zabbix_export:
version: '7.0'
template_groups:
- uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
name: Templates/Power
templates:
- uuid: 340ec6917c274ead8fab36925e57f30a
template: 'APC Smart-UPS RT 1000 RM XL by SNMP'
name: 'APC Smart-UPS RT 1000 RM XL by SNMP'
description: |
Template Power APC Smart-UPS RT 1000 RM XL
MIBs used:
HOST-RESOURCES-MIB
PowerNet-MIB
SNMPv2-MIB
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
Generated by official Zabbix template tool "Templator"
vendor:
name: Zabbix
version: 7.0-4
groups:
- name: Templates/Power
items:
- uuid: 94c5c76b7e09402bb221827ee1fea5bc
name: 'Battery capacity'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.1.0]'
key: 'battery.capacity[upsHighPrecBatteryCapacity]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The remaining battery capacity expressed as
percentage of full capacity.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: 8ab182b26a0443539a1a114767d8acd7
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}'
name: 'APC Smart-UPS: Battery has low capacity'
event_name: 'APC Smart-UPS: Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%)'
opdata: 'Current capacity: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: capacity
- uuid: 1a52452353b443d6b965293fda3b16b9
name: 'External battery packs count'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.5.0]'
key: 'battery.external_packs_count[upsAdvBatteryNumOfBattPacks]'
delay: 1h
description: |
MIB: PowerNet-MIB
The number of external battery packs connected to the UPS. If
the UPS does not use smart cells then the agent reports
ERROR_NO_SUCH_NAME.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: 7a887ae254b04b19bac605bb36141767
name: 'Battery last replace date'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.1.3.0]'
key: 'battery.last_replace_date[upsBasicBatteryLastReplaceDate]'
delay: 1h
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The date when the UPS system's batteries were last replaced
in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value
is originally set at the factory. When the UPS batteries
are replaced, this value should be reset by the administrator.
For Symmetra PX 250/500 this OID is read-only and is configurable in the local display only.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: 8f4351d23be04a3abee1e6edb746a9ec
name: 'Battery replace indicator'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.4.0]'
key: 'battery.replace_indicator[upsAdvBatteryReplaceIndicator]'
description: |
MIB: PowerNet-MIB
Indicates whether the UPS batteries need replacement.
valuemap:
name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: ab0db1327cf04a9c9a9ee757f0869603
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2'
name: 'APC Smart-UPS: Battery needs replacement'
priority: HIGH
description: 'A battery installed has an internal error condition.'
tags:
- tag: scope
value: notice
- uuid: f151210b9cd749b2b3e5af2145733c82
name: 'Battery runtime remaining'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.3.0]'
key: 'battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]'
value_type: FLOAT
units: s
description: |
MIB: PowerNet-MIB
The UPS battery run time remaining before battery
exhaustion.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.01'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: a631704123c2498aa8ce973e36c13698
name: 'Battery status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.1.1.0]'
key: 'battery.status[upsBasicBatteryStatus]'
description: |
MIB: PowerNet-MIB
The status of the UPS batteries. A batteryLow(3) value
indicates the UPS will be unable to sustain the current
load, and its services will be lost if power is not restored.
The amount of run time in reserve at the time of low battery
can be configured by the upsAdvConfigLowBatteryRunTime.
A batteryInFaultCondition(4)value indicates that a battery
installed has an internal error condition.
valuemap:
name: 'PowerNet-MIB::upsBasicBatteryStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
triggers:
- uuid: c8787a09c2ea4aeb977b868ae0a3218b
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/battery.status[upsBasicBatteryStatus])=4'
name: 'APC Smart-UPS: Battery has an internal error condition'
priority: AVERAGE
description: 'A battery installed has an internal error condition.'
tags:
- tag: scope
value: notice
- uuid: 40d1fdcec63d4c3785b5ba77fbd14ee7
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/battery.status[upsBasicBatteryStatus])=3'
name: 'APC Smart-UPS: Battery is Low'
priority: AVERAGE
description: 'The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.'
tags:
- tag: scope
value: capacity
- uuid: c03e15aaf58f4056b88677c44c5d7d87
name: 'Battery temperature'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.2.0]'
key: 'battery.temperature[upsHighPrecBatteryTemperature]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The current internal UPS temperature in Celsius.
Temperatures below zero read as 0.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: temperature
triggers:
- uuid: e2debe06675d4d4584b60b768633887b
expression: 'min(/APC Smart-UPS RT 1000 RM XL by SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
name: 'APC Smart-UPS: Battery has high temperature'
event_name: 'APC Smart-UPS: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})'
opdata: 'Current temperature: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 4b456cb5c0224b31a2f8b4bb40d8203b
name: 'Battery voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.4.0]'
key: 'battery.voltage[upsHighPrecBatteryActualVoltage]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The actual battery bus voltage in Volts.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 0a12f157ae844129a35084b5ab0a8eab
name: 'Input fail cause'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.3.2.5.0]'
key: 'input.fail[upsAdvInputLineFailCause]'
description: |
MIB: PowerNet-MIB
The reason for the occurrence of the last transfer to UPS
battery power. The variable is set to:
- noTransfer(1) -- if there is no transfer yet.
- highLineVoltage(2) -- if the transfer to battery is caused
by an over voltage greater than the high transfer voltage.
- brownout(3) -- if the duration of the outage is greater than
five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- blackout(4) -- if the duration of the outage is greater than five
seconds and the line voltage is between 40% of the rated
output voltage and ground.
- smallMomentarySag(5) -- if the duration of the outage is less
than five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- deepMomentarySag(6) -- if the duration of the outage is less
than five seconds and the line voltage is between 40% of the
rated output voltage and ground. The variable is set to
- smallMomentarySpike(7) -- if the line failure is caused by a
rate of change of input voltage less than ten volts per cycle.
- largeMomentarySpike(8) -- if the line failure is caused by
a rate of change of input voltage greater than ten volts per cycle.
- selfTest(9) -- if the UPS was commanded to do a self test.
- rateOfVoltageChange(10) -- if the failure is due to the rate of change of
the line voltage.
valuemap:
name: 'PowerNet-MIB::upsAdvInputLineFailCause'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 0ceb5a6d71f440fcbd2da06b0cc1bbb3
name: 'Input frequency'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.3.3.4.0]'
key: 'input.frequency[upsHighPrecInputFrequency]'
value_type: FLOAT
units: Hz
description: |
MIB: PowerNet-MIB
The current input frequency to the UPS system in Hz.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: b29cd7e33c1e4e16b10fe436c1f7e6d6
expression: 'min(/APC Smart-UPS RT 1000 RM XL by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 RM XL by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS RT 1000 RM XL by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})'
name: 'APC Smart-UPS: Unacceptable input frequency'
event_name: 'APC Smart-UPS: Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD})'
opdata: 'Current frequency: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: d7281586af02462a9a2f511c0a5741eb
name: 'Input voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.3.3.1.0]'
key: 'input.voltage[upsHighPrecInputLineVoltage]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The current utility line voltage in VAC.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: d38f2151f0eb486e8d44b72a2e361a5f
expression: 'min(/APC Smart-UPS RT 1000 RM XL by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 RM XL by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 RM XL by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})'
name: 'APC Smart-UPS: Unacceptable input voltage'
event_name: 'APC Smart-UPS: Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current voltage: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 145d3bf81b00427aad5563a4feb7aea1
name: 'Output current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.3.4.0]'
key: 'output.current[upsHighPrecOutputCurrent]'
value_type: FLOAT
units: A
description: |
MIB: PowerNet-MIB
The current in amperes drawn by the load on the UPS.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: cd7b2c1b12df4fd19f37485aa380b295
name: 'Output load'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.3.3.0]'
key: 'output.load[upsHighPrecOutputLoad]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The current UPS load expressed as percentage
of rated capacity.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
triggers:
- uuid: 57197c601f8a433d8ccdcb040d047f6f
expression: 'min(/APC Smart-UPS RT 1000 RM XL by SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}'
name: 'APC Smart-UPS: Output load is high'
event_name: 'APC Smart-UPS: Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD})'
opdata: 'Current load: {ITEM.LASTVALUE1}'
priority: HIGH
description: 'A battery installed has an internal error condition.'
tags:
- tag: scope
value: notice
- uuid: 3170d441ede24494b9570b6d318cc05f
name: 'Output status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.1.1.0]'
key: 'output.status[upsBasicOutputStatus]'
description: |
MIB: PowerNet-MIB
The current state of the UPS. If the UPS is unable to
determine the state of the UPS this variable is set
to unknown(1).
During self-test most UPSes report onBattery(3) but
some that support it will report onBatteryTest(15).
To determine self-test status across all UPSes, refer
to the upsBasicStateOutputState OID.
valuemap:
name: 'PowerNet-MIB::upsBasicOutputStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
triggers:
- uuid: e9289d8f4e124097990e2af98e916368
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/output.status[upsBasicOutputStatus])=16'
name: 'APC Smart-UPS: UPS is Emergency Static Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 13735964f51d4d1bb17e6b0587a43020
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/output.status[upsBasicOutputStatus])=10'
name: 'APC Smart-UPS: UPS is Hardware Failure Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: d74ae82199884a7fb4a20b48f3c7ff1f
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/output.status[upsBasicOutputStatus])=7'
name: 'APC Smart-UPS: UPS is Off'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 4df5271075904c228a0372d5f667530e
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/output.status[upsBasicOutputStatus])=3'
name: 'APC Smart-UPS: UPS is on battery'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 3f02d9cb7f5142599e59e7781808e5c3
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/output.status[upsBasicOutputStatus])=4'
name: 'APC Smart-UPS: UPS is on Smart Boost'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 515ad03892694fd4a2f2350a6bb8af6f
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/output.status[upsBasicOutputStatus])=12'
name: 'APC Smart-UPS: UPS is On Smart Trim'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 2a2d35e4e4674b6aa49068a7970caa03
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/output.status[upsBasicOutputStatus])=8'
name: 'APC Smart-UPS: UPS is Rebooting'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: ef1ddb8869074847b70e8f669883c56b
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/output.status[upsBasicOutputStatus])=11'
name: 'APC Smart-UPS: UPS is Sleeping Until Power Return'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 0d6e4e664ddf425e8c03155802fe45be
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/output.status[upsBasicOutputStatus])=6'
name: 'APC Smart-UPS: UPS is Software Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 12a3a33152824ffe863a8d79c1372195
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/output.status[upsBasicOutputStatus])=9'
name: 'APC Smart-UPS: UPS is Switched Bypass'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 273c561c2afb4d78be86218e370c9a1f
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/output.status[upsBasicOutputStatus])=5'
name: 'APC Smart-UPS: UPS is Timed Sleeping'
priority: AVERAGE
tags:
- tag: scope
value: notice
- uuid: 6c7d7d803647478c8f2a79875457110c
name: 'Output voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.4.3.1.0]'
key: 'output.voltage[upsHighPrecOutputVoltage]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The output voltage of the UPS system in VAC.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: d08fb7e3fae84d2cbae64ab9771ffcdc
name: 'SNMP traps (fallback)'
type: SNMP_TRAP
key: snmptrap.fallback
delay: '0'
value_type: LOG
trends: '0'
description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items'
logtimefmt: 'hh:mm:sszyyyy/MM/dd'
tags:
- tag: component
value: network
- uuid: da60acc731a64257a90512b5c70d1e92
name: 'System contact details'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.4.0]'
key: 'system.contact[sysContact.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
The textual identification of the contact person for this managed
node, together with information on how to contact this person. If no contact
information is known, the value is the zero-length string.
inventory_link: CONTACT
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 12h
tags:
- tag: component
value: system
- uuid: 01302a36cafd421c90d746f785c83f3f
name: 'System description'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.1.0]'
key: 'system.descr[sysDescr.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
A textual description of the entity. This value should
include the full name and version identification of the system's hardware type, software operating-system, and
networking software.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 12h
tags:
- tag: component
value: system
- uuid: 60bef30ff568425eb5e4c5e6dc861e79
name: 'Uptime (hardware)'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.25.1.1.0]'
key: 'system.hw.uptime[hrSystemUptime.0]'
delay: 30s
trends: '0'
units: uptime
description: |
MIB: HOST-RESOURCES-MIB
The amount of time since this host was last initialized. Note that this is different from sysUpTime in the SNMPv2-MIB [RFC1907] because sysUpTime is the uptime of the network management portion of the system.
preprocessing:
- type: CHECK_NOT_SUPPORTED
parameters:
- '-1'
error_handler: CUSTOM_VALUE
error_handler_params: '0'
- type: MULTIPLIER
parameters:
- '0.01'
tags:
- tag: component
value: system
- uuid: d0351d1bc1dc4f1b853fe64d456b3570
name: 'System location'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.6.0]'
key: 'system.location[sysLocation.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
The physical location of this node (e.g., `telephone closet, 3rd floor'). If the location is unknown, the value is the zero-length string.
inventory_link: LOCATION
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: system
- uuid: 866889bb71e949c18520bf8fefd3e7ea
name: Model
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.1.1.1.0]'
key: 'system.model[upsBasicIdentModel]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The UPS model name (e.g. 'APC Smart-UPS 600').
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: 482bec6573f249abbb721f2ec90def3b
name: 'System name'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.5.0]'
key: 'system.name[sysName.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
An administratively-assigned name for this managed node.By convention, this is the node's fully-qualified domain name. If the name is unknown, the value is the zero-length string.
inventory_link: NAME
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: system
triggers:
- uuid: b13b087b9828426aac82a281071ceb8b
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS RT 1000 RM XL by SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS RT 1000 RM XL by SNMP/system.name[sysName.0]))>0'
name: 'APC Smart-UPS: System name has changed'
event_name: 'APC Smart-UPS: System name has changed (new name: {ITEM.VALUE})'
priority: INFO
description: 'The name of the system has changed. Acknowledge to close the problem manually.'
manual_close: 'YES'
tags:
- tag: scope
value: notice
- tag: scope
value: security
- uuid: 336ef2166914449fafa13ab08fe7c7a1
name: 'Uptime (network)'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.3.0]'
key: 'system.net.uptime[sysUpTime.0]'
delay: 30s
trends: '0'
units: uptime
description: |
MIB: SNMPv2-MIB
The time (in hundredths of a second) since the network management portion of the system was last re-initialized.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.01'
tags:
- tag: component
value: system
- uuid: 1c00c980ff284fb2bafb8358cc477d13
name: 'System object ID'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.2.1.1.2.0]'
key: 'system.objectid[sysObjectID.0]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: SNMPv2-MIB
The vendor's authoritative identification of the network management subsystem contained in the entity. This value is allocated within the SMI enterprises subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1 to its `Fred Router'.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: system
- uuid: 269ce166bb904fa8b11fc2fdf1f67d76
name: 'Serial number'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.1.2.3.0]'
key: 'system.sn[upsAdvIdentSerialNumber]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
An 8-character string identifying the serial number of
the UPS internal microprocessor. This number is set at
the factory. NOTE: This number does NOT correspond to
the serial number on the rear of the UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: f4f9ebb1e55b41a5a6e470a541e136bc
name: 'SNMP agent availability'
type: INTERNAL
key: 'zabbix[host,snmp,available]'
description: |
Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.
Possible values:
0 - not available
1 - available
2 - unknown
valuemap:
name: zabbix.host.available
tags:
- tag: component
value: health
- tag: component
value: network
triggers:
- uuid: 53263bf0536d479785b45883b9b7ab21
expression: 'max(/APC Smart-UPS RT 1000 RM XL by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
name: 'APC Smart-UPS: No SNMP data collection'
opdata: 'Current state: {ITEM.LASTVALUE1}'
priority: WARNING
description: 'SNMP is not available for polling. Please check device connectivity and SNMP settings.'
tags:
- tag: scope
value: availability
discovery_rules:
- uuid: 67fa8bb8687b4a36b8d32cda72083966
name: 'External bad battery packs discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#EXTERNAL_PACKS},1.3.6.1.4.1.318.1.1.1.2.2.6]'
key: battery.packs.bad.discovery
delay: 1h
filter:
evaltype: AND
conditions:
- macro: '{#EXTERNAL_PACKS}'
value: '-1'
operator: NOT_MATCHES_REGEX
formulaid: A
description: 'Discovery of the number of external defective battery packs.'
item_prototypes:
- uuid: b144bee7e8464540bbcd8a3c28ce7e9f
name: '{#SNMPINDEX}: External battery packs bad'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.2.6.0]'
key: 'battery.external_packs_bad[upsAdvBatteryNumOfBadBattPacks.{#SNMPINDEX}]'
delay: 15m
description: |
MIB: PowerNet-MIB
The number of external battery packs connected to the UPS that
are defective. If the UPS does not use smart cells then the
agent reports ERROR_NO_SUCH_NAME.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: b4a8277fdf6f4e76a641690aaf6e7faa
name: 'External battery packs discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#CARTRIDGE_STATUS},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7,{#BATTERY_PACK},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1,{#CARTRIDGE_INDEX},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2]'
key: battery.packs.discovery
delay: 1h
filter:
evaltype: AND
conditions:
- macro: '{#CARTRIDGE_STATUS}'
value: ^$
operator: NOT_MATCHES_REGEX
formulaid: A
item_prototypes:
- uuid: 9715d1700f5f49ffaf3ff35c666f50cf
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery estimated replace date'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8.{#SNMPINDEX}]'
key: 'battery.estimated_replace_date[upsHighPrecBatteryPackCartridgeReplaceDate.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
delay: 1h
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The battery cartridge estimated battery replace date.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- tag: component
value: power
- uuid: 2e7f6a940840406cb17bb1af20936326
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7.{#SNMPINDEX}]'
key: 'battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The battery cartridge health.
bit 0 Battery lifetime okay
bit 1 Battery lifetime near end, order replacement cartridge
bit 2 Battery lifetime exceeded, replace battery
bit 3 Battery lifetime near end acknowledged, order replacement cartridge
bit 4 Battery lifetime exceeded acknowledged, replace battery
bit 5 Battery measured lifetime near end, order replacement cartridge
bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: c1eefbeeb0d146c3bea5cae929d0c30b
expression: 'find(/APC Smart-UPS RT 1000 RM XL by SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1'
name: 'APC Smart-UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay'
opdata: 'Current bit set: {ITEM.LASTVALUE1}'
priority: WARNING
description: |
The battery cartridge health.
bit 0 Battery lifetime okay
bit 1 Battery lifetime near end, order replacement cartridge
bit 2 Battery lifetime exceeded, replace battery
bit 3 Battery lifetime near end acknowledged, order replacement cartridge
bit 4 Battery lifetime exceeded acknowledged, replace battery
bit 5 Battery measured lifetime near end, order replacement cartridge
bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge
tags:
- tag: scope
value: notice
- uuid: ad5ce159270e41899665be0a9f9697e1
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10.{#SNMPINDEX}]'
key: 'battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
The status of the UPS batteries. A batteryLow(3) value
indicates the UPS will be unable to sustain the current
load, and its services will be lost if power is not restored.
The amount of run time in reserve at the time of low battery
can be configured by the upsAdvConfigLowBatteryRunTime.
A batteryInFaultCondition(4)value indicates that a battery
installed has an internal error condition.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: 28b8fb69a85549288cf0e26b9ca0a2cf
expression: 'find(/APC Smart-UPS RT 1000 RM XL by SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0'
name: 'APC Smart-UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay'
opdata: 'Current bit set: {ITEM.LASTVALUE1}'
priority: WARNING
description: |
The battery cartridge status:
bit 0 Disconnected
bit 1 Overvoltage
bit 2 NeedsReplacement
bit 3 OvertemperatureCritical
bit 4 Charger
bit 5 TemperatureSensor
bit 6 BusSoftStart
bit 7 OvertemperatureWarning
bit 8 GeneralError
bit 9 Communication
bit 10 DisconnectedFrame
bit 11 FirmwareMismatch
tags:
- tag: scope
value: notice
- uuid: 1628e49e7f7b468ca2dee87a80321b44
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperature'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5.{#SNMPINDEX}]'
key: 'battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The current internal UPS temperature in Celsius.
Temperatures below zero read as 0.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: temperature
trigger_prototypes:
- uuid: fa007fcfbe7c499d8f97a808991f2800
expression: 'min(/APC Smart-UPS RT 1000 RM XL by SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
name: 'APC Smart-UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature'
event_name: 'APC Smart-UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})'
opdata: 'Current temperature: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: 7c2aec802cfa4b0292e9d1daa94aee05
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4.{#SNMPINDEX}]'
key: 'system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]'
delay: 15m
value_type: CHAR
trends: '0'
description: |
MIB: PowerNet-MIB
An 8-character string identifying the serial number of
the UPS internal microprocessor. This number is set at
the factory. NOTE: This number does NOT correspond to
the serial number on the rear of the UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: inventory
- uuid: 59467725274d4dba8e839d167cabe693
name: 'External sensor port 1 discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#EXTERNAL_SENSOR1_NAME},1.3.6.1.4.1.318.1.1.25.1.2.1.3]'
key: external.sensor1.discovery
delay: 1h
description: uioSensorStatusTable
item_prototypes:
- uuid: 0336e646ea6247ad8ef4254dff64623e
name: '{#EXTERNAL_SENSOR1_NAME}: Humidity sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.1.7.{#SNMPINDEX}]'
key: 'external.sensor.humidity[uioSensorStatusHumidity.1.{#SNMPINDEX}]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The sensor's current humidity reading - a relative humidity
percentage. -1 indicates an invalid reading due to either a
sensor that doesn't read humidity or lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: humidity
- tag: component
value: power
- uuid: 137fdf42e0ab476e86e7b0b3bc87d5cc
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.1.9.{#SNMPINDEX}]'
key: 'external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}]'
description: |
MIB: PowerNet-MIB
The alarm status of the sensor. Possible values:
uioNormal (1),
uioWarning (2),
uioCritical (3),
sensorStatusNotApplicable (4)
valuemap:
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: 175c1def62ac412eb5f9ef015a9b8ac3
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3'
name: 'APC Smart-UPS: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical'
priority: HIGH
description: 'The external sensor has returned a value greater than the critical threshold.'
tags:
- tag: scope
value: notice
- uuid: e7610cf822674591bea6ed7ba5e4198d
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4'
name: 'APC Smart-UPS: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable'
priority: INFO
description: 'The external sensor does not work or is not connected.'
tags:
- tag: scope
value: notice
- uuid: 44353bbfcfbe42e59d2e58b544d32b43
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2'
name: 'APC Smart-UPS: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning'
priority: AVERAGE
description: 'The external sensor has returned a value greater than the warning threshold.'
tags:
- tag: scope
value: notice
- uuid: b97e3012569840f1bb7da5f5403db6e0
name: '{#EXTERNAL_SENSOR1_NAME}: Temperature sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.1.6.{#SNMPINDEX}]'
key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.1.{#SNMPINDEX}]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The sensor's current temperature reading in Celsius.
-1 indicates an invalid reading due to lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- tag: component
value: temperature
overrides:
- name: Temp
step: '1'
filter:
conditions:
- macro: '{#EXTERNAL_SENSOR1_NAME}'
value: Temp
formulaid: A
operations:
- operationobject: ITEM_PROTOTYPE
operator: LIKE
value: Humidity
discover: NO_DISCOVER
- uuid: d4b34302c7d74f83a409947f2eed37b0
name: 'External sensor port 2 discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#EXTERNAL_SENSOR2_NAME},1.3.6.1.4.1.318.1.1.25.1.2.2.3]'
key: external.sensor2.discovery
delay: 1h
description: uioSensorStatusTable
item_prototypes:
- uuid: 872bd20f6f5d453490324cd8ea5be7c2
name: '{#EXTERNAL_SENSOR2_NAME}: Humidity sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.2.7.{#SNMPINDEX}]'
key: 'external.sensor.humidity[uioSensorStatusHumidity.2.{#SNMPINDEX}]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The sensor's current humidity reading - a relative humidity
percentage. -1 indicates an invalid reading due to either a
sensor that doesn't read humidity or lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: humidity
- tag: component
value: power
- uuid: e10189271da445a494d274d99269ab75
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.2.9.{#SNMPINDEX}]'
key: 'external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}]'
description: |
MIB: PowerNet-MIB
The alarm status of the sensor. Possible values:
uioNormal (1),
uioWarning (2),
uioCritical (3),
sensorStatusNotApplicable (4)
valuemap:
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: health
- tag: component
value: power
trigger_prototypes:
- uuid: 5e937c991aa146fe98c1a4f868be6b70
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3'
name: 'APC Smart-UPS: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical'
priority: HIGH
description: 'The external sensor has returned a value greater than the critical threshold.'
tags:
- tag: scope
value: notice
- uuid: f8dd227322784a708ae6297e796177f9
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4'
name: 'APC Smart-UPS: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable'
priority: INFO
description: 'The external sensor does not work or is not connected.'
tags:
- tag: scope
value: notice
- uuid: b142607d33e9447d88f23fc3ff7dc11d
expression: 'last(/APC Smart-UPS RT 1000 RM XL by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2'
name: 'APC Smart-UPS: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning'
priority: AVERAGE
description: 'The external sensor has returned a value greater than the warning threshold.'
tags:
- tag: scope
value: notice
- uuid: 11cac46ee1834e7c816a2cd9dcc02e82
name: '{#EXTERNAL_SENSOR2_NAME}: Temperature sensor'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.25.1.2.2.6.{#SNMPINDEX}]'
key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.2.{#SNMPINDEX}]'
value_type: FLOAT
units: ℃
description: |
MIB: PowerNet-MIB
The sensor's current temperature reading in Celsius.
-1 indicates an invalid reading due to lost communications.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- tag: component
value: temperature
overrides:
- name: Temp
step: '1'
filter:
conditions:
- macro: '{#EXTERNAL_SENSOR2_NAME}'
value: Temp
formulaid: A
operations:
- operationobject: ITEM_PROTOTYPE
operator: LIKE
value: Humidity
discover: NO_DISCOVER
- uuid: 525a204918834dbfa788a3681c2d0527
name: 'Input phases discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.2.3.1.2.1.1]'
key: input.phases.discovery
delay: 1h
description: 'The input phase identifier. OID upsPhaseInputPhaseIndex.1.1'
item_prototypes:
- uuid: fd698a699cd546418802964c6157290e
name: '{#PHASEINDEX}: Phase input current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.2.3.1.6.1.1.{#PHASEINDEX}]'
key: 'phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: A
description: |
MIB: PowerNet-MIB
The input current in 0.1 amperes, or -0.1 if it's
unsupported by this UPS.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 1baaad88e9064b92b453fb2c1c7d73d5
name: '{#PHASEINDEX}: Phase input voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.2.3.1.3.1.1.{#PHASEINDEX}]'
key: 'phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The input voltage in VAC, or -1 if it's unsupported
by this UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
trigger_prototypes:
- uuid: 971301abf4d6457da125fd7ebd903728
expression: 'min(/APC Smart-UPS RT 1000 RM XL by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 RM XL by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
name: 'APC Smart-UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage'
event_name: 'APC Smart-UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
- uuid: cbd6b174482c4769887fc1aa2dc2ad5a
name: 'Output phases discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.3.3.1.2.1.1]'
key: output.phases.discovery
delay: 1h
description: 'The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1'
item_prototypes:
- uuid: 84ec9adaa7c94f10b55ae9968449d673
name: '{#PHASEINDEX}: Phase output current'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.3.3.1.4.1.1.{#PHASEINDEX}]'
key: 'phase.output.current[upsPhaseOutputCurrent.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: A
description: |
MIB: PowerNet-MIB
The output current in 0.1 amperes drawn
by the load on the UPS, or -1 if it's unsupported
by this UPS.
preprocessing:
- type: MULTIPLIER
parameters:
- '0.1'
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 6d1812674e5646f8acf2ea47acf05a6d
name: '{#PHASEINDEX}: Phase output load, %'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.3.3.1.10.1.1.{#PHASEINDEX}]'
key: 'phase.output.load.percent[upsPhaseOutputPercentLoad.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: '%'
description: |
MIB: PowerNet-MIB
The percentage of the UPS load capacity in VA at
redundancy @ (n + x) presently being used on this
output phase, or -1 if it's unsupported by this UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
- uuid: 3c0573d586b24e53aeebb6c44b907bbd
name: '{#PHASEINDEX}: Phase output voltage'
type: SNMP_AGENT
snmp_oid: 'get[1.3.6.1.4.1.318.1.1.1.9.3.3.1.3.1.1.{#PHASEINDEX}]'
key: 'phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]'
value_type: FLOAT
units: V
description: |
MIB: PowerNet-MIB
The output voltage in VAC, or -1 if it's unsupported
by this UPS.
preprocessing:
- type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- 6h
tags:
- tag: component
value: power
trigger_prototypes:
- uuid: d7167a129de146d19218edb85c82c69b
expression: 'min(/APC Smart-UPS RT 1000 RM XL by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 RM XL by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
name: 'APC Smart-UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage'
event_name: 'APC Smart-UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}'
priority: HIGH
tags:
- tag: scope
value: notice
tags:
- tag: class
value: power
- tag: target
value: apc
- tag: target
value: apc-smart-ups-rt-1000-rm-xl
macros:
- macro: '{$BATTERY.CAPACITY.MIN.WARN}'
value: '50'
description: 'Minimum battery capacity percentage for trigger expression.'
- macro: '{$BATTERY.TEMP.MAX.WARN}'
value: '55'
description: 'Maximum battery temperature for trigger expression.'
- macro: '{$SNMP.TIMEOUT}'
value: 5m
description: 'The time interval for SNMP agent availability trigger expression.'
- macro: '{$TIME.PERIOD}'
value: 15m
description: 'Time period for trigger expression.'
- macro: '{$UPS.INPUT_FREQ.MAX.WARN}'
value: '50.3'
description: 'Maximum input frequency for trigger expression.'
- macro: '{$UPS.INPUT_FREQ.MIN.WARN}'
value: '49.7'
description: 'Minimum input frequency for trigger expression.'
- macro: '{$UPS.INPUT_VOLT.MAX.WARN}'
value: '243'
description: 'Maximum input voltage for trigger expression.'
- macro: '{$UPS.INPUT_VOLT.MIN.WARN}'
value: '197'
description: 'Minimum input voltage for trigger expression.'
- macro: '{$UPS.OUTPUT.MAX.WARN}'
value: '80'
description: 'Maximum output load in % for trigger expression.'
dashboards:
- uuid: 4b5beff567794c0ca4bb0d0b0868e703
name: 'APC Smart-UPS RT 1000 RM XL: General'
pages:
- name: 'APC Smart-UPS RT 1000 RM XL: General'
widgets:
- type: graph
name: Voltage
width: '36'
height: '5'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'APC Smart-UPS RT 1000 RM XL by SNMP'
name: 'APC Smart-UPS RT 1000 RM XL: Voltage'
- type: STRING
name: reference
value: AAAAA
- type: graph
name: 'Capacity of the UPS batteries'
'y': '5'
width: '36'
height: '5'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'APC Smart-UPS RT 1000 RM XL by SNMP'
name: 'APC Smart-UPS RT 1000 RM XL: Capacity of the UPS batteries'
- type: STRING
name: reference
value: AAAAC
- type: graph
name: Output
x: '36'
width: '36'
height: '5'
fields:
- type: GRAPH
name: graphid.0
value:
host: 'APC Smart-UPS RT 1000 RM XL by SNMP'
name: 'APC Smart-UPS RT 1000 RM XL: Output'
- type: STRING
name: reference
value: AAAAB
valuemaps:
- uuid: 7cf932d3b9304f2cb151134e9ea3be82
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
mappings:
- value: '1'
newvalue: Normal
- value: '2'
newvalue: Warning
- value: '3'
newvalue: Critical
- value: '4'
newvalue: 'Not applicable'
- uuid: 63c5f0e1601947e5a02abd25a07a9af4
name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator'
mappings:
- value: '1'
newvalue: 'no Battery Needs Replacing'
- value: '2'
newvalue: 'battery Needs Replacing'
- uuid: 70d097ce846c45aeb3c8be031c427511
name: 'PowerNet-MIB::upsAdvInputLineFailCause'
mappings:
- value: '1'
newvalue: 'no Transfer'
- value: '2'
newvalue: 'High Line Voltage'
- value: '3'
newvalue: Brownout
- value: '4'
newvalue: Blackout
- value: '5'
newvalue: 'Small Momentary Sag'
- value: '6'
newvalue: 'Deep Momentary Sag'
- value: '7'
newvalue: 'Small Momentary Spike'
- value: '8'
newvalue: 'Large Momentary Spike'
- value: '9'
newvalue: 'Self Test'
- value: '10'
newvalue: 'Rate of Voltage Change'
- uuid: 3424a9229a134b47b8544d611be082fb
name: 'PowerNet-MIB::upsBasicBatteryStatus'
mappings:
- value: '1'
newvalue: Unknown
- value: '2'
newvalue: Normal
- value: '3'
newvalue: Low
- value: '4'
newvalue: 'In Fault Condition'
- uuid: 05a60d9c47274f5a8f6c92efe8158b8e
name: 'PowerNet-MIB::upsBasicOutputStatus'
mappings:
- value: '1'
newvalue: Unknown
- value: '2'
newvalue: Online
- value: '3'
newvalue: 'On Battery'
- value: '4'
newvalue: 'On Smart Boost'
- value: '5'
newvalue: 'Timed Sleeping'
- value: '6'
newvalue: 'Software Bypass'
- value: '7'
newvalue: 'Off'
- value: '8'
newvalue: Rebooting
- value: '9'
newvalue: 'Switched Bypass'
- value: '10'
newvalue: 'Hardware Failure Bypass'
- value: '11'
newvalue: 'Sleeping Until Power Return'
- value: '12'
newvalue: 'On Smart Trim'
- value: '13'
newvalue: 'Eco Mode'
- value: '14'
newvalue: 'Hot Standby'
- value: '15'
newvalue: 'On Battery Test'
- value: '16'
newvalue: 'Emergency Static Bypass'
- value: '17'
newvalue: 'Static Bypass Standby'
- value: '18'
newvalue: 'Power Saving Mode'
- value: '19'
newvalue: 'Spot Mode'
- value: '20'
newvalue: E-Conversion
- value: '21'
newvalue: 'Charger Spotmode'
- value: '22'
newvalue: 'Inverter Spotmode'
- value: '23'
newvalue: 'Active Load'
- value: '24'
newvalue: 'Battery Discharge Spotmode'
- value: '25'
newvalue: 'Inverter Standby'
- value: '26'
newvalue: 'Charger Only'
- uuid: d4ee88b3cf5d4d95b27be2e7b2f20e3c
name: zabbix.host.available
mappings:
- value: '0'
newvalue: 'not available'
- value: '1'
newvalue: available
- value: '2'
newvalue: unknown
triggers:
- uuid: 87ebd137f2744ae6879d6fd9d51314ef
expression: |
(last(/APC Smart-UPS RT 1000 RM XL by SNMP/system.hw.uptime[hrSystemUptime.0])>0 and last(/APC Smart-UPS RT 1000 RM XL by SNMP/system.hw.uptime[hrSystemUptime.0])<10m)
or (last(/APC Smart-UPS RT 1000 RM XL by SNMP/system.hw.uptime[hrSystemUptime.0])=0 and last(/APC Smart-UPS RT 1000 RM XL by SNMP/system.net.uptime[sysUpTime.0])<10m)
name: 'APC Smart-UPS: Host has been restarted'
event_name: 'APC Smart-UPS: {HOST.NAME} has been restarted (uptime < 10m)'
priority: WARNING
description: 'Uptime is less than 10 minutes.'
manual_close: 'YES'
dependencies:
- name: 'APC Smart-UPS: No SNMP data collection'
expression: 'max(/APC Smart-UPS RT 1000 RM XL by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
tags:
- tag: scope
value: notice
graphs:
- uuid: 566f3eed2c324e5faa80f4170cb40b5b
name: 'APC Smart-UPS RT 1000 RM XL: Capacity of the UPS batteries'
type: PIE
graph_items:
- color: 199C0D
item:
host: 'APC Smart-UPS RT 1000 RM XL by SNMP'
key: 'battery.capacity[upsHighPrecBatteryCapacity]'
- uuid: 09da5776f4ff4e978e488a12f33dc8bc
name: 'APC Smart-UPS RT 1000 RM XL: Output'
graph_items:
- color: 199C0D
item:
host: 'APC Smart-UPS RT 1000 RM XL by SNMP'
key: 'output.current[upsHighPrecOutputCurrent]'
- sortorder: '1'
color: F63100
item:
host: 'APC Smart-UPS RT 1000 RM XL by SNMP'
key: 'output.load[upsHighPrecOutputLoad]'
- uuid: df0833759bae450e8125c3fb76519775
name: 'APC Smart-UPS RT 1000 RM XL: Voltage'
graph_items:
- color: 199C0D
item:
host: 'APC Smart-UPS RT 1000 RM XL by SNMP'
key: 'input.voltage[upsHighPrecInputLineVoltage]'
- sortorder: '1'
color: F63100
item:
host: 'APC Smart-UPS RT 1000 RM XL by SNMP'
key: 'output.voltage[upsHighPrecOutputVoltage]'