Replacing'
- uuid: a3bbd0be8c7c4dc1aa9accb9f22292c9
name: 'PowerNet-MIB::upsAdvInputLineFailCause'
mappings:
- value: '1'
newvalue: 'no Transfer'
- value: '2'
newvalue: 'High Line Voltage'
- value: '3'
newvalue: Brownout
- value: '4'
newvalue: Blackout
- value: '5'
newvalue: 'Small Momentary Sag'
- value: '6'
newvalue: 'Deep Momentary Sag'
- value: '7'
newvalue: 'Small Momentary Spike'
- value: '8'
newvalue: 'Large Momentary Spike'
- value: '9'
newvalue: 'Self Test'
- value: '10'
newvalue: 'Rate of Voltage Change'
- uuid: f801d4fb07c644e4be1f01e99ba48aa7
name: 'PowerNet-MIB::upsBasicBatteryStatus'
mappings:
- value: '1'
newvalue: Unknown
- value: '2'
newvalue: Normal
- value: '3'
newvalue: Low
- value: '4'
newvalue: 'In Fault Condition'
- uuid: 28964e9cf2b849fbb2f8d998cecdacda
name: 'PowerNet-MIB::upsBasicOutputStatus'
mappings:
- value: '1'
newvalue: Unknown
- value: '2'
newvalue: Online
- value: '3'
newvalue: 'On Battery'
- value: '4'
newvalue: 'On Smart Boost'
- value: '5'
newvalue: 'Timed Sleeping'
- value: '6'
newvalue: 'Software Bypass'
- value: '7'
newvalue: 'Off'
- value: '8'
newvalue: Rebooting
- value: '9'
newvalue: 'Switched Bypass'
- value: '10'
newvalue: 'Hardware Failure Bypass'
- value: '11'
newvalue: 'Sleeping Until Power Return'
- value: '12'
newvalue: 'On Smart Trim'
- value: '13'
newvalue: 'Eco Mode'
- value: '14'
newvalue: 'Hot Standby'
- value: '15'
newvalue: 'On Battery Test'
- value: '16'
newvalue: 'Emergency Static Bypass'
- value: '17'
newvalue: 'Static Bypass Standby'
- value: '18'
newvalue: 'Power Saving Mode'
- value: '19'
newvalue: 'Spot Mode'
- value: '20'
newvalue: E-Conversion
- value: '21'
newvalue: 'Charger Spotmode'
- value: '22'
newvalue: 'Inverter Spotmode'
- value: '23'
newvalue: 'Active Load'
- value: '24'
newvalue: 'Battery Discharge Spotmode'
- value: '25'
newvalue: 'Inverter Standby'
- value: '26'
newvalue: 'Charger Only'
- uuid: 12058346f9e046388767c2939bbed2cf
name: zabbix.host.available
mappings:
- value: '0'
newvalue: 'not available'
- value: '1'
newvalue: available
- value: '2'
newvalue: unknown
triggers:
- uuid: 6f0fbe74ad4945e987e7ffdfa741d92f
expression: |
(last(/APC Smart-UPS SRT 8000 by SNMP/system.hw.uptime[hrSystemUptime.0])>0 and last(/APC Smart-UPS SRT 8000 by SNMP/system.hw.uptime[hrSystemUptime.0])<10m)
or (last(/APC Smart-UPS SRT 8000 by SNMP/system.hw.uptime[hrSystemUptime.0])=0 and last(/APC Smart-UPS SRT 8000 by SNMP/system.net.uptime[sysUpTime.0])<10m)
name: 'APC Smart-UPS: Host has been restarted'
event_name: 'APC Smart-UPS: {HOST.NAME} has been restarted (uptime < 10m)'
priority: WARNING
description: 'Uptime is less than 10 minutes.'
manual_close: 'YES'
dependencies:
- name: 'APC Smart-UPS: No SNMP data collection'
expression: 'max(/APC Smart-UPS SRT 8000 by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
tags:
- tag: scope
value: notice
graphs:
- uuid: e040a4ac7b024c4c878c8145b34969aa
name: 'APC Smart-UPS SRT 8000: Capacity of the UPS batteries'
type: PIE
graph_items:
- color: 199C0D
item:
host: 'APC Smart-UPS SRT 8000 by SNMP'
key: 'battery.capacity[upsHighPrecBatteryCapacity]'
- uuid: 7cd3c6f5dcaf40e28cbc0ac9e3c35d7a
name: 'APC Smart-UPS SRT 8000: Output'
graph_items:
- color: 199C0D
item:
host: 'APC Smart-UPS SRT 8000 by SNMP'
key: 'output.current[upsHighPrecOutputCurrent]'
- sortorder: '1'
color: F63100
item:
host: 'APC Smart-UPS SRT 8000 by SNMP'
key: 'output.load[upsHighPrecOutputLoad]'
- uuid: 2fe4eba0af2745c994ad3d6abfe30140
name: 'APC Smart-UPS SRT 8000: Voltage'
graph_items:
- color: 199C0D
item:
host: 'APC Smart-UPS SRT 8000 by SNMP'
key: 'input.voltage[upsHighPrecInputLineVoltage]'
- sortorder: '1'
color: F63100
item:
host: 'APC Smart-UPS SRT 8000 by SNMP'
key: 'output.voltage[upsHighPrecOutputVoltage]'